GENERAC Standby Generators Liquid-Cooled Gaseous Engine User Guide

June 6, 2024
Generac

Standby Generators Liquid-Cooled Gaseous Engine

Standby Generators

Standby Generators

Standby Generators Liquid-Cooled Gaseous Engine

1 of 9

INCLUDES: · Two Line LCD Tri-Lingual Digital NexusTM
Controller · Isochronous Electronic Governor · Sound Attenuated Enclosure

Standby Power Rating
Model QT070 (Aluminum – Bisque) – 70 kW 60 Hz Model QT080 (Aluminum – Bisque) – 80 kW 60 Hz Model QT100 (Aluminum – Bisque) – 100 kW 60 Hz Model QT130 (Aluminum – Bisque) – 130 kW 60 Hz Model QT150 (Aluminum – Bisque) – 150 kW 60 Hz

· Closed Coolant Recovery System

· Smart Battery Charger

· UV/Ozone Resistant Hoses

· ±1% Voltage Regulation

· Natural Gas or LP Operation

· 2 Year Limited Warranty

· UL 2200 Listed

*Built in the USA using domestic and foreign parts
Meets EPA Emission Regulations 70, 100, 130 & 150 kW meet CA/MA emissions requirement with optional catalyst
80 kW not for sale in CA/MA

FEATURES

¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.

¡ TEST CRITERIA: PROTOTYPE TESTED SYSTEM TORSIONAL TESTED

NEMA MG1-22 EVALUATION MOTOR STARTING ABILITY

¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Digital voltage regulation at ±1%.
¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
¡ GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.

ISO
9 0 0 1: 2008

Standby Generators

70 · 80 · 100 · 130 · 150 kW

application & engineering data

GENERATOR SPECIFICATIONS
Type Rotor Insulation Class Stator Insulation Class 2 of 9 Telephone Interference Factor (TIF) Alternator Output Leads 1-Phase
Alternator Output Leads 3-Phase
Bearings
Coupling
Excitation System
VOLTAGE REGULATION
Type Sensing Regulation
GOVERNOR SPECIFICATIONS
Type Frequency Regulation Steady State Regulation

Synchronous H H
<50 4 wire 6 wire (70, 80 & 150 kW) or 12 wire (100 & 130 kW) Sealed Ball Flexible Disc (70, 80 & 150 kW) or Gear Drive (100 & 130 kW) Brushless
Electronic Single Phase
± 1%
Electronic Isochronous
± 0.25%

ENGINE SPECIFICATIONS: 80 kW
Make Model Cylinders Displacement (Liters) Bore (in/mm) Stroke (in/mm) Compression Ratio Intake Air System Lifter Type

Generac V-Type 8 5.4
3.55/90.2 4.17/105.9
9:1 Naturally Aspirated
Hydraulic

ENGINE SPECIFICATIONS: 70, 100, 130 & 150 kW

Make

Generac

Model

V-Type

Cylinders

10

Displacement (Liters)

6.8

Bore (in/mm)

3.55/90.2

Stroke (in/mm)

4.17/105.9

Compression Ratio

9:1

Intake Air System

Naturally Aspirated

Lifter Type

Hydraulic

ELECTRICAL SYSTEM
Battery Charge Alternator Static Battery Charger
Recommended Battery (battery not included)
System Voltage

12 Volt 30 Amp 2 Amp
Group 24F, 525 CCA (70, 80 & 150 kW)
or Group 27F, 700 CCA (100 & 130 kW) 12 Volts

GENERATOR FEATURES
Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 °C above a 40 °C ambient Class H insulation is NEMA rated All models fully prototyped tested

ENCLOSURE FEATURES

Aluminum weather protective enclosure

Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.

Enclosed critical grade muffler

Quiet, critical grade muffler is mounted inside the unit to prevent injuries.

Small, compact, attractive Makes for an easy, eye appealing installation.

SAE

Sound attenuated enclosure ensures quiet operation.

ENGINE LUBRICATION SYSTEM
Oil Pump Type Oil Filter Type Crankcase Capacity (qt/l)
ENGINE COOLING SYSTEM
Type Water Pump
Fan Speed (rpm)
Fan Diameter (in/mm)
Fan Mode
FUEL SYSTEM
Fuel Type Carburetor Secondary Fuel Regulator Fuel Shut Off Solenoid Operating Fuel Pressure

Gear Full flow spin-on cartridge 5/4.7 (70, 100, 130 & 150 kW)
or 6/5.7 (80 kW)
Closed Belt driven 2300 – 70 kW 2174 – 80 kW 1670 – 100 kW 1950 – 130 kW 2200 – 150 kW 22/558.8 (70 kW) or 26/660.4 (80, 100, 130 & 150 kW) Pusher (70 kW) or Puller (80, 100, 130 & 150 kW)
Natural gas, propane vapor Down Draft Standard Standard
11-14″ water column/21-26 mm HG

(All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271)

Standby Generators

70 · 80 · 100 · 130 · 150 kW

GENERATOR OUTPUT VOLTAGE/kW – 60 Hz

kW LPG

120/240 V, 1Ø, 1.0 pf

67

120/208 V, 3Ø, 0.8 pf

70

QT070

120/240 V, 3Ø, 0.8 pf

70

277/480 V, 3Ø, 0.8 pf

70

120/240 V, 1Ø, 1.0 pf

77

120/208 V, 3Ø, 0.8 pf

80

QT080

120/240 V, 3Ø, 0.8 pf

80

277/480 V, 3Ø, 0.8 pf

80

120/240 V, 1Ø, 1.0 pf

100

120/208 V, 3Ø, 0.8 pf

100

QT100

120/240 V, 3Ø, 0.8 pf

100

277/480 V, 3Ø, 0.8 pf

100

120/240 V, 1Ø, 1.0 pf

130

120/208 V, 3Ø, 0.8 pf

130

QT130

120/240 V, 3Ø, 0.8 pf

130

277/480 V, 3Ø, 0.8 pf

130

120/240 V, 1Ø, 1.0 pf

144

120/208 V, 3Ø, 0.8 pf

150

QT150

120/240 V, 3Ø, 0.8 pf

150

277/480 V, 3Ø, 0.8 pf

150

Amp LPG 292 243 211 105 333 278 241 120 417 347 301 150 542 451 391 195 625 520 451 225

kW Nat. Gas 64 67 67 67 77 80 80 80 89 94 94 94 117 122 122 122 136 142 142 142

operating data

Amp Nat. Gas

CB Size (Both)

267

300

232

300

201

250

101

125

3 of 9

333

400

278

300

240

300

120

150

371

450

326

400

283

350

141

175

488

600

423

500

367

450

183

225

567

700

493

600

427

500

214

250

SURGE CAPACITY IN AMPS

ENGINE FUEL CONSUMPTION

QT070 QT080 QT100 QT130 QT150

120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø 120/240 V, 1Ø 120/208 V, 3Ø 120/240 V, 3Ø 277/480 V, 3Ø

Voltage Dip @ < .4 pf

15%

30%

129

356

194

471

168

408

83

201

174

435

186

466

161

404

70

175

150

413

186

452

161

392

107

261

236

648

364

885

315

767

161

390

486

1214

534

1334

463

1156

250

624

Note: Fuel pipe must be sized for full load. For Btu content, multiply gal/hr x 90950 (LP) or ft3/hr x 1000 (NG).

QT070 QT080 QT100 QT130 QT150

Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load

Natural Gas

(ft³/hr) (m³/hr)

110

3.1

260

7.4

500

14.2

696

19.8

1020

29

95

2.7

549.5 15.6

784.4 22.2

1024.8 29.0

1252.2 35.5

130

3.7

371

10.5

713

20.3

991

28.2

1260 35.8

135

3.8

482

13.7

927

26.3

1292 36.7

1786 50.8

155

4.4

556

15.8

1070 30.4

1491 42.4

2061 58.6

For megajoule content, multiply l/hr x 25.35 (LP) or m³/hr x 37.26 (NG).

