PRODUCT SPECIFICATION SHEET
The CM701 thermostat is designed to provide automatic time and temperature
control of heating systems in villas and apartments.
It can be used as part of a system in conjunction with combi boilers, oil-
burners and gas-fired boilers, circulation pumps, thermal actuators, zone
valves and electric heat systems (<5A).
The CM701 is designed with the installer in mind and includes a molded back-
plate with trunking guides and wiring breakouts to make installation quick and
easy.
The CM701 large LCD display, button layout based on the same simple
programming philosophy used on our acclaimed CM20 products and the
introduction of an ‘OK’ button makes it easier to install and more user-
friendly.
The unit is ideal for consumers who want reliable precise temperature control
from a modern looking, simple to program, and easy to use the product.
FEATURES
- Attractive slim, modern styling makes it ideal for location in any type of home.
- 24-hour heating program.
- Up to 4 daily independent time and temperature level changes let you set 4 time and temperatures pairs to suit your lifestyle.
- Temporary programmed temperature override to temporarily override the programmed temperature till the next switch point.
- Room Temperature Enquiry.
- EEPROM memory holds the user program indefinitely.
- The OFF mode has an integral frost protection setting at a minimum 5°C (installer adjustable) so that pipes in the house will never freeze in winter.
- 24…230V 5A resistive, 2A inductive SPDT relay provides compatibility with most domestic central heating systems reducing the need to stock many different models.
- Battery-powered by 2 x AA size (LR6) alkaline cells.
- Minimum battery life of 2 years with low battery warning indicator.
- Built-in default heating program.
- Surface or wall box mounting options, with trunking guides and wiring breakouts to simplify installation.
- No installer links or special installer switches on the back of the unit mean no adjustment is required for combi boilers and most domestic central heating systems.
- User Set-Up Mode allows extra functions to be set at the discretion of the user:
- AM-PM or 24hr time display.
- Resetting the heating profile to factory default.
- Installer Set-Up Mode allows extra functions to be set at the discretion of the installer to match the consumer’s applications and needs:
- Pump Exercise.
- Upper / Lower Setpoint Limit Adjust.
- Temperature offset.
- Minimum ON time.
- Cycle rate.
- Proportional Band Width.
- Diagnostic Mode to assist in faultfinding.
CONTROLS / DISPLAY LAYOUT
PRODUCT LAYOUT:
1. LCD Screen
2. Battery Low Indicator
3. Time Display
4. Burner On Indicator
5. Temperature Display
6. Temperature Change Buttons
7. Information Enquiry Button| 8. Operating Mode Buttons
9. Green OK Button
10. Battery Compartment
11. Battery Cover
12. Program Buttons
13. Time Change Buttons
---|---
SPECIFICATIONS
Batteries :
Battery life:
Battery replacement :
Switch type:
Electrical rating: Time display :
Time keeping accuracy :
Program :
Time setting resolution :
Sensing element :
Temperature setting range :| 2 x 1.5 V IEC LR6 (AA) Alkaline cells
Minimum 2 years
Program retained in EEPROM
SPDT (potential free)
230 V~, 50…60 Hz, 0.1 A to 5 A resistive 0.1 A to 2 A inductive (0.6 pf) 24
V~, 50…60 Hz, 0.5 A to 5 A resistive 0.5 A to 2 A inductive (0.6 pf)
24 hour or 12 hour AM/PM format
Typically better than 10 minutes per year
4 daily time and temperature level changes
Time of day – 1 minute , Program – 10-minute steps
100K (@ 25 oC ) NTC thermistor
Program: 5 to 35 o C in 0.5 o C steps Frost o: 5 C or equal to ower limit o (5
C to 21 o C).
---|---
Temperature control accuracy| ±0.5 K (nominal) @ 20 o C, 50% load 3 K ∆/hour
---|---
Room Temperature display range| From 0 o C to 50 o C
Control form| P + I (Proportional + Integral)
Minimum ON time| 10% of cycle time (min one minute), adjustable to 2 to 5 min
(see installer set up)
Cycle rate| Selectable by application (see installer set up)
Wiring| Terminal block capable of accepting wires up to 2.5 mm 2
Wire access| Mains wiring – rear right.
Low voltage wiring – rear right.
Dimensions| 133 x 88.5 x 26 mm (w x h x d)
130 x 175 x 26 mm (w x h x d)flap open)
Environmental| Operating temperature range 0 to 40 o C Shipping and storage
temperature range -20 to 55 o C
Humidity range 10 to 90% rh, noncondensing
Approvals| Designed to meet European EN
approvals EN60730-1(Nov 2000),
EN55014-1 (1997), EN55014-2 (2000)
INSTALLER SET-UP
To enter the installer set-up mode:
a) Press the OFF button.
b) Press and hold the INFO i button and the two program buttons ‘< >’
together.
c) The unit will display the first parameter of installer parameter group
category 1 (from n.1 to n.19).
d) Press the TEMP or buttons to change the factory setting. The display will
flash indicating that a change has been made.
e) Press the green OK button to confirm this change and the display will stop
flashing.
f) Press the + button to go to the next parameter.
g) Press the program button > to go to category 2 in the Installer mode (from
n.1 to n.5).
h) To exit the installer mode, press the AUTO, MAN or OFF buttons.
In Installer set-up we can:
- Set-up specific applications
- Enable special features
Specific Applications | Setting | What do you need to change? |
---|---|---|
Cycle/ Hour | Minimum ON time | |
(in minutes) | Note : |
a.To change Cycle/Hour, please go to parameter n. 2, category 2 in the
installer set-up mode.
b.To change Minimum ON Time, please go to parameter n. 1, category 2 in the
installer set-up mode.
Heating| Gas Boilers (<30KW)| 6| 1| No action required
| Oil Boiler| 3| 4| 1.Set Minimum ON Time to 4 minutes.
2.Set Cycle/Hour to 3.
| Thermal Actuator| 12| 1| Set Cycle/Hour to 12.
| Zone valve| 6| 1| No action is required.
| Electric heating (for applications <5A)| 12| 1| 1. Set Cycle/Hour to 12.
Special Features| Description| What to do if we wish this feature
---|---|---
AM-PM/ 24hr Display| Change display format (default 24hr).| Set parameter n.1,
category 1 in the installer set-up mode to 12.
Pump exercise| When enabled the Pump Exercise will switch the relay on for 1
minute at 12:00 if the relay has not been switched on since 12:00 the previous
day.
While in Holiday mode the Pump Exercise feature, if enabled, will operate.|
Set parameter n.5, category 2 in the installer set-up mode to 1.
Upper-Temperature Limit| The normal upper-temperature limit of 35°C can be
reduced down to 21 °C to save the homeowner energy. Useful if the homeowner
rents to tenants.| Set parameter n.6, category 1 in the installer set-up mode
to the desired limit.
Lower Temperature Limit| The normal lower temperature limit of 5°C can be
increased up to 21 °C to protect the inhabitants from cold. Useful if the
inhabitants include the elderly, children or disabled.| Set parameter n.7,
category 1 in the installer set-up mode to the desired limit.
Temperature Offset| If the thermostat is located in a hot/cold location and
cannot be moved because of wiring then the measured/ displayed temperature can
be adjusted by +/- 3°C. Useful if the homeowner wants the reading to match
another appliance temperature display.| Set parameter n.12, category 1 in the
installer set-up mode to the desired offset value.
Proportional Band Width| Can be adjusted up to 3°C (default is 1.5 °C) to
provide better temperature control (less overshoot).
Useful for:
a.Well insulated homes with oversized heating systems.
b.Air systems with fast response.| Set parameter n.13, category 1 in the
installer set-up mode to the desired value.
Parameter| Installer Set-Up Number / Abbreviation (Press + or – keys to
select)| Factory Setting| Optional Setting| Installer Set-
Up Category
(Press PROG keys i< or >’ to select)
---|---|---|---|---
| | Display| Description| Display/Setting| Description|
Category 1: Thermostat Parameters
AM-PM / 24hr Display| 1:C1| 24| 24 hr clock display| 12| 12 hrAM /
PMdcckcisplay| 1
RESET Time / Temperature Program| 2:rP| 1| Time / Temperature profile set to
factory default
Changes to 0 when one of the time/temp profiles are changed| 0
1| Time / Temperature is as programmed
To restore the factory profile set to 1| 1
Upper-Temperature Limit| 6:uL| 35| 35°C Upper Temp. Limit| 21 to 34| 21°C to
34°C adjustments in 1°C steps| 1
Lower Temperature Limit| 7:LL| 5| 5°C Lower Temp. Limit| 6 to 21| 6°C to 21°C
adjustments in 1°C steps| 1
Temperature Offset| 1210| 0| No offset| -3 to +3| -3°C to 4-3°C adjustment in
0.1°C steps| 1
Proportional Eland Width| 13:Pb| 2.| 1.5°C Proportional Band| 1.6 to 3.0|
1.6°C to 3.0t
adjustment in 0.1°C steps| 1
Reset Parameters to Factory
Defaults| 19:FS| 1| All settings held are the factory defaults. Changes to 0
when one of the
parameter values are changed| 0
1| Settings are as modified above
To restore the factory profile set to 1| 1
‘Category 2: System Parameters (You must press the 5.’ program key to enter
this section)
Minimum ON Time| 1:01| 1| 1 minute minimum ON time| 2 to 5| 2 – 2 minutes
3 – 3 minutes
4 – 4 minutes
5 – 5 minutes| 2
Cycle Rate| 2:Cr| 6| 6 cycles per hour (mph) for gas boilers. zone valves and
fan-coil| 3/9/12| 3 – 3 cph
9 – 9cph
12 – 12 cph| 2
Pump Exercise| 5:PE| 0| Pump Exercise Disabled| 1| Pump Exercise Enabled| 2
DIMENSIONS
INSTALLATION
LOCATION
The CM701 thermostat is the control element of the heating system and,
therefore, MUST be located in a position with good air circulation, at average
room temperature, and on an inside wall, 1.5 meters above the floor level. Do
not position the CM701 thermostat near sources of heat (radiators, hot-air
vents, TV or lights), near doors or windows, or indirect sunlight.
MOUNTING
The CM701 thermostat can be mounted directly on the wall surface or onto an
electrical wall box.
WIRING
The CM701 thermostat is designed for fixed wiring only and must be installed
in accordance with the latest l.E.E. regulations. Ensure the wiring connection
to the supply is via a fuse rated at no more than 5 amps and a Class “A”
switch (having a contact separation of at least 3 mm in all poles).
IMPORTANT
- The installer must be a trained service engineer
- Disconnect the power supply before beginning installation
WIRING
ORDERING SPECIFICATION
Description | Model | Logo | Literature | Spec Sheet |
---|---|---|---|---|
1-day programmable thermostat | CMT701A1006 | Honeywell | French, Dutch, Italian, | |
Spanish, German, Portuguese. | ENOH8543 |
Honeywell Control Systems Limited
Newhouse Industrial Estate
Motherwell ML1 5SB
United Kingdom
http://europe.hbc.honeywell.com
EN0H 8543 UK07 R08/05
https://thermostat.guide/honeywell/honeywell-home-cm701-programmable- thermostat-user-guide/
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>