Intesis INBACRTR0320000 BACnet MS/TP to BACnet IP router Installation Guide
- June 7, 2024
- Intesis
Table of Contents
INBACRTR0320000
Intesis BACnet MS/TP to BACnet IP router
Order Code: INBACRTR0320000
** stands for the Intesis gateway capacity and varies depending on the
specific gateway acquired.
Installation Sheet rev.1.5
HMS Industrial Networks S.L.U ©
Owner’s Record
The serial number is located at the rear of the gateway.
Record this information in the space provided below.
Refer to it whenever you contact upon your gateway dealer or support team
regarding this product.
Serial No ………
SAFETY INSTRUCTIONS
WARNING
Follow carefully this safety and installation instructions.
Improper work may lead to serious harm to your health and may also damage
seriously the gateway and/or any other equipment connected to it.
The gateway must be installed by an accredited electrician or similar
technical personnel, following all the safety instructions given here and in
accordance always with the country legislation for installation of electric
equipment.
The gateway cannot be installed outdoors or exposed to direct solar radiation,
water, high relative humidity, or dust.
The gateway must only be installed in a restricted access location.
In case of wall mount, fix firmly the gateway on a not vibrating surface
following the instructions next.
In the case of the DIN rail, mount fix the gateway properly to the DIN rail
following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to the earth
is recommended.
Disconnect always a power of any wires before manipulating and connecting them
to the gateway.
A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV
rated is to be used.
Respect always the expected polarity of power and communication cables when
connecting them to the gateway.
Supply always a correct voltage to power gateway, see details of voltage range
admitted by the device in the technical characteristics below.
CAUTION: The device is to be connected only to networks without routing
to the outside plant, all communication ports are considered indoor only.
This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels above 4
kV, precautions should be taken when the device is mounted outside an
enclosure. When working in an enclosure (ex. making adjustments, setting
switches, etc.) typical anti-static precautions should be observed before
touching the unit.
Safety instructions in other languages can be found at:
https://intesis.com/docs/manuals/v6-safety
CONFIGURATION
Use the Configuration Tool to configure the gateway.
See instructions to download and install the latest version at:
https://intesis.com/docs/software/intesis-maps-installer
Use the Ethernet connection for communication between the gateway and the
configuration tool. See CONNECTIONS below and follow instructions of the
user’s manual for more details.
INSTALLATION
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to the gateway.
Disconnect the power of any bus or communication cable before connecting it to
the gateway.
Mount the gateway in a vertical position on the wall or DIN rail following the
instruction given below, respecting the safety instructions given above.
IMPORTANT: Connect an NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply to the gateway, respect the polarity if DC power or Line
and Neutral if AC power. This power supply must not be shared with other
devices. Apply always a voltage within the range admitted by the gateway and
of enough power (see technical characteristics).
Circuit-breakers must be used before the power supply. Rating 250V6A.
Connect the communication cables to the gateway, see details on the user’s
manual.
Power the gateway and the rest of the devices connected to it.
Wall Mount
- Separate the fixing clips in the bottom of the box, pushing them to the outside until hearing the “click” which indicates that now the clips are in position for wall mount, see in the figure below.
- Use the holes of the clips to fix the box in the wall using screws. Use the template below for the wall wholes.
DIN Rail Mount
With the clips of the box in their original position, insert first the box in the upper edge of the DIN rail and later insert the box in the down part of the rail, using a small screwdriver and following the steps in the figure below.
CONNECTIONS
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV-rated power
supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage
applied is within the range admitted (check table below). The power supply can
be connected to earth but only through the negative terminal, never through
the positive terminal.
Ethernet / BACnet IP
Connect the cable coming from the IP network to the connector ETH of the
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the
building, contact the network administrator and make sure traffic on the port
used is allowed through all the LAN path (check the gateway user manual for
more information). With factory settings, after powering up the gateway, DHCP
will be enabled for 30 seconds. After that time, if no IP is provided by a
DHCP server, the default IP 192.168.100.246 will be set.
Port BACnet MS/TP
Connect the EIA485 bus to connectors A3 (B+), A2 (A-), and A1 (SNGD) of the
gateway’s Port. Respect the polarity.
Note for MS/TP port; Remember the characteristics of the standard EIA485 bus:
maximum distance of 1200 meters, maximum 32 devices connected to the bus, and
in each end of the bus it must be a termination resistor of 120 Ω.
ELECTRICAL & MECHANICAL FEATURES
Enclosure| Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 93x53x58 mm
Recommended space for installation (dxwxh): 100x60x70mm
Color: Light Grey. RAL 7035
---|---
Mounting| Wall.
DIN rail EN60715 TH35.
Terminal Wiring(for power supply and low-voltage signals)| Per terminal: solid
wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm 2… 2.5mm2
2 cores: 0.5mm2 … 1.5mm2
3 cores: not permitted
Power| 1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
9-36 VDC / 24 VAC / 50-60 Hz / 0.140 A / 1.7 W
Ethernet| 1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Port| 1 x Serial EIA485 (Plug-in screw terminal block 3 poles)
A, B, SGND (Reference ground or shield)
1500VDC isolation from other ports
Operation Temperature| 0°C to +60°C
Operational Humidity| 5 to 95%, no condensation
Protection| IP20 (IEC60529)
This marking on the product, accessories, packaging or literature (manual)
indicates that the product contains electronic parts and they must be properly
disposed of by following the instructions at https://intesis.com/weee-
regulation
https://www.intesis.com
Rev.1.5
© HMS Industrial Networks S.L.U – All rights reserved.
This information is subject to change without notice.
References
- Waste Electrical and Electronic Equipment | Intesis
- intesis.com/docs/manuals/v6-safety
- Waste Electrical and Electronic Equipment | Intesis
- Intesis | Gateway solutions for Building Automation