Refer to “Emissions Data Sheets” for maximum fuel flow for EPA and SCAQMD permitting purposes.

(gal/hr)
1.2 2.85 5.46 7.62 11.17 1.4 3.46 6.62 9.24 12.78 1.4 4.1 7.9 11 13.9 1.4 5.3 10.3 14.3 19.8 1.7 6.09 11.72 16.33 22.57

Propane (l/hr) 4.6 10.8 20.8 29.1 42.6 5.51 13.11 25.1 34.96 48.38 5.4 15.5 29.8 41.5 52.6 5.7 20 38.7 54 74.6 6.5 23.2 44.7 62.3 86.1

(ft3/hr)
44 104 200 280 411 53 126 241 336 465 52 149 287 400 507 55 193 373 520 719 63 224 431 600 830

STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.

Standby Generators

70 · 80 · 100 · 130 · 150 kW

operating data

ENGINE COOLING

Air flow (inlet air including alternator and combustion air in ft³/min)

System coolant capacity (gal/liters)

4 of 9

Heat rejection to coolant (BTU/hr)

Maximum operation air temperature on radiator (°C/°F)

Maximum ambient temperature (°C/°F)

70 kW 5200/147.2
4.5/17 287,000/302.8

80 kW 5300/150.1
4/15.1 316,000/333.4

100 kW 5500/155.7
4.5/17 342,000/360.8
60/150 50/140

130 kW 6450/182.6
4.5/17 496,000/523.3

150 kW 7800/220.9
4.5/17 568,000/599.3

COMBUSTION REQUIREMENTS

Flow at rated power (cfm/cmm)

205/5.8

143/4

262/7.4

336/9.5

410/11.6

SOUND EMISSIONS

Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode*

64

65

68

69

66

Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load*

72

74

72

75

79

*Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.

EXHAUST

Exhaust flow at rated output (cfm/cmm) Exhaust temperature at muffler outlet (°C/°F)

557/15.8 477/890

720/20.4 796/1465

888/25.1 516/960

1119/31.7 521/970

1535/43.5 593/1100

ENGINE PARAMETERS

Rated Synchronous rpm

1800

3600

2300

2970

3600

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration ……………………………………………………………………………………………..3% for every 10 °C above 25 °C or 1.65% for every 10 °F above 77 °F Altitude Deration (70,100,130 & 150)………………………………………………………………………1% for every 100 m above 183 m or 3% for every 1000 ft above 600 ft Altitude Deration (80 kW) …………………………………………………………………………………… 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft
CONTROLLER FEATURES
2-Line Plain Text LCD Display ……………………………………………………………………………………………………………………….Simple user interface for ease of operation. Mode Switch: Auto …………………………………………………………………………………………………………………………….Automatic Start on Utility failure. 7 day exerciser
Off……………………………………………………………………………………………………………Stops unit. Power is removed. Control and charger still operate. Manual…………………………………………………………………………….. Start with starter control, unit stays on. If utility fails, transfer to load takes place. Programmable start delay between 10-30 seconds ………………………………………………………………………………………………………………………………………… Standard Engine Start Sequence……………………………………………………………………………………………………… Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration) Engine Warm- up…………………………………………………………………………………………………………………………………………………………………………………………… 5 sec Engine Cool-Down …………………………………………………………………………………………………………………………………………………………………………………………1 min Starter Lock-out ………………………………………………………………………………………………………………..Starter cannot re-engage until 5 sec after engine has stopped. Smart Battery Charger ……………………………………………………………………………………………………………………………………………………………………………….. Standard Automatic Voltage Regulation with Over and Under Voltage Protection……………………………………………………………………………………………………………….. Standard Automatic Low Oil Pressure Shutdown …………………………………………………………………………………………………………………………………………………………. Standard Overspeed Shutdown ………………………………………………………………………………………………………………………………………………………………………. Standard, 72 Hz High Temperature Shutdown……………………………………………………………………………………………………………………………………………………………………….. Standard Overcrank Protection …………………………………………………………………………………………………………………………………………………………………………………. Standard Safety Fused……………………………………………………………………………………………………………………………………………………………………………………………. Standard Failure to Transfer Protection………………………………………………………………………………………………………………………………………………………………………. Standard Low Battery Protection……………………………………………………………………………………………………………………………………………………………………………….. Standard 50 Event Run Log……………………………………………………………………………………………………………………………………………………………………………………… Standard Future Set Capable Exerciser………………………………………………………………………………………………………………………………………………………………………. Standard Incorrect Wiring Protection…………………………………………………………………………………………………………………………………………………………………………. Standard Internal Fault Protection …………………………………………………………………………………………………………………………………………………………………………….. Standard Common External Fault Capability……………………………………………………………………………………………………………………………………………………………….. Standard Governor Failure Protection………………………………………………………………………………………………………………………………………………………………………… Standard

Standby Generators

70 · 80 · 100 · 130 · 150 kW

available accessories

Model #
G006463-4
G006478-0
G005632-1 – 70, 80 & 150 kW G005633-0 – 100 & 130 kW G005620-0 – 70, 100 & 130 kW G006204-0 – 80 kW G005667-0 – 150 kW

Product Mobile LinkTM

Description

Generac’s Mobile Link allows you to check the status of your generator

from anywhere that you have access to an Internet connection from a

PC or with any smart device. You will even be notified when a change in

the generator’s status occurs via e-mail or text message. Note: Harness

5 of 9

Adapter Kit required. Available in the U.S. only.

Harness Adapter Kit

The Harness Adapter Kit is required to make liquid-cooled units compatible with Mobile LinkTM.

Cold Weather Kit

If the temperature regularly falls below 32 °F (0 °C), install a cold weather kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap.

Extreme Cold Weather Recommended where the temperature regularly falls below 32 °F (0 °C)

Kit

for extended periods of time. For liquid cooled units only.

G005651-0

Base Plug Kit

Add base plugs to the base of the generator to keep out debris.

G005703-0 G005660-0 – 70, 100, 130, and 150 kW G006915-0 – 80 kW G006664-0 G006665-0
G006873-0
G007005-0
G006510-0

Paint Kit

If the generator enclosure is scratched or damaged, it is important to touch- up the paint to protect from future corrosion. The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure.

Scheduled Maintenance Kit

The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform complete maintenance on Generac liquid-cooled generators.

Completely wireless and battery powered, Generac’s wireless remote Local Wireless Monitor monitor provides you with instant status information without ever
leaving the house.

Wireless Remote Extension Harness

Recommended for use with the Wireless Remote on units up to 60 kW, required for use on units 70 kW or greater.

Smart Management Module (50 Amps)
Wi-Fi LP Fuel Level Monitor
E-Stop

Smart Management Modules are used in conjunction with the Automatic Transfer Switch to increase its power management capabilities. It provides additional power management flexibility not found in any other power management system.
The Wi-Fi enabled LP fuel level monitor provides constant monitoring of the connected LP fuel tank. Monitoring the LP tank’s fuel level is an important step in making sure your generator is ready to run during an unexpected power failure. Status alerts are available through a free application to notify when your LP tank is in need of a refill.
E-stop allows for immediate fuel shutoff and generator shutdown in the event of anemergency.

