Magnetic Door Holders
Manual
DH-151SQ | Surface-mount |
---|---|
DH-171SQ | Flush-mount |
Features:
- For use with door closers to control the release and closing of residential, commercial, and public area doors
- Adjustable armature plate reduces installation time and adjusts to door alignment changes
- Surface-mount or flush-mount models are available
- Fail-safe operation
- Low profile design
- Holding force – 33-lb (15kg)
- 3 voltages: 12/24 VAC/VDC, and 120VAC
- Cast aluminum faceplate
- No residual magnetism for easy release
- Built-in voltage spike suppressor
- Optional extension bars available: 3 /4″, 1″, 4″, 7″
- Use with SECO-LARM door closers SD-C121-S, SD-131-SQ, SD-C101-SGQ, SD-C101-SBAQ, or SD-C101-SBBQ
SECO-LARM Magnetic Door Holders
Introduction:
The SECO-LARM Magnetic Door Holders are designed for virtually any remote door
release application. The UL Listed SECO-LARM Magnetic Door Holders, used in
conjunction with UL Listed SECO-LARM door closers, control the release and
closing of residential, commercial, and public area doors including
apartments, schools, hotels, hospitals, and offices. The fail-safe operation,
tri-volt coils, and adjustable armature plate allows for easy and flexible
installation. SECO-LARM Magnetic Door Holders also come in surface-mount or
flush-mount models with full mounting hardware included.
Specifications:
Model
| DH-151SQ|
DH-171SQ
---|---|---
Installation|
Surface-mount
|
Flush-mount
Operating voltage| 12 VAC/VDC, 24 VAC/VDC, 120VAC
**** Current draw| 52mA@12VAC, 60mA@12VDC
27mA@24VAC, 31mA@24VDC
24mA@120VAC
Holding force| 33-lb (15kg)
Dimensions
| Magnet box| 23/4″49/16″x3″ (70×116.5×76 mm)| 23/4″x49/16″x21/16″
(70×116.5×52 mm)
Door armature| 29/16″x29/16″x 19/16″ (65x65x40 mm)
Weight| Magnet box| 1-lb 6.6-oz (641g)| 1-lb 1.6-oz (498g)
Door armature|
8.4-oz (237g)
**Parts List:
**
1x Door holder
2x Jumpers (1x pre-installed)
4x M4x8 Machine screws
1x 1″ Extension bar| 1x Armature plate
2x M5x15 Machine screws
2x M3x10 Machine screws
1x Extension bar wrench| 1x Manual
2x #10×1
1 /4″ Wood screws
1x Back box*
---|---|---
Available Accessories: Extension Bars
DH-100E-07SQ
DH-100E-10SQ
DH-100E-40SQ
DH-100E-70SQ| 3 /4″ (19mm)
1″ (25mm)
4″ (102mm)
7″ (178mm)
---|---
Wiring Diagram:
Installation:
-
Determine the mounting location of both the Magnetic Door Holder and the Armature Plate. Run the power wires to that location in compliance with any local codes.
-
Select the voltage (two jumpers for 12VAC/VDC, or a single jumper for 24VAC/VDC or 120VAC) for the Door Holder (See “Voltage Settings:” below) and adjust the jumpers.
-
For the DH-151SQ (Surface-Mount Magnetic Door Holder):
a. Mount the backbox to the location where your wires are run and connect the wires according to the wiring diagram on pg. 2.*
b. Finish screwing down the unit to the backbox and test the unit. -
For the DH-171SQ (Flush-Mount Magnetic Door Holder):
a. Connect the wires according to the wiring diagram on pg. 2.*
b. Finish screwing down the unit to the single-gang box and test the unit. -
Mount the Armature Plate to the door and make sure it lines up with the door holder (extensions available if needed, see pg. 2).
-
Double-check all connections and mountings to make sure the installation is complete.
*IMPORTANT: The wiring connections must match the voltage jumper settings and the supplied voltage.
Voltage Settings:
Set the voltage using the jumpers as in the diagram.
NOTE: Factory default is 120VAC. To avoid personal injury or damage to
the product, ensure that the jumper setting matches the wiring connections
(See “Wiring Diagram:” on pg. 2) and the supplied voltage. Improper
settings/wiring will void the warranty and SECO- LARM will not be responsible
for any resulting injury.
Dimensions:
DH-151SQ:
DH-171SQ:
Armature:
California Proposition 65 Warning: These products may contain chemicals that
are known to the State of California to cause cancer and
birth defects or other reproductive harm. For more information, go to
www.P65Warnings.ca.gov.
LIMITED WARRANTY:
This SECO-LARM product is warranted against defects in material and
workmanship while used in normal service for two (2) years from the date of
sale to the original customer. SECO-LARM’s obligation is limited to the repair
or replacement of any defective part if the unit is returned, transportation
prepaid, to SECO-LARM. This Warranty is void if the damage is caused by or
attributed to acts of God, physical or electrical misuse or abuse, neglect,
repair or alteration, improper or abnormal usage, or faulty installation, or
if for any other reason ECO-LARM determines that such equipment is not
operating properly as a result of causes other than defects in material and
workmanship. The sole obligation of SECO – LARM and the purchaser’s exclusive
remedy, shall be limited to the replacement or repair only, at SECO-LARM’s
option. In no event shall SECO-LARM be liable for any special, collateral,
incidental, or consequential personal or property damage of any kind to the
purchaser or anyone else.
NOTICE: The SECO-LARM policy is one of continual development and
improvement. For that reason, SECO-LARM reserves the right to change
specifications without notice. SECO-LARM is also not responsible for
misprints. All trademarks are the property of SECO- LARM U.S.A., Inc. or their
respective owners. Copyright © 2021 SECO-LARM U.S.A., Inc. All rights
reserved.
SECO-LARM ® U.S.A., Inc.
16842 Millikan Avenue, Irvine, CA, 92606
Phone: 949-261-2999 |
800-662-0800
Website: www.seco-larm.com
Email: sales@seco-larm.com
MI_DH-1x1SQ_210416.docx
SECO-LARM U.S.A., Inc.
Documents / Resources
|
SECO-LARM DH-171SQ Magnetic Door
Holders
[pdf] User Manual
DH-151SQ, DH-171SQ, DH-171SQ Magnetic Door Holders, Magnetic Door Holders,
Door Holders
---|---
|
SECO-LARM DH-171SQ Magnetic Door
Holders
[pdf] Instruction Manual
DH-151SQ, DH-171SQ, DH-171SQ Magnetic Door Holders, DH-171SQ, Magnetic Door
Holders
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>