Honeywell Home T1 Pro Non-Programmable Thermostat Installation Guide

June 6, 2024
Honeywell Home

Honeywell Home T1 Pro Non-Programmable Thermostat Installation Guide
Honeywell Home T1 Pro Non-Programmable Thermostat

Package Includes

  • T1 Pro Thermostat
  • UWP Mounting System
  • Decorative Cover Plate
  • Screws and Anchors
  • 2 AA Batteries
  • Thermostat Literature

Optional Cover Plate installation

NOTE: If Optional Cover Plate is not required, see “UWP Mounting System installation”.

Use the Optional Cover Plate when you need to cover paint gap from old thermostat.

There are different cover plates depending on when the thermostat was manufactured.

For the square cover plate:

  1. Separate the Cover Plate from Mounting Plate.
    Optional Cover Plate installation

  2. Mount the Mounting Plate on to the wall using any of the 8 screw holes. Insert and tighten mounting screws supplied with Cover Plate Kit. Do not overtighten. See Figure 2. Make sure the Mounting Plate is level.
    Optional Cover Plate installation

  3. Attach the UWP by hanging it on the top hook of the Mounting Plate and then snapping the bottom of the UWP in place. See Figure 3.
    Optional Cover Plate installation

  4. Snap the Cover Plate onto the Mounting Plate. See Figure 4.
    Optional Cover Plate installation

For the rectangular cover plate:

  1. Mount the Cover Plate on the wall using any of the 6 screw holes. Insert and tighten the mounting screws supplied with the Cover Plate. Do not overtighten. See Figure 1
    Rectangular Cover Plate
    Make sure the Cover Plate is level. Attach the UWP by hanging it on the top hook of the Cover Plate and then snapping the bottom of the UWP in place. See Figure 2.
    Rectangular Cover Plate

  2. If there are no existing wall anchors:

  3. Position the Cover Plate on wall. Level and mark hole positions.

  4. Drill holes at marked positions, and then lightly tap supplied wall anchors into the wall using a hammer.

  * If your box contains red anchors, drill 7/32” (5.6 mm) holes.
  * If your box contains yellow anchors, drill 3/16” (4.8 mm) holes.
  * Use 2x supplied screws (#8 1-1/2” (38 mm) for red anchors and #6 1-1/2” (38 mm) for yellow anchors).

UWP Mounting System installation

  1. Before starting, turn the power off at the breaker box or switch. Open package to find the UWP. See Figure 1.
    UWP Mounting System installation

  2. Position the UWP on wall. Level and mark hole positions. See Figure 2.
    UWP Mounting System installation
    Drill holes at marked positions, and then lightly tap supplied wall anchors into the wall using a hammer.

    • If your box contains red anchors, drill 7/32” holes.
    • If your box contains yellow anchors, drill 3/16” holes.
  3. Pull the door open and insert the wires through wiring hole of the UWP. See Figure 3.
    UWP Mounting System installation

  4. Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not overtighten. Tighten until the UWP no longer moves. Close the door. See Figure 4.
    UWP Mounting System installation

Power options

  • Insert R and C wires into designated terminals for primary AC power (C terminal is optional if batteries are installed, but it is recommended). Remove wires by depressing the terminal tabs.
    Power options
    Power options

Setting Slider Tabs

Set R Slider Tab.

  • Use built-in jumper (R Slider Tab) to differentiate between one or two transformer systems.
  • If there is only one R wire, and it is connected to the R, Rc, or RH terminal, set the slider to the up position (1 wire).
  • If there is one wire connected to the R terminal and one wire connected to the Rc terminal, set the slider to the down position (2 wires).

NOTE: Slider Tabs for U terminals should be left in place for T1 Pro models.

UWP Mounting System

UWP Mounting System

R/Rc Slider Tab (built-in jumper)

UWP Wiring terminal designations

  • Y Compressor contactor (stage 1)

  • Y2 Not used for T1 thermostat.

  • G Fan Relay

  • C 24VAC common. For 2 transformer systems, use common wire from cooling transformer.

  • L/A – A Not used for T1 thermostat

  • O/B Changeover Valve (TH1110D only)

  • AUX -W2 Not used for T1 thermostat.

  • E Not used for T1 thermostat.

  • W Heat relay (stage 1)

  • K Not used for T1 thermostat.

  • R 24VAC power from heating transformer*

  • Rc 24VAC power from cooling transformer*

  • Terminal can be jumped using Slider Tab. See “Setting Slider Tabs” above.

UWP Wiring terminal designations

Note: Not all terminals may be used, depending on the system type that is being wired. The most commonly used terminals are shaded.

Wiring conventional systems: forced air and hydronics

Shaded areas below apply only to TH1110D.

1H/1C System (1 transformer)

  • R Power [1]
  • Rc [R+Rc joined by Slider Tab] [2]
  • Y Compressor contactor
  • C 24VAC common [3]
  • W Heat relay
  • G Fan relay

1H/1C System (2 transformers)

  • R Power (heating transformer) [1]
  • Rc Power (cooling transformer) [1]
  • Y Compressor contactor
  • C 24VAC common [3, 4]
  • W Heat relay
  • G Fan relay

Heat-only System

  • R Power [1]
  • Rc [R+Rc joined by Slider Tab] [2]
  • C 24VAC common [3]
  • W Heat relay

Heat-only System with Fan

  • R Power [1]
  • Rc [R+Rc joined by Slider Tab] [2]
  • C 24VAC common [3]
  • W Heat relay
  • G Fan relay

Heat-only System (Series 20) [5]

  • R Series 20 valve terminal “R” [1]
  • Rc [R+Rc joined by Slider Tab] [2]
  • Y Series 20 valve terminal “W”
  • C 24VAC common [3]
  • W Series 20 valve terminal “B”

Cool-only System

  • R Power [1]
  • Rc [R+Rc joined by Slider Tab] [2]
  • Y Compressor contactor
  • C 24VAC common [3]
  • G Fan relay

Heat-only System (power open zone valve) [5]

  • R Power [1]
  • Rc [R+Rc joined by Slider Tab] [2]
  • W Valve
  • C 24VAC common [3]

Wiring heat pump systems

1H/1C Heat Pump System

  • R Power [1]
  • Rc [R+Rc joined by Slider Tab] [2]
  • Y Compressor contactor
  • C 24VAC common [3]
  • O/B Changeover valve [7]
  • G Fan relay

NOTES

Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required.

  1. Power supply. Provide disconnect means and overload protection as required.
  2. Move R-Slider Tab on UWP to the R setting. For more information, see “Setting Slider Tabs” on page 3
  3. Optional 24VAC common connection.
  4. Common connection must come from cooling transformer.
  5. In ISU set Heat system type to Radiant Heat. Set number of cool stages to 0.
  6. In Installer Setup, set changeover valve to O (for cool changeover) or B (for heat changeover).

Thermostat mounting

Thermostat mounting

  1. Push excess wire back into the wall opening.
  2. Close the UWP door. It should remain closed without bulging.
  3. Align the UWP with the thermostat, and push gently until the thermostat snaps in place.
  4. Turn the power on at the breaker box or switch.

System operation settings

System operation settings

  1. Press the Menu to cause the Mode and Fan menus to appear.

  2. Press Mode ( ) to cycle through the available modes.
    NOTE: Available System modes vary by model and system settings. System modes:

    • Heat: Thermostat controls only the heating system.
    • Cool: Thermostat controls only the cooling system.
    • Off: Heating and cooling system is off. Fan will still operate if fan is set to On.

Fan operation settings

Fan operation settings

  1. Press Menu to cause the Mode and Fan menus to appear.

  2. Press Fan ( ) to cycle through Fan modes.
    NOTE: Available Fan modes vary with system settings.
    Fan modes:

    • Auto: Fan runs only when the heating or cooling system is on.
    • On: Fan is always on.

Installer setup (ISU)

  1. Press and hold Menu (center) for approximately 3 seconds to enter menu.
  2. Press Edit ( ) to change values within a setup option.
  3. Press Next ( ) to advance to the next setup option.
  4. Press Done to Save and return to the main menu screen.

NOTE: To keep the factory default settings, press to advance through the setup options. Once you pass the last option, the thermostat will automatically save and return you to the main menu.
NOTE: A complete list of all setup (ISU) parameters and options starts below and continues through.

Installer setup options (ISU)

NOTE: Depending on system settings, not all options may be available.

# ISU ISU Name ISU Options (factory default in bold)
125 Temperature Indication Scale 0 = Fahrenheit

1 = Celsius

200| Heating System Type| 1 = Conventional Forced Air Heat

2 = Heat Pump (TH1110D only) 3 = Radiant Heat

5 = None (Cool Only)

_ Note: This option selects the basic system type your thermostat will _control.

205| Heating Equipment Type| Conventional Forced Air Heat:

1 = Standard Efficiency Gas Forced Air

2 = High Efficiency Gas Forced Air

3 = Oil Forced Air

4 = Electric Forced Air 5 = Hot Water Fan Coil

Heat Pump:

7 = Air to Air Heat Pump

8 = Geothermal Heat Pump

Radiant Heat:

9 = Hot Water Radiant Heat

12 = Steam

Note: This option selects the equipment type your thermostat will control.

Note: This feature is NOT displayed if feature 200 is set to Cool Only.

218| Reversing Valve O/B| 0 = O (O/B in Cool)

1 = B (O/B in Heat)

_ Note: This option is only displayed if the Heat Pump configured. Select _whether reversing valve O/B should energize in cool or in heat.

220| Cool Stages / Compressor Stages 200=Conv / 200=HP| 0, 1

Note:
Select how many Cool or Compressor stages of your equipment the thermostat will control. Set value to 0 if you do not have Cool Stage/ Compressor Stage. This ISU will not be shown on TH1010D model.

221| Heat Stages| 0, 1

Note: Select how many Heat stages of your equipment the thermostat will control. This ISU will not be shown on TH1010D model.

230| Fan Control in Heat| 1 = Equipment Controls Fan

2 = Thermostat Controls Fan

Note: This ISU is only displayed if ISU 205 is set to Electric Forced Air or Fan Coil.

430| Minimum Cool Setpoint| 50 °F to 99 °F (50 °F)

10.0 °C to 37.0 °C (10.0 °C)

Note: The cool temperature cannot be set below this level. This ISU will not be shown on TH1010D model unless ISU 200 is set to 5 (cool only).

431| Maximum Heat Setpoint| 32 °F to 90 °F (90 °F)

0 °C to 32.0 °C (32 °C)

_ Note: The heat temperature cannot be set above this level. This ISU will _not be shown on TH1010D model unless ISU 200 is not set to 5 (cool only).

1400| Backlighting| 0 = On Demand

1 = Continuous

Note: Common wire needed for continuous. This ISU will not be shown if the device is powered only by battery.

1420| Temperature Display Offset| -3 to 3F (0)

-1.5 to 1.5C (0)

Note: 0 °F – No difference in displayed temperature and the actual room temperature. The thermostat can display up to 3 °F (1.5 C) lower or higher than the actual measured temperature.

Specifications

  • Temperature Ranges
    Heat: 32 °F to 90 °F (0 °C to 32.0 °C)
    Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)

  • Operating Ambient Temperature
    32 °F to 102 °F (0 °C to 38.9 °C)

  • Shipping Temperature
    -20 °F to 120 °F (-28.9 °C to 48.9 °C)

  • Operating Relative Humidity
    5% to 90% (non-condensing)

  • Physical Dimensions in inches (mm) (H x W x D)
    4-1/16” H x 4-1/16” W x 1-5/32” D
    103.5 mm H x 103.5 mm W x 29 mm D

Electrical Ratings

Terminal Voltage (50/60Hz) Running Current
W Heating 20-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
Y Compressor Stage 1 20-30 Vac 0.02-1.0 A
G Fan 20-30 Vac 0.02-0.5 A
O/B Changeover (TH1110D only) 20-30 Vac 0.02-0.5 A

CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly

CAUTION: MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.

CAUTION: ELECTRONIC WASTE NOTICE
The product should not be disposed of with other household waste. Check for the nearest authorized collection centers or authorized recyclers. The correct disposal of end-of-life equipment will help prevent potential negative consequences for the environment and human health.

FCC statement at:
https://customer.resideo.com/en-US/support/residential/codes-and- standards/FCC15105/Pages/default.aspx

Customer assistance

For assistance with this product, please visithoneywellhome.com/support

Thermostat
Pull to remove the thermostat from the UWP.

resideo Logo
www.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
https://www.honeywellhome.com/support
33-00189EFS—09 M.S. Rev. 09-20 | Printed in United States

© 2020 Resideo Technologies, Inc. All rights reserved.