Standby Generators

70 · 80 · 100 · 130 · 150 kW
Drawing #0H7452-D
6 of 9

(IF EQUIPPED)

interconnections

70 kW

installation layout
Drawing #0F6287-E
7 of 9

DIMENSIONS: MM [INCH]

Standby Generators

80 kW
Drawing #0L3178-B
8 of 9

Standby Generators

RADIATOR/EXHAUST DISCHARGE AIR (BOTH SIDES)

BATTERY 12V GROUP 26
NEGATIVE GROUND P/N: 058208

A_1

1422 [56] CENTER OF GRAVITY
SEE NOTE 5
AIR INTAKE (BOTH SIDES)

REMOVE COVER FOR ACCESS TO RADIATOR FILL CAP

LOW VOLTAGE

AREA ONLY 91

TOP VIEW

[3.6] 206 [8.1]

872 [34.3]

SERVICE ITEM OIL FILL CAP OIL DIP STICK OIL FILTER OIL DRAIN HOSE RADIATOR DRAIN HOSE AIR CLEANER ELEMENT SPARK PLUGS
MUFFLER FAN BELT BATTERY

5.4L LEFT DOOR LEFT DOOR LEFT DOOR RIGHT DOOR LEFT DOOR EITHER DOOR EITHER DOOR SEE NOTE 12 EITHER DOOR RIGHT DOOR

REFERENCE OWNERS MANUAL FOR PERIODIC REPLACEMENT PART LISTINGS.

STUB-UP AREA SEE NOTE 4

128 [5.0]

86 [3.4]

EXHAUST MUFFLERS & FAN BELT ENCLOSED WITHIN SEE NOTE 12

CONTROL PANEL BATTERY CHARGER IS ENCLOSED WITHIN.

NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1241 (49″) WIDE 3228 (127″) LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION: – SEE SPECIFICATION SHEET OR OWNERS MANUAL – ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. INSIDE STUB-UP AREA FOR AC LOAD LEAD CONDUIT CONNECTION, NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (.5 AMP MAX) CONNECTION AND ACCESS TO TRANSFER SWITCH CONTROL WIRES. REMOVE FRONT COVER FOR ACCESS.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. 6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. 7. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 24 INCHES H2O. 8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 9. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS) 10. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. 11. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. 12. REMOVE EITHER LEFT OR RIGHT HAND SIDE PANEL TO ACCESS EXHAUST MUFFLERS
AND FAN BELT. 13. FIELD CUT HOLE IS ONLY REQUIRED FOR MOUNTING OF GENERATOR ON AN EXISTING
PAD.
VISE ACTION LATCH, ONE PER DOOR, TWO LIFT-OFF DOORS PER SIDE OF GENERATOR.

RADIATOR/ EXHAUST DISCHARGE AIR
68 [2.7] 47 [1.8]

A

A

1521 [59.9] OVERALL HEIGHT

1777 [70.0]

51 [2.0] 2832 [111.5] LEFT SIDE VIEW
FUEL LINE CONNECTION 3/4″ NPT FEMALE COUPLING

STUB-UP AREA
FIELD CUT FOR OUTSIDE CONDUIT CONNECTION ONLY SEE NOTE 13

LIFTING PROVISION (4 PLACES) SEE NOTES 5, 8 AND CENTER OF GRAVITY DIMENSIONS.

935 [36.8] REAR VIEW

WEIGHT DATA

ENGINE/KW

ENCLOSURE MATERIAL

WEIGHT GENSET ONLY
KG [LBS]

WEIGHT SHIPPING SKID
KG [LBS]

SHIPPING WEIGHT KG [LBS]

5.4L/80KW

AL

925 [2035]

79 [175]

1004 [2210]

DIMENSIONS: MM [INCH]

A A
RIGHT SIDE VIEW

installation layout

Standby Generators

100 · 130 · 150 kW

installation layout
Drawing #0H4105-B
9 of 9

DIMENSIONS: MM [INCH]

Generac Power Systems, Inc. · S45 W29290 HWY. 59, Waukesha, WI 53189 · generac.com
©2017 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0199370SBY-M 05/31/17

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals