DuraVent Chimney Liner Instruction Manual
- June 6, 2024
- DuraVent
Table of Contents
Member of M&G Group
Installation Instructions
Ventinox®
DuralFlex® Pro
DuralFlex® SW
DuralFlex® 316
DuralFlex® 304
TherMix®
ProFoil®
A MAJOR CAUSE OF VENT-RELATED FIRES IS THE FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE TO INSTALL ONLY IN ACCORDANCE WITH THESE iNSTRUCTi0NS.
IMPORTANT:
Read through all of these instructions before beginning your installation.
Failure to install this product as described in these instructions will void
the manufacturer’s warranty may create a fire or other safety hazard and may
affect your homeowner’s insurance and safety listing of your appliance.
Keep these instructions for future reference.
Dear Customer, Installer, or End User:
We welcome any comments regarding matters pertaining to our DuraVent products.
We welcome any ideas, input, or complaints and I’ll make sure that someone
responds directly back to you.
Send your emails to:
president@duravent.com
If you are searching for tech support or product information, please phone us
at 800-835-4429. Or email us at:
techsupport@duravent.com
LISTED
MH45609
Installation Instructions
For the most up-to-date installation instructions, see www.duravent.com
READ THESE INSTRUCTIONS COMPLETELY BEFORE ATTEMPTING TO INSTALL ANY DURA VENT
FLEXIBLE CHIMNEY
LINING SYSTEM
INTRODUCTION
DuraVent Flexible Chimney Liners are intended to service residential heating appliances burning wood, wood pellets, oil fuel, natural gas, or propane as (Category I or drañ-hood equipped appliances), or other appliances listed for use with Type B gas vents. DuraVent Liners should not be used to vent unlisted gas or oil appliances, unlisted wood or coal-burning appliances, Category II, III, and IV gas appliances (unless specifically listed to UL 1738 or ULC-S636 in Canada), or gas appliances listed for use only with Type BW vent. DuraVent Liners must be installed by an experienced professional, familiar with the operation and maintenance of heating appliances and chimneys.
Every vent system must be properly planned and installed for optimum performance and safety. Refer to the appliance manufacturer’s instructions to determine venting requirements and limitations with respect to installation and use of the appliance. It is the responsibility of the installer to contact local building and fire officials concerning any installation restrictions and/or inspection requirements that may apply. Permits may be required before the commencement of the installation. These products must be installed in accordance with local building code requirements.
DuraVent Chimney Liners are made from highly corrosion-resistant stainless steel alloys. It is common, however, for indoor air to contain chlorides given oP from carpeting, paints, paint thinners, and laundry detergents. When combustion air for the heating appliance is drawn from the house, these contaminants can combine with flue gas condensates to form aggressive chemicals, such as hydrochloric acid that can attack and degrade connector pipes and chimney liners. Since it is diPicult to determine if contaminants are present, the venting system should be designed to minimize the potential for condensation (i.e. insulate the liner and use B vent type double-wall connectors) and to supply outside combustion air directly to the appliance. Refer to the appliance manufacturer’s instructions and local codes for methods of providing outside air.
INSPECTING AND PREPARING THE CHIMNEY
Inspect the masonry chimney for proper construction and compliance with
applicable building codes, authorities having jurisdiction should be consulted
before installation to determine the need to obtain a permit. The chimney must
meet the following minimum requirements before lining or
relining it with
DuraVent Chimney Liners:
- The masonry chimney must have a wall thickness of at least 3.5 inches (4 in. nominals), a minimum height of 10 feet, and a maximum height of 100 feet.
- In wood-burning applications, the chimney must extend at least 3 feet above the highest point where it passes through the roof and at least 2 feet higher than any portion of the building within 10 feet.
- Only one solid fuel heater may be connected into a flue and may not be combined to vent gas or oil-burning appliances.
- If the flue’s capacity is sufficient, multiple gases and/or oil-burning appliances may be vented into one flue. Gas appliances must connect into the fue ABOVE any oil-fired heater.
- Oil-fired appliances require a base Tee.
- Connector pipes between a heater and chimney must be installed with proper clearance to combustibles as specified by the appliance manufacturer and by any applicable building codes and standards. In the US, refer to the National Fire Protection Association’s NFPA 21\. In Canada, refer to CSA B365M91 Installation Code for Solid Fuel Burning Appliances and Equipment.
The chimney must be thoroughly cleaned before a liner is installed. Examine the chimney for obstructions, soot or tar, glazed creosote, cracked, loose or missing bricks, and eroded moLar joints. Any defects or potential safety problems must be repaired prior to relining the chimney or must be rectified by the installation of a DuraVent Lining System.
FACTORY-BUILT CHIMNEYS
This application is only acceptable in Canadian installations for gas-fired Category I appliances (not oil, pellets, or solid fuels). Before installing a DuraVent Lining System into a factory-built chimney, the chimney must be thoroughly cleaned and checked for structural defects. All parts of the chimney system, such as supports, radiation shields, and fire stops specified by the chimney manufacturer must be installed correctly and, in addition, there must be proper clearances between the chimney and surrounding combustible materials, as specified by the chimney’s installation instructions.
DETERMINING THE REQUIRED LINER SIZE
To determine the correct diameter of a liner, refer to the appliance manufacturer’s installation instructions, or to local building codes: model code NFPA 211 (wood), model code NFPA 54 (gas), model code NFPA 31 (oil), the GAMA Venting Tables For Category I Central Furnaces (gas) or in Canada, the Installation Code for Natural Gas and Propane Burning Appliances and Equipment, CAN1-B149.1 and .2 and Installation Code for Oil burning equipment, CSA B139.
Appliance(s) flue outlet must not be larger than the liner is at its smallest point unless a qualified person has sized the liner to suit the appliance.It is very important that high-efficiency appliances with low flue gas temperatures have correctly sized flue liners. Condensation within the flue system and improper venting/appliance performance can result if flue liners are sized incorrectly.
FITTING DURAVENT FLEX LINERS INTO A MASONRY CHIMNEY
Note: DuraVent Flex Liners are tested and listed as alternative lining materials to standard clay tiles and can be installed into existing clay tiles, or clay tiles may be removed and replaced with a DuraVent Liner.
DuraVent Flexible Liners venting gas or oil appliances do not require a
minimum clearance or insulation between the outside of the liner and inside of
the masonry shell*. Leave enough clearance for the liner to slide into place
without difficulty. If round DuraVent Flex Liners do not fit a chimney’s
inside dimensions, they may be ovalized to allow a proper fit. When ovalizing
a DuraVent Flex Liner, its cross-sectional area decreases. Refer to L1244 for
details or contact your DuraVent Flex Liner supplier for assistance.
When ova/sizing DuraFlex SIP’, Please refer to Installation Instruction
L1244.
Instructions available online at www.duravent.com
*Please note : While insulation is not required for every installation (refer to UL1777 or ULC-S635 for appropriate listings or standards), the performance of the entire heating system is greatly enhanced when installing insulating materials. The venting system acts and reacts in step with the heating unit’s operation. Insulation improves draft and minimizes condensation, helping flue solaces warm up more quickly to achieve a heater’s rated efficiency. Insulation is particularly important for exterior chimneys. Read the sections outlining insulating procedures before beginning the installation.
DuraVent Flex Liners venting solid fuel heaters must be installed with a minimum of one inch of TherMix° or with a ¹/2 layer of ProFoil or Flexwrap insulating blanket between the outside of the liner and the inside of the masonry shell to meet the requirements of UL1777 or ULC-S635 at zero clearance to combustibles.
TOOLS AND SUPPLIES
The following tools and supplies may be required when installing DuraVent Chimney Liners:
Hammer
Key Hole Saw(s)
Screwdriver w/Hex head
Reversible Electric
Drill Cold Chisel
Mortar Mixing Trough
Tin Snips
Silicone Caulk
Trowel
Refractory Mortar| Measuring Tape
Ladder
Eye Protection
Pliers
Work Gloves
Rope
Dust Respirator
Hack Saw Masonry Drill Bit(s)
Ovalizing Machine
---|---
DuraVent Flex Liners are available in 3, 4, 5,
5.5, 6, 7, 8, 9, 10, 11, and 12 inch diameters.
Ventinox Liners can also be ovalized to assume many different cross-sectional
shapes
Ventinox° components are made from various stainless steel alloys. When
ordering, matching liner and component materials.
Components are fastened to DuraVent Flex Liners by tightening the built-in
draw band. Pre-drilling liners or using pop rivets is not necessary.
For the complete list of Ventinox® Components, please refer to DuraVent’s Product Catalog (L820) or visit the Literature Library on our website, www.duravent.com, click on the catalogs and instructions link.
Liner and component arrangements depend on the size and configuration of the
chimney structure and the type, number, and location of the appliances that
are to be vented into the chimney. For assistance, review the manufacturer’s
instructions for appropriate codes and standards, or contact your DuraVent
Liner supplier or DuraVent Customer Service at
800-835-4429.
NOTE: The safe operation of a venting system depends on the proper
installation and use of all materials and parts supplied by the manufacturer
and the proper use and operation of the connected heating equipment.
PREPARING THE THIMBLE AREA
A Tee with Tee Cap is the most common way to terminate a lining system at the
bottom.
Elbows or Universal Take-offs may be used as well. If necessary, enlarge the
thimble area(s) to accommodate the fittings. Make sure that proper clearances
between connector pipes, heating appliances, and combustibles are maintained
after the liner and heating appliances are installed. If penetrating a
combustible wall, be sure to install an approved wall penetration device.
DETERMINING THE REQUIRED LINER LENGTH
Measure the distance from the thimble to the top of the chimney. Add 6 inches
to allow for the installation of the chimney crown and Rain Cap. Subtract the
length of the bottom Tee and any other system components. In a chimney with
offsets, add one foot for each set. Mark the liner, then cut with a hacksaw or
reciprocating saw with a metal cutting blade. When cutting DuraFlex S¥P° fo
length, it is important to use an Angle Grinder with a masonry cutting blade
(Refer to Installation Instruction #L1244).
Typical system layouts for chimneys serving one or more Categories! appliances
DURAVIT FLEXIBLE CHIMNEY LINING SYSTEMS WITH A TREAT THE THIMBLE
Prepare the liner assembly. Slide the expanded end of the Tee body onto the
liner and tighten the draw band. Attach the Tee Cap to the Tee Body in the
same fashion. Do not attach the Tee Snout at this time.
Note: DuraFlex SW° must be installed with the arrow imprinted on the
liner pointing AWAY from the appliance! The rough side should face towards the
appliance.
Lower the liner into the chimney from the top until the Tee reaches the
thimble area. With the draw band of the Tee Snout fully extended, push the
Snout through the thimble into the chimney. Lower the liner and feed it
through the draw band of the Snout. Rotate the liner until the Snout and Tee
are aligned and tighten the draw band securely.
VENTINOX® ONLY
In tight chimneys or chimneys with offsets, it may be difficult to see the
liner with the Tee attached. In such cases, feed a rope through the hole of an
appropriately sized VIC Installation Cone, tie a knot at the end of the rope
and thread the Cone into the liner. Slide the liner down the chimney until it
reaches the offset and the rope extends through the thimble. Pull-on the rope
while a second person at the top of the chimney pushes downward and turns the
liner clockwise. When the liner reaches the thimble, remove the installation
Cone and install the fully assembled Tee onto the liner.
UNIVERSAL TAKE-OFF (TO) INSTALLATION
Use when additional gas or oil appliances need to be vented into the DuraVent
Liner (common vent), or it is used with an ovalized liner instead of a round
Tee section. When a TO is installed into a round DuraVent Liner, the liner
must be at least one inch larger in diameter than the diameter of the TO.
Cut an access hole into the masonry chimney at the point where the TO is to be
joined into the liner. Use an appropriate diameter hole saw (with pilot drill
bit) and a reversible drill, to make a pilot hole through the liner. Before
the main hole is cut, switch the drill into reverse and press lightly but
firmly against the liner to cut the main hole. Remove the cutout portion of
the liner.
When cutting a TO into a 0uraFlex S\IP° Liner, please read 7ech Bulletin
1244.
Feed the TO’s draw band around the liner and into the turnbuckle. Tighten the
draw band.
Apply a bead of High Temp RTV Silicone between the TO and liner.
CLOSING UP THE THIMBLE AREA
Use the Tee Snout or TO to center the liner within the chimney. Fill the space
between the Tee Snout or TO and the chimney structure with masonry and mortar
to form an airtight seal. Silicone caulking may also be used for this purpose.
INSTALLING A DURANT FLEX LINER IN FIREPLACE APPLICATIONS
Seal the area at the top of the smoke chamber by lacing strips of ceramic
blanket insulation with refractory cement and packing them tightly between the
bottom of the liner and masonry (sealing plug). Keep the liner centered.
Insulate DuraVent Flex Liners from here to the top.
Alternatively, the Base Plate (BP) and the Sleeve (SL) can anchor the liner at
the top of the smoke chamber and seal the gap between the liner and masonry.
The BP can be supposed by wedging it into mortar joints or by supporting it
with steel rods. When trimming the BP, make sure that the hole in the plate is
centered in the flue. Attach the SL to the DuraVent Flex Liner, then lower
it until the male end of the SL is seated in the Base Plate. When venting a
stove or inserting through a fireplace and into a chimney, a DuraVent
Liner can provide a continuous flue from the heater to the top:
Ovalize the bottom 4 or 5 feet of the DuraVent Flex Liner so that the
ovalized poLion of the liner fits through the damper and into the firebox
(refer to Tech Bulletin L1009 for cross-sections). Connect the heater with an
oval
Tee or other adaptors. Seal chimney with a Damper Sealing Kit (see
instructions for Stove and Fireplace Insert Installation Kits) or a sealing
plug at the damper level or at the top of the smoke chamber.
Alternatively, remove portions of the damper frame and smoke shelf so that
around DuraVent Flex Liner can be connected to the heater with a standard
Tee, Sleeve, Boot, or Adapter. Again, seal chimney with a Damper Sealing Kit
(see instructions for Stove and Fireplace Insel Installation
Kits) or a sealing plug at the damper level or at the top of the smoke
chamber. Insulate a DuraVent Flex Liner from here to the top.
FINISHING THE TOP OFA DU• RAVENS FLEX LINED CHIMNEY
1) Vertical Cap Kits (-VCK) include a Top Plate, Storm Collar, and
Vertical Cap. These kits and provide one method for terminating a DuraFlex
Liner at the top.
Vertical Cap Kits can be used to finish TherMixâ or ProFoil insulated
chimneys. When the liner is insulated with ProFoil, the Vertical Cap Kit both
seals the system and supports the liner.
Slip the Top Plate over the liner and position it on the chimney with the
liner centered. Trim as necessary or fold edges over the outside of the
chimney. Apply a generous bead of High Temp RTV Silicone under the Top Plate
and press it into position. Slip the Storm Collar portion of the
Vertical Cap over the liner, position it over the Top Plate, and tighten the
clamp band. Trim of excess liner lush with the Storm Collar.
Re-assemble Vertical Cap.
Please Note:
Vertical Caps incorporating bird screens are necessary and/or required in some
areas but may be susceptible to blockage through
Chimney termination using Top Kit
freezing moisture in areas of low ambient temperature. Consult authority
having jurisdiction.
2) Masonry crowns with a Vertical Cap(-VC) are commonly used to finish
TherMix” insulated DuraVent Flex Liners. Fill TherMix” to within four inches
from the chimney top. Fill the remaining four inches with mortar or crown mix
and form a slope from the liner to the outside of the top course of bricks.
Attach a VeLical Cap (-VC) to the liner.
Chimney termination using masonry crown
3) Masonry
crowns with a clay tile and any UL listed rain cap: Fill TherMix⁶ to within
four inches from the chimney top. Slip a full or partial length of any
standard clay tile over the DuraVent Flex Liner. Fill the gap between the
outside of the tile with mortar or crown mix and form a slope to the outside
of the top course of bricks. Fill the gap between the DuraVent Flex Liner and
the tile with TherMix° and seal the last inch with mortar
or crown mix. A DuraVent Flex Liner may be terminated anywhere within the
tile, as long as it protrudes at least four inches into the tile. Attach a UL
Listed rain cap to the clay tile.
INSULATING DURA VENT FLEX LINERS
General Guidelines:
DuraVent Flex Liners have been tested and are listed by Underwriters
Laboratories, Inc (UL) to UL 1777 and ULC-S635 standard at zero clearance to
combustibles and for use with all fuels. When venting wood-fired heaters or
fireplaces, a minimum of one-inch TherMix° or at least \/2″ of ProFoil are
needed to conform to the UL1777 and ULC-S635, zero clearance listing.
All temperature tests were performed on chimneys featuring a 4” nominal
masonry shell and a DuraVent Flex Liner with or without the specified
insulation between the liner and interior of the chimney (no clay tiles). The
outside of the chimney was surrounded by a wood enclosure at zero clearance as
specified by the standard.
METHOD #1: INSULATING WITH THERMAX®
TherMix° is poured into the chimney AFTER the flex liner is installed.
TherMix° is a pre-mixed insulation material and only requires the addition of
water at the job site. Review TherMix° literature to determine the volume of
TherMix® needed to fill a specific chimney. Empty a TherMix^ bag into a mortar
trough or wheelbarrow. Add 7 to 9 gallons of water and mix with a hoe. Proper
consistency is achieved when the material feels damp but is still granular.
Little or no water should appear between fingers when a handful of TherMi@ is
squeezed. Correctly prepared TherMix° pours like “loose fill” into the void
between the liner and the chimney. Complete instructions are on each TherMix°
bag.
During the pouring process, distribute the insulation evenly into the
available space. Spacers may be used every 5 ñ. to center the liner. Vibrate
the liner by firmly tapping it. Continue to pour TherMix® until the chimney is
filled to the top and finish as described previously. Inspect the liner at
this time to ensure that no TherMixᵒ has fallen inside the venting system.
All heaters or fireplaces can be fired up right after the installation is
complete. Keep flue gas temperatures below 700 degrees F for three weeks. This
allows for TherMix° to dry gradually. The operator is responsible for making
sure that the heater is not overfired during this initial period.
METHOD #2: INSULATING WITH PROFILE OR FLEX-WRAP CERAMIC BLANKETS.
Ceramic blankets are attached to DuraVent Flex Liners BEFORE the liner is installed into the chimney. Blankets are 1/2” in. thick, 8 pounds density, and faced with a 2 mil. aluminum foil. The 1/2″ thick blanket is the minimum amount of insulation needed when using ProFoil. If using 1/4″ ProFoil blankets, two wraps are necessary to achieve the required 1/2″ insulation. Aluminum tape, wire mesh, and clamps are needed for proper installation.
|
---|---
Bag of TherMix| Profil ceramic blanket
METHOD #1 THERMAX BENEFITS AT-A-GLANCE:
- No Health Risks: Non-fibrous, non-toxic, inert, and manufactured under stringent quality controls. Safe to the installer and homeowner, today and into the future.
- Adds Safety: Chimneys insulated by TherMix reduce creosote build-up, the chance of a chimney fire is minimized and its dangers are decreased.
- Superior Performance: Featuring high “R” values, flue surface temperatures are balanced and react quickly to the firing cycles of heating units. Aiding in optimal heating ef1iciencies.
- Durable & Tested: When properly installed, TherMix does not leak, separate, or deteriorate. Field-tested since 1984.
- Reinforces: Insulates the liner & flue gas while providing a strong bond for the masonry chimney.
THERMAX: THE “THERMAL BRIDGE” BETWEEN FLEXIBLE CHIMNEY LINERS AND MASONRY
Thermax lowers temperatures onliners during over firing or chimney fires:
Allows heat to be slowly absorbed into the entire mass of a chimney, where it
is safely dissipated over a large surface area.
Thermax maintains higher temperatures onliners when flue gas temperatures are
low: Maintaining flue gas temperatures above the dew point, (-128°F), is
essential to avoid condensation.
The insulating mass of TherMix retains the maximum available heat close to the
liner: the flue stays warm for a longer period of time after the appliance
shuts down. With oil and gas appliances, keeping the flue warmer between
firing cycles greatly reduces the possibility of momentary flue gas spillage
which occurs at the start of the next cycle. With wood burning applications,
warmer flues help eliminate back pumping and other deal related problems.
Thermax minimizes fluctuations of liner surface temperatures during heating
cycles. This is critical when a deal must be established quickly each time an
appliance fires up and when minimizing condensation within the entire height
of the flue is important.
NOTE: To comply with the specifications of a UL Listed, zero clearance
solid flue installation, a minimum thickness of 1” of TherMix must be
installed between a listed stainless steel liner and a 4” thick masonry
chimney wall. In verifiable code-complying, clay-tile-lined chimneys, no
minimum thickness of TherMix is required. Table I shows how TherMix reduces
heat transfer to combustible material surrounding a masonry chimney. The data
is an actual UL test where chimney flue gasses were maintained at 1000°F for
an eight-hour period. The (+) line shows temperatures on a plywood enclosure
located at one inch from a code-approved, tile-lined chimney. The (n) line
shows temperatures with a Ventinox liner, which is insulated with TherMix at
the same thermo- couple location. The (*) line shows acceptable temperature
limits specified by the UL standard, (90°F plus ambient for the first 4.5
hours and 117°F plus ambient for the remainder of the test).
There is no change in the consistency of TherMix over time. Even añer exposure to many high-temperature tests at UL, the structural integrity, chemical composition, and insulating qualities remained consistent over time, every time.
- Thermax insulated chimneys can be used right after the installation is complete, as long as flue gas temperatures do not exceed 1000°F during the first 48 hours of actual use. Please note that drying and curing are two separate processes:
- Curing or hardening of TherMix takes place over a 28-day period, with 65ᵒ/ to 75% of this process occurring the first week.
- Drying time depends on the thickness TherMix, the permeability of the chimney, and weather conditions. The drying process is enhanced and completed over time by using the heating appliance.
Figure 1
TherMix Field Benefits
| TherMix|
Ceramic Blankets
---|---|---
Zero-clearance to combustibles| Yes| Yes
Ease-of-installation| Yes| Yes
Difficulties with Offsets| No| Yes
Seals dangerous cracks and voids in chimneys| Yes| No
Eliminates air leakage into the chimney| Yes| No
Eliminates moisture buildup between liner & chimney structure| Yes| No
Ships UPS/FedEx (Boxes Only)| Yes| Yes
Accepted by building code officials| Yes| Yes
Can be removed| Yes| Yes
Avoids reliance on a respirator during installation| Yes| No
Eliminates the need for reflective surfaces to reduce heat transfer| Yes| No
Poured method means one size fits all insulation| Yes| No
Holds liner in place| Yes| No
Figure 2
WHEN USING THERMAX
There is no need to purchase spray adhesives, tapes, wire, mesh, and/or sheet
metal parts which add to the cost and time to complete a job (Figure 2.)
• TherMix can be used to insulate modular masonry fireplaces.
• TherMix stays in place when installed but can be easily removed. Dry weight
per cubic foot installed is -20Ibs.
Thermax is delivered in a strong poly-lined bag or box containing all
ingredients except water, which must be added to moisten the material (Figure
3.) Proper consistency is achieved
TABLE 2: CROSS-SECTION AREA OF LINER
Liner Size| CS Area| Oval Liner Size| Oval Dimensions| CS Area
Round 5″| 19.62in2| | |
Round 6″| 28.46in2| Oval 6″| (4.2″ x 7.2″)| 24.60in2
Round 7″| 38.461n2| Oval 7″| (4.2″ x 9.1″)| 32.20in2
Round 8″| 50.25in2| Oval r| (4.2 x 10.3″)| 37.20in2
Round 9″| 62.50in2| | |
Round 10″| 78.50in2| Oval 10″| (4.2″ x 13.3″)|
49.50in2
Round 12″| 113.22in2| | |
W — Width of flue opening (in inches)
D — Depth of flue opening (in in‹hes)
H — Height of flue (inin‹hes)
CS= Cross Section areas (table 2)
TABLE 1: THERMAX VOLUME PER ONE FOOT OF CHIMNEY HEIGHT
Flue Opening| Diameter of Liner
5″| 6″| 7″| 8″| 10″| 12″
7.5″ x 7.5″| .25| .20| —| —| —| – –
7.5″ x 11.5″| .46| .40| (Ovalized) .38| (Ovalized) .32| – –| – –
8.5″ x 8.5″| .36| .30| .23| – –| – –| – –
8.5″ x 11.5″| .54| .48| .41| (Ovalized) .36| (Ovalized) .33| – –
9.5″ x 9.5″| .49| .43| .36| .27| —| – –
11.5″ x 11.5″| .78| .72| .65| .60| .37| – –
11.5″ x 16.5″| 1.18| 1.12| 1.05| .96| .77| – –
12.5″ x 12.5″| .95| .88| .82| .73| .53| – –
14.5″ x 14.5″| 1.30| 1.26| 1.20| 1.10| 92| .65
14.5″ x 18.5″| 1.70| 1.66| 1.60| 1.50| 1.30| 1.04
when the material feels damp but still granular (-7 to 9 gallons of water per
bag/box). When a handful of properly moistened TherMix is squeezed hard,
little to no water appears between the fingers.
During the installation, correctly prepared Ther- Mix pours like “loose fill.”
TherMix is distributed within the chimney cavity by vibrating the liner.
Do not tamp or compress TherMix.
METHOD #2 PROFILE ATTACHING CERAMIC BLANKETS TOA DURAVENT FLEX LINER:
Roll out the insulation blanket on a clean solace, foil face down. Lay the fex liner on top and trim the blanket so that it is about one foot shorter than the liner.
Wrap the insulation around the liner lengthwise and trim it so that a butt
joint is formed. Seal the joint with aluminum foil tape. Spray adhesive may be
used to hold the blanket in place until it can be secured with foil tape. A
minimum of 1/2″ of insulation is required. If a double layer of the blanket is
needed, install it with the butt joint on the opposite side.
Install ProMesh protective wire mesh over the blanket(s). The promise is used
to protect the ProFoil insulation as the liner is lowered into the chimney.
Slip the ProMesh over the insulated liner and secure one end with a stainless
steel band clamp. Pull the ProMesh towards the other end of the liner so that
it tightens snugly around the insulation, then trim off the excess. Secure
this end with a stainless steel band clamp.
CONNECTING THE APPLIANCE AND CHECKING DRAFT
When installing gas or oil appliances, use connector pipes specifically
designed for Liner
Attaching a ceramic blanket Checking for drafts
connecting such appliances. Attach the connector pipe directly and securely to
the Tee Snout or to a listed wall penetration assembly. Secure all sections of
the connector pipe with screws or rivets.
Record the date of installation (on the label provided with the liner) and
attach it to the Tee
Snout or wall penetration assembly.
The label provides the DuraVent Flex Liner
DOUBLE WRAPPING Y4″ PROFILE
Profil Size| Single Wrap Liner Size| Double Wrap Liner Size
22″x 25″| 3″-6″| 3″-5″
24″x 25″| 7″| 6″
29″x 25″| 8″| 7″-8″
48″x 25″| 9″-12″| 9″-12″
brand name, liner manufacturer, the date of installation and states the intended use of the particular DuraVent Flex Liner. After the installation is complete, make sure the appliances are venting properly. With a gas-burning appliance equipped with a draft hood, turn on the unit, let it warm up, then hold a match under the draft hood. If the flame is blown outward or extinguished, the appliance is not drafting properly. Fan-assisted appliances (without draft hoods) have built-in pressure sensing switches. If the chimney draft is not adequate, the appliance shuts off. With oil-burning appliances, barometric draft dampers should be installed in the connector pipe. Hold a match in front of the partially opened barometric damper to check the draft. If more than one appliance is connected to a common vent, test each appliance with and without the other in operation. If draft problems exist, corrections must be made before the appliance is used.
INSPECTION AND MAINTENANCE
Creosote formation and the need for removal: When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote that accumulates inside a chimney flue. When ignited, creosote produces extremely hot fires. Creosote or soot buildup can occur in all venting systems and should be removed to reduce the risk of a chimney fire. Therefore, Ventinox & DuraFler Lining Systems should be inspected at least once every two months during the heating season to determine if a creosote or soot buildup has occurred. An annual inspection is required to comply with the terms of the warranty. If creosote or debris have accumulated, they must be removed to eliminate the risk of a chimney fire or the formation of carbon monoxide. Excessive condensation and chimney fires can be prevented through proper appliance use and maintenance.
To properly inspect the liner, gain access either from the top or bottom of
the chimney.
When examining from the bottom, remove the connector from the thimble, or if
access is available, inspect through the clean-out cap of the Tee. Use a
mirror and flashlight or chimney inspection camera to examine the inside of
the liner. When examining from the top, remove the Rain Cap, examine the
inside as above and determine if cleaning is necessary. Should a fire occur
within a DuraVent Flex Liner, notify the fire department immediately. Fires
are catastrophic events for any chimney. Before using the chimney after a
fire, it must be inspected by a qualified person and cleaned or repaired as
necessary. The posting of notices at a point where the connection is made to
the appliance concerning the liner’s limitations of use with specific fuels
and appliances including a reminder to homeowners to check the rain cap for
icing during low ambient temperatures. Such notices shall include the date of
installation, the manufacturer’s name, the model number, and the class of the
lining system.
CLEANING PROCEDURE
Remove the Vertical Cap, or if working from the bottom, remove the appliance connector or clean-out cap. Select appropriately sized polypropylene chimney brushes and flexible fiberglass extension rods. Run the brush-up and down inside the liner until any deposits or debris are removed. Reinstall the Vertical Cap, connector pipe, or Tee Cap.
M &G DURAVENT LIMITED LIFETIME WARRANTY
M&G DuraVent, Inc. (“DuraVent”) provides this limited lifetime warranty for
all of its products with the exception of Ventnor (lifetime), and PolyPro®
(ten years). Subject to the limitations set forth below, DuraVent warrants
that its products will be free from defects in material or manufacturing if
properly installed, maintained, and used. DuraVent products are fully
warranted if installed only by a professional installer. This Warranty is
transferable from the original homeowner to the buyer of the home. This
warranty does not cover normal wear and tear, smoke damage or damage caused by
chimney fires, acts of God, or any product that was: (1) purchased other than
from an authorized DuraVent dealer, retailer, or distributor; (2) modified or
altered; (3) improperly serviced, inspected or cleaned; or (4) subject to
negligence or any use not in accordance with the installation instructions
included with the product as determined by DuraVent Installation instructions
are available online at www.duravent.com under
Support/Literature and through our Customer Service Department
800-835-4429 or
customerservice@duravent.com. This
limited lifetime warranty applies only to parts manufactured by DuraVent.
DuraVent provides the following warranties for its products: One Hundred
Percent (100%) MSRP 15 years from the date of purchase, and Fifty Percent
(50%) thereafter, except for the following limitations on all Termination Caps
and DuraBlacr are warranted at One Hundred Percent (10096) for five years. All
warranty obligations of DuraVent shall be limited to repair or replacement of
the defective product pursuant to the terms and conditions applicable to each
product line. These remedies shall constitute DuraVent’s sole obligation and
sole remedy under this warranty. This warranty provides no cash surrender
value. The terms and conditions of this warranty may not be modified, altered,
or waived by any action, inaction, or representation, whether oral or in
writing, except upon the express, written authority of an executive officer of
DuraVent Corn, bio-fuels, driftwood, or other wood containing salt,
preservative-treated lumber, plastic, and household trash or garbage, or wood
pellets containing such materials must not be burned in the appliance or
fireplace In case of a chimney fire, the chimney must be inspected and
approved by a certified Chimney Sweep before reuse. After each annual
inspection, maintenance, and cleaning, the certified Chimney Sweep must fill
out and date the appropriate section of the warranty card provided with the
chimney liner.
LIMITATIONS ON INTERNET SALES:
Notwithstanding any other terms or conditions of this Limited Lifetime
Warranty, DuraVent provides no warranty for the following specific products if
such products are not installed by a qualified professional installer.
Duratec, DuraPlus DuraChimney° II, PelletVent Pro°, DirectVent Pro°,
FasNSeal°, FasNSeal° W2, FasNSeal° Flex, and PolyPro°, and M&G DuraVent’s
relining products including DuraLiners, DuraFlex° (SW, Pro, 316, 304), and
Vete. For purposes of this warranty, a trained professional installer is
defined as one of the following: licensed contractors with prior chimney
installation experience, CSIA Certified Chimney Sweeps, NEI Certified
Specialists or WETT Certified Professionals. DuraVent must be notified and
given the opportunity to inspect the defective products prior to replacement
under the terms of this limited lifetime warranty. All warranty claims must be
submitted with proof of purchase. Labor and installation costs are not covered
under this warranty. To obtain warranty service contact: DuraVent Warranty
Service 877 Coning Ct, Vacaville CA 95688, or call
800-835-4429. WHERE LAWFUL DURA VENT
DISCLAIMS ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. IN NO
EVENT WILL DURANT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, PUNITIVE, OR
SPECIAL DAMAGES OR DIRECT OR INDIRECT LOSS OF ANY KIND, INCLUDING BUT NOT
LIMITED TO PROPERTY DAMAGE AND PERSONAL INJURY. DURAVENT’S ENTIRE LIABILITY IS
LIMITED TO THE PURCHASE PRICE OF THIS PRODUCT. SOME STATES DO NOT ALLOW
LIMITATIONS ON IMPLIED WARRANTIES, OR THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS AND EXCLUSIONS
MAY NOT APPLY TO YOU. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS,
AND YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM STATE TO STATE.
For the most up-to-date installation instructions, see
www.duravent.com
REV 3.22.2012
Manufactured in Vacaville CA and Albany NY
Member of M&G Group
Customer Service Support 800-835-4429
707-446-4740 FAX
www.duravent.com
DuraFlex and Ventinox have registered trademarks of the M&G DuraVent, Inc.
All rights reserved. Made in the USA. M&G DuraVent is a member of M&G Group.
©2012
L253 672012
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>