ELRO FS4610 Ultra Thin Smoke Detector With a 10-Year Battery Instruction Manual

June 6, 2024
ELRO

ELRO

ELRO FS4610 Ultra Thin Smoke Detector With a 10-Year Battery

ELRO FS4610 Ultra Thin Smoke Detector With a 10-Year
Battery

INTENDED USE: FIRE SAFETY
ESSENTIAL CHARACTERISTICS: PASSED
Nominal activation conditions/ Sensitivity, Response delay (response me) and Performance under fire condition – Operational reliability – Tolerance to supply voltage – Durability of operational reliability and response delay, temperature resistance, vibraration resistance, humidity resistance, corrosion resistance, electrical stability

Instructions

Instructions-table

This smoke alarm is equipped with a self-test mechanism. At least once a month at a random moment, the device automatically checks the functionality of the sensor and the siren. During a successful test, the detector will beep and blink briefly. If problems are detected, the detector switches to error mode. Replace the device immediately if the error message occurs!

Important Important 02

Overview LED & acous c signalling

Operating mode| Visual signal (flash)| Acoustic signal (beep)| Description mode
---|---|---|---
Normal| 1 x per 40 second| None| Device is functioning properly
Self test| 1 x| 1 x| Device functions correctly
Manual test| 3 x| 3 x| Device functions correctly
Alarm| 1 x per second (3 x) / pause of 1,5 seconds| 1 x per seconds (3 x) / pause of 1,5 seconds| Device is detecting smoke
Alarm silence| 1 x per 8 seconds| None| Smoke alarm signal is muted
Low battery warning| 1 x per 40 seconds| 1 x per 40 seconds| Battery is running low
Low battery warning silence| None| None| Low battery warning is muted
Sensor fault warning| 1 x per 40 seconds| 1 x per 40 seconds| Sensor is not functioning properly
Buzzer fault warning| 2 x per 40 seconds| None| Buzzer is not functioning properly

Warnings:

  • To prevent injury, this apparatus must be securely attached to the ceiling in accordance with the installation instructions.
  • Batteries shall not be exposed to excessive heat such as sunshine and fire.
  • Battery life shortens without monthly tests.
  • Keep away from air conditioning/ventilation.
  •  Do not paint or cover the device.
  • Consult local regulations.

Troubleshooting: False alarm is often caused by dust or steam. In case of doubt: Leave the building and take ac on!
Additional mounting instructions: Corridor max width 3m: Max 15m between 2 alarms. Max. 7,5m to front side and alarms at edges/crossings of corridors. Galleries: Length and width >2m and >16m², additional alarms below gallery.
Partial roof slopes: Flat ceiling ≤1m wide, consider as the roof slope. Flat ceiling >1m wide, consider as flat ceiling.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals