Honeywell HM700A1000 Electrode Steam Humidifier Installation Guide

June 7, 2024
Honeywell

Honeywel logo

HM700A1000 Electrode Steam Humidifier
QUICK INSTALLATION GUIDE

This is a legacy product document supported by Resideo. It is no longer manufactured

TOOLS & SUPPLIES NEEDED

  • Screwdriver
  • Shut-off water valve
  • Wrench
  • Waterline (LDPE or Copper)
  • Pliers

MOUNTING

Requirements

  • Wall mount, minimum of 24 inches above the floor.
  •  The unit must be level.
  • The location must have ambient temp between 41° and 104° F.
  • The location must have a relative humidity of 5-95%.
  • Allow 36-inch front clearance.

Honeywell HM700A1000 Electrode -

Mounting Process

  1. Preparation: use #8 screws at least 2” (5 cm) in length. Mount on 2×4 studs (or stronger) vertical surface.

  2.  Install the rst screw at least 43.5 in. above the oor. Leave 1/4” (6 mm) of the shaft exposed for hanging the unit.
    Honeywell HM700A1000 Electrode - Mounting Process

  3. Hang unit from top screw using the key-hole on back and ensure it is level.
    Honeywell HM700A1000 Electrode - ensure it is leve

  4. Secure unit with the second screw driven through the hole at the bottom.
    Honeywell HM700A1000 Electrode - through hole at
bottom

PLUMBING

Supply Requirements

  • Use potable water;
  • DO NOT use reverse osmosis or de-ionized water.
  • Pressure: 30-100 PSI;
  •  Conductivity: 125-1250 microsiemens;
  • Temperature: 34-68° F (1-20° C).

Supply Plumbing

Honeywell HM700A1000 Electrode - Supply Plumbing

Drain Line Installation Process

Honeywell HM700A1000 Electrode - 2

Honeywell HM700A1000 Electrode - qr

ELECTRICAL

High Voltage Wiring
Requirements

  • The humidifier MUST be connected GFCI circuit.
  • 15 amp, 120/240-volt circuit required.
  • The local disconnect must be installed for future servicing.
  •  Wiring must be performed by a licensed electrician.

High Voltage Wiring Install Process
Hard wire the unit to local circuit disconnect as shown below.

  1. Connect ground to the peg at the right.
    Honeywell HM700A1000 Electrode - Supply Plumbing2

  2. Connect neutral to terminal 1 (or hot, in the case of 240 volt).
    Honeywell HM700A1000 Electrode - Connect neutra

  3.  Connect hot to terminal 5.
    Honeywell HM700A1000 Electrode - Connect hot

  4. Insert jumper wire:
    120 Volt: use the yellow jumper wire (supplied) to connect terminals 1 & 4.
    Honeywell HM700A1000 Electrode - Insert jumpe 120 Volt: use the yellow jumper wire (supplied) to connect terminals 1 & 2.
    Honeywell HM700A1000 Electrode - use the yellow

  5. Remove the ground wire screw from the case body.
    Honeywell HM700A1000 Electrode - Remove the ground

  6. Clip the other end of the green ground wire as close as possible to the drain valve. Remove the cut wire.
    Honeywell HM700A1000 Electrode - Remove the cut wir

Low Voltage Control Wiring
Requirements

  • 18 AWG solid wire minimum.
  • Keep control wires as short as possible.

Control Wiring
Standard wiring only includes connecting terminals 1 and 2 to the thermostat.
For details on other wiring configurations, please refer to the product manual.
Honeywell recommends that all installations use Air Proving to ensure steam is only distributed when the fan is active.

Honeywell HM700A1000 Electrode - Control Wiring

Honeywel logo

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com

®U.S. Registered Trademark
© 2016 Honeywell International Inc.
33-00162EFS—03 M.S. Rev. 08-16
Printed in United States