Honeywell LP9116 Pneumatic Remote Bulb Thermostats User Manual
- June 7, 2024
- Honeywell
Table of Contents
Honeywell LP9116 Pneumatic Remote Bulb Thermostats
GENERAL
The LP916A, B and C Remote Bulb Thermostats provide proportional control of induction units, fan coil units, and unit ventilators. Wide throttling range models are available for duct discharge control of heating and/ or cooling coils and mixed air dampers.
FEATURES
- A proportional two-pipe controller with a liquid filled remote bulb thermal element.
- An integral mounting bracket.
- A high impact styrene cover and a zinc plated base with a black phenolic knob.
- Scale plate available in several ranges.
- Protected barb connectors.
- External knob adjustment.
- A variety of mounting brackets available as accessories.
- A 36-inch (9-14mm)capillary length.
DESCRIPTION
The LP916A, B, and C Remote Bulb Thermostats provide proportional control of duct discharge of heating and/or cooling coils and mixed air dampers.
SPECIFICATIONS
Models:
- LP916A: Direct acting.
- LP916B: Direct acting at 18 psi (125 kPa) supply pressure. Reverse acting at 9 psi (60 kPa) or 13 psi (90 kPa) supply pressure. A switchover mechanism changes from direct to reverse acting with a change in main line pressure (for automatic changeover systems).
- LP916C: Reverse acting.
Maximum Safe Air Pressure:
25 psi (175 kPa).
Maximum Safe Temperature:
Duct-mounted models, 190F (88C); all others, 135F (57C).
Dimensions:
5 x 2-3/ 4 x 3 inches deep
Mounting:
Integral Mounting Bracket Model: Typically mounted inside a unit end
compartment. May also be duct mounted using mounting bracket AK3993.
Mounting Kit Model: May be mounted from the top directly or with mounting
bracket assemblies 316016A, B, or C.
Air Connections:
Two 1/4 in. (6 mm) push-on barbs. A convenient plug-in branchline pressure
gage port is provided on the front.
Fittings:
Integral Mounting Bracket Model: Hangers, mounting screws and tinnerman clips
are included with the device.
Mounting Kit Model: Ordered separately.
Accessories:
For Integral Mounting Bracket Model: AK3993 Duct
Mounting Bracket with sheet metal screws and foam gasket.
For Mounting Kit Model: Bag Assemblies 316016A and B with scale plate,
mounting bracket, bulb hangers, and mounting screws. Bag Assembly 316016C with
scale plate, knob and mounting screws.
Table 1. LP916 Specifications.
Model| Setpoint RangeF(C)| Scale/Marks| Throttling RangeF(C)| Restriction Size In.| Mounting Bracket| Bulb Size In.(mm)| NominalMLP
psi (kPa)
---|---|---|---|---|---|---|---
LP916A| 65-85(I8-29)| WARMER-COOLER/2F| 3.5 (2)
3.5 (2)
3.5 (2)
7 (3.5)
| 0.007| Integral| l/2×5-7/8(13×149)| 18(125)
| 65-85(18-29)| WARMER-COOLER/2F| 0.005| Not Included| 3/8 X 9-5/8(JO
X 244)| 18(125)
| 65-85(18-29)| WARMER-COOLER/2F| 0.005| Integral| 3/8 X 9-5/8(10 X
244)| 18(125)
| 40-80(4-27)| 40-50-60-70-80/2F| 0.007| Integral| 3/8 X 6-7/8(JO X
175)| 18(125)
LP916B| 65-85(I8-29)| WARMER-COOLER/2F| 3.5 (2)| 0.007| Integral Integral
Not Included Integral Integral
| l/2×5-7/8(13×149) l/2×5-7/8(13 X 149) 3/8 X 9-7/8(10 X 25J)
3/8 X 9-7/8(IO X 251)
3/8×9-7/8(10×251)
| 13-18(90-125)
| 65-85(18-29)| WARMER-COOLER/2F| *2(1)| 0.007| 9-18(60-125)
| 65-85(18-29)| None| 3.5 (2)| 0.005| 13-18(90-125)
| 65-85(18-29)| WARMER-COOLER/2F| 3.5 (2)| 0.005| 13-18(90-125)
| 65-85(18-29)| WARMER-COOLER/2F| 3.5(2)| 0.005| 13-18(90-125)
LP916C| 60-80(I6-27)| 60-80/lF| 3.5(2)| 0.007| Integral| 3/8×9-7/8(!Ox251)|
18(125)
| 65-85(I8-29)| WARMER-COOLER/2F| 3.5(2)| 0.007| Integral| l/2×5-7/8(13×149)|
18(125)
| 65-85(18-29)| WARMER-COOLER/2F| 3.5 (2)| 0.005| Integral| 3/8 X 9-7/8(
JO X 251)| 18(125)
| 40-80(4-27)| 40-50-60-70-80/2F| 7(3.5)| 0.007| Integral| 3/8 X
6-7/8(!Ox175)| 18(125)
*Throttling range for 3 to 9 psi (21 to 60 kPa) branchline pressure.
In the USA: Honeywell Plaza, Minneapolis, Minnesota 5 5408 In Canada:
Scarborough, Ontario MIP 2V9
Subsidiaries and Affiliates Around the World
Printed in USA
Documents / Resources
|
Honeywell LP9116 Pneumatic Remote Bulb
Thermostats
[pdf] User Manual
Pneumatic Remote Bulb Thermostats
---|---
Read User Manual Online (PDF format)