Electro Industries Nexus 1500+ Power Quality Meter with Phasor Measurement Unit User Guide
- June 6, 2024
- Electro Industries
Table of Contents
Nexus® 1500+ Meter Quickstart Guide
CAUTION! Installation of the Nexus® 1500+ meter must be performed only by
qualified personnel who follow standard safety precautions during all
procedures. That personnel should have appropriate training and experience
with high voltage devices. Appropriate safety gloves, safety glasses, and
protective clothing are recommended.
During normal operation of the Nexus® meter, dangerous voltages flow through
many parts of the unit, including Terminals and any connected CTs (Current
Transformers) and PTs (Potential Transformers), all I/O Modules and their
circuits. All Primary and Secondary circuits can, at times, produce lethal
voltages and currents. Avoid contact with any current-carrying surfaces. Do
not use the meter or any I/O device for primary protection or in an energy-
limiting capacity. The meter can only be used as secondary protection.
IMPORTANT! Refer to your meter’s Installation and Operation Manual for
additional safety warnings before performing installation, wiring, or
maintenance of your meter. See the link to the manual, below.
NOTE: This Quickstart Guide gives basic installation, wiring, and
programming instructions. For additional meter operation and programming
information, refer to your meter’s Installation and Operation Manual and the
Communicator PQA TM, MeterManagerPQA TM, and EnergyPQA.com Software User
manual on EIG’s website:
User Manual:
https://www.electroind.com/products/nexus-1500-power-quality-meter-with-
phasor-measurement-unit/ From the webpage, click Technical Documents>User
Manual.
Software Manual:
https://www.electroind.com/products/communicatorpqa-power-monitoring-
software/ From the webpage, click Technical Documents>User Manual.
CommunicatorPQA TM Setup Software:
https://www.electroind.com/products/communicatorpqa-power-monitoring-
software/
From the webpage, click Download Compaq Pro. To get a Professional license for
the software, email sales@electroind.com or
call 516-334-0870.
All EIG’s metering and software products’ literature can be accessed from:
https://www.electroind.com/power-metering-products/
For software and metering integration, EIG’s Technical Support Engineers are
available on an hourly or daily basis to
help with typical commissioning assistance, which includes:
- Verifying meter installation and wiring.
- Verifying proper system integration.
- Working with 3rd parties to ensure cross-compatibility.
- Advising users on best practices for optimal implementation.
You can reach Technical Support from 8 a.m. to 8 p.m. EST, Monday-Friday, at 516-334-0870.
Mechanical Installation
1. Slide the meter into the panel’s cut-out. (See the diagram shown below.
You can use either an octagonal or a rectangular cut-out.)
NOTE : You can also mount the meter vertically.
2. From the back of the panel, slide the 4 Mounting Brackets into the grooves
on the top and bottom of the meter housing – 2 fit on the top, and 2 fit on
the bottom.
3. Snap the Mounting Brackets into place.
4. Secure the meter to the panel with a lock washer and a #8 screw in each of
the 4 mounting brackets.
5. Tighten the screws with a #2 Philips screwdriver. Do not over-tighten –
maximum torque is 3.5 Lb-In.
Cut-out Dimensions
Electrical Installation (See the meter’s Installation and Operation Manual for additional wiring configurations.)
WYE or DELTA Direct 3 Phase, 4-wire * Optional CT for Current Measurement
Only
DELTA Direct 3 Phase, 3-wire
DELTA Direct 3 Phase, 3-wire DELTA with PTs, 3 Phase, 3-wire
Power Supply Connections
Wire gauge: 12-18 AWG for either solid or stranded wire Torque: 3.5 Lb-In
The branch circuit protection size should be 15 A. The Nexus® 1500+ meter
requires a separate power source. There are three control power options:
115AC, D2 high-voltage, and D low-voltage.
CAUTION! The power supply voltage and connections vary depending on the
power supply Option being used. CAREFULLY follow the instructions and drawings
for proper wiring.
115AC/D2 Power Supply Connection
For all three power supply options, add a properly voltage-rated, 4 A, time- delayed (slow blow) fuse in the power supply feed, for example, UL approved Littelfuse® part number FLQ4. For the 115AC and D2 Option power supplies:
- Connect the line supply wire to the L+ terminal.
- Connect the neutral supply wire to the N(-) terminal.
- Connect earth ground to the PE GND terminal.
For the D Option power supply:
- Connect the negative voltage to the V(-) terminal.
- Connect the positive voltage to the V(+) terminal.
- Connect earth ground to the PE GND terminal.
Programming the Nexus® 1500+ Meter Using the USB Virtual Com Port Connecting
your PC to the Meter
1. Attach a USB cable from your PC’s USB port to the meter’s front panel USB
port. The meter’s USB port uses a USB Type B plug.2. Windows® 7 and above operating systems install the USB driver
and display the screen shown on the right. Make note of the Com port being
used.
Connecting to the Meter via Software
- Open CommunicatorPQA™ software (see page QS-1 for download instructions).
- Click the Connect icon on the Tool Bar. You will see the connect screen.
- Click Serial Port.
- Select Baud rate of 115200.
- Select the Port that is the USB Virtual Com port.
- Click Connect. You will see the Device Status screen.
- Click OK. You will see the Main CommunicatorPQA™ software screen.
Configuring the Meter via Software
Click the Profile icon on the Icon Bar. You will see the Device Profile
screen.
NOTE: Instructions for a few basic settings are given in this Quickstart
Guide. For more information, download the manual from EIG’s website (see page
QS-1) or click elp>Contents from the Title Bar of the CommunicatorPQA™
application’s Main screen, to view the CommunicatorPQA™, MeterManagerPQA™, and
EnergyPQA.com™ Software User Manual.
CT, PT Ratios and System Hookup
From the Device Profile screen, double-click General Settings>CT, PT Ratiosand
System Hookup. The current settings are shown on the screen.
- Double-click one of the settings to open the CT and PT Ratios screen, shown below.
- You can enter CT and PT Ratios and select Hookup from the pull-down menu. Click Help to view instructions for configuring these settings.
- Click OK to close the screen. Click Update Device from the Device Profile screen to save your settings.
Example CT Settings:
200/5 Amps: set the Primary Current value as 200.00; set the Secondary Current
value as 5.00.
Example PT Settings:
14400/120 Volts: set the Primary Voltage value as 14400.00; set the Secondary
Voltage as 120.00.
Communication Settings
- From the Device Profile screen, double-click General Settings>Communications. The current settings for the meter’s Ports are shown on the screen.
- Double-click one of the Port settings to open the Communications screen, shown above.
- You can configure the settings for all four Communication Ports, as well as the two Network Cards. Click Help to view instructions for configuring these settings.
- Click OK to close the screen. Click Update Device from the Device Profile screen to save your settings.
NOTE: You can also use the standard or optional Ethernet ports, the
optional RS485 ports, or the ANSI optical port to connect to and configure the
Nexus® 1500+ meter. See the meter’s manual (see page QS-1), and the software
manual (click Help>Contents from the CommunicatorPQA™ application’s Main
screen).
Program Meter Time
The meter is preset to the United States Eastern time. To change the meter
time:
1. From the Main screen’s Title bar, click Tools>Set Device Time.
2. You can either enter the time in the Time fields or click Use PC Time to
match the meter time with the PC time.
3. Click Send.
Program Meter Name
The meter’s name is used in database files and report titles. To give the
meter a unique name:
1. From the meter’s Device Profile screen, click General Settings>Labels, and
then double-click on one of the lines underneath to open the Labels screen.
2. Enter a name for the meter in the Meter Designation field.
3. Click OK.
IMPORTANT! When you have made changes to the meter’s Device Profile,
click Update Device at the bottom of the Device Profile screen, to send the
new settings to the meter. The meter will reboot and then you can reconnect to
it.
Nexus® is a registered trademark of Electro Industries/GaugeTech. The distinctive shape, style, and overall appearance of the Nexus® 1500+ meter is a trademark of Electro Industries/GaugeTech. CommunicatorPQA TM , MeterManagerPQA TM , and EnergyPQA.com are trademarks of Electro Industries/GaugeTech. Windows® is a registered trademark of Microsoft Corporation in the United States and/or other countries. Littelfuse® is a registered trademark of Littelfuse, Inc. https://electroind.com/