Electro Industries Shark 100S/200S Meter User Guide

June 6, 2024
Electro Industries

Electro - LOGO Shark® 100S/200S Quickstart

Shark® 100S/200S Meter Quickstart Guide

CAUTION! Installation of the Shark® 100S/200S meter must be performed only by qualified personnel who follow standard safety precautions during all procedures. That personnel should have appropriate training and experience with high voltage devices. Appropriate safety gloves, safety glasses, and protective clothing are recommended.
During normal operation of the Shark® meter, dangerous voltages flow through many parts of the unit, including ing: Terminals and any connected CTs (Current Transformers) and PTs (Potential Transformers),  all I/O Modules and their circuits. All Primary and  Secondary circuits can, at times, produce lethal voltages and currents. Avoid contact with any current-carrying surfaces.
Do not use the meter or any I/O device for primary protection or in an energy- limiting capacity. The meter can only be used as secondary protection.

IMPORTANT! Refer to your meter’s Installation and Operation Manual for additional safety warnings before performing installation, wiring, or maintenance of your meter. See the link to the manual, below.
NOTE: This Quickstart Guide gives basic installation, wiring, and programming instructions. For additional meter operation and programming information, refer to your  meter’s Installation and Operation Manual and the Communicator  PQA TM, MeterManagerPQA TM, and EnergyPQA.com TM  Software User Manual on EIG’s website:

User Manual:
Shark® 100S Meter
https://www.electroind.com/products/shark-100s-economical-wifi-submeter/

Shark® 200S Meter
https://www.electroind.com/products/shark-200s-advanced-data-logging-wifi- submeter/
From the webpage, click Technical Documents>User Manual.

Software Manual:https://www.electroind.com/products/communicatorpqa- software-application-5/ From the webpage, click Technical Documents>User Manual.

CommunicatorPQA TM Setup Software:https://www.electroind.com/products /communicatorpqa-software-application-5/
From the webpage, click Download Compaq Pro. To get a Professional license for the software, email [email protected] or call 516-334-0870.
All EIG’s metering and software products’ literature can be accessed from: https://www.electroind.com/all-products/
For software and metering integration, EIG’s Technical Support Engineers are available on an hourly or daily basis to help with typical commissioning assistance, which includes:

  • Verifying meter installation and wiring.
  • Verifying proper system integration.
  • Working with 3rd parties to ensure cross-compatibility.
  • Advising users on best practices for optimal implementation. You can reach Technical Support from 8 a.m. to 8 p.m. EST, Monday-Friday, at 516-334-0870.

Electro Industries Shark 100S 200S Meter - During
normal

WARNING! During normal operation of the meter, dangerous voltages flow through many parts of the meter, including Terminals and any connected CTs and PTs, all I/O modules, and their circuits. All Primary and Secondary circuits can, at times, produce lethal voltages and currents. Avoid contact with any current-carrying surfaces. Before performing ANY work on the Shark® 100S/200S meter, make sure the meter is powered down and ALL circuits are de-energized.

IMPORTANT! All wiring is done with the cover open, as shown above. The front cover support fits into its base. Make sure the support is up before closing the front cover.

Electro Industries Shark 100S 200S Meter - Ethernet
communica

NOTE: Jumper 2 (JP2) must be set for either RS485 or Ethernet communication (see figures on the left for location of JP2 and settings). Put the jumper on positions 2 and
3 for LAN (Ethernet) communication, or on 1 and 2 for RS485 communication.

Select a wiring diagram to meet your application. See User Manual for additional wiring diagrams.

Program Settings Using the Faceplate Buttons: (MENU, ENTER, DOWN ARROW, RIGHT ARROW) See the figure below for the location of the faceplate buttons.

Electro Industries Shark 100S 200S Meter - Faceplate
Buttons

Access Configuration Mode:

  1. Push the MENU button – you will see the display on the right; it will be blinking.
  2. Press the DOWN arrow once. CFG (Configuration) moves to the top of the display.
  3. Press the ENTER button. You will see the Configuration menu, shown on the right.
  4. Press the DOWN ARROW and then press the ENTER button. You will see the CT numerator setting screen (Ct-n). The current CT numerator is shown in the second line. To change the setting, press the DOWN ARROW until the value you want is displayed. Then press the RIGHT ARROW to move to the next digit. Repeat until the setting is done.
  5. Press the ENTER button to go to the CT denominator screen (CT-d). This setting is displayed only – it can’t be changed.
  6. Press the ENTER button to go to the CT Scaling setting screen (CT-S). The current Scaling is shown in the second line. Press the DOWN ARROW to choose another value. You can choose 1, 10, or 100.
  7. Press the ENTER button to go to the PT numerator setting screen (Pt-n). The current PT numerator is shown in the second line. To change the setting, press the DOWN ARROW until the value you want is displayed. Then press the RIGHT ARROW to move to the next digit. Repeat until the setting is done.
  8. Press the ENTER button to go to the PT-denominator screen (Pt-d). The current PT denominator is shown in the second line. To change the setting, press the DOWN ARROW until the value you want is displayed. Then press the RIGHT ARROW to move to the next digit. Repeat until the setting is done.
  9. Press the ENTER button to go to the PT Scaling setting screen (PT-S). The current Scaling is shown in the second line. Press the DOWN ARROW to choose another value. You can choose 1, 10, 100, or 1000. NOTE: See example CT and PT Settings on the next page.
  10. Press the ENTER button to go to the Connection setting screen (Connect). The current setting is shown in the second line. Press the DOWN ARROW to choose another value. You can choose 3 EL (element) WYE, 2 Ct del (Delta), or 2.5 EL WYE.
  11. Press the ENTER button to go to the meter Address setting screen (ADR). The meter’s current address is shown in the second line. To change the setting, press the DOWN ARROW until the value you want is displayed. Then press the RIGHT ARROW to move to the next digit. Repeat until the setting is done. Valid address- es are from 001  through 247. If you are using the Ethernet option, do NOT change anything on this screen.
  12. Press the ENTER button to go to the meter Baud Rate setting screen (bAUd). The meter’s current Baud Rate is shown in the second line. Press the DOWN ARROW to choose another Baud Rate. You can choose 9600 (choose this for RS485 connection), 19.2 (19200), 38.4 (38400) or 57.6 (57600). If you are using the Ethernet option, do  OT change anything on this screen.
  13. Press the ENTER button to go to the meter Protocol setting screen (Prot). The meter’s current Protocol is shown in the second and third lines. Press the DOWN ARROW  to choose another communication Protocol. You can choose Mod RTU (Modbus RTU; choose this for RS485 connection), Mod ASCI (Modbus ASCII), or  DNP (DNP 3.0). If you are using the Ethernet option, do NOT change anything on this screen.
  14. Press the ENTER button to go to the Scroll setting screen (SCrL). The current setting is shown in the second line. Press the DOWN ARROW to choose another setting.  You can choose YES (the meter readings will scroll on the display) or no (the meter readings will not scroll on the display). 
  15. Press the MENU button twice. You will see the Store Settings screen (Stor ALL?) The default setting is YES. To save the settings you’ve made, press the ENTER button.  You will see the confirmation screen (Stor ALL done) and then the meter resets.
    NOTE: If you do not want to save your settings, press the RIGHT ARROW. YES, changes to no. Press the ENTER button. Example CT Settings: 200/5 Amps: set the Ct-n value as 200, Ct-S value as 1. 800/5Amps: set the Ct-n value as 800, Ct-S value as 1. 2000/5 Amps: set the Ct-n value as 2000, Ct-S value as 1 10,000/5 Amps: set the Ct-n value as 1000, Ct-S value as 10. Example PT Settings:
 200/5 Amps:     set the Ct-n value as 200, Ct-S value as 1.
   800/5Amps:   set the Ct-n value as 800, Ct-S value as 1.
   2000/5 Amps:    set the Ct-n value as 2000, Ct-S value as 1
   10,000/5 Amps:     set the Ct-n value as 1000, Ct-S value as 10.

For additional programming instructions for the faceplate buttons, see Chapter 7 in your meter’s User Manual (see page QS-1).

Follow these steps to connect to the meter via the IrDA port:

  1.  Connect the meter to the PC. EIG offers a USB to IrDA cable, which can be ordered from EIG’s website: https://www.electroind.com/products/usb-to-irda-adapter/.
  2. Open CommunicatorPQA TM software (see page QS-1 for the download link).
  3. Click Connect in the Icon Bar.
  4. You will see the Connect screen. Make sure your settings match the ones shown on the right (use pull-down menus).Electro Industries Shark 100S 200S Meter - Connect screen
  5. Click Connect. The Device Status screen opens, confirming the connection. Click OK to close the Device Status screen.6. Click the Profile icon in the Icon bar.
  6. The Device Profile screen opens. For the 100S, the tabs on the top of the screen let you choose setting screens. For the 200S, there is a Tree menu on the left side of the screen.Electro Industries Shark 100S 200S Meter - Device Profile screen opens

Electro Industries Shark 100S 200S Meter - Shark® 200S
Meter NOTE: The screens shown here are from the Shark® 100S meter. Some of the Shark® 200S meter screens have additional settings. See Chapter 8 in the software user manual for details.

Program CT, PT Ratios:

  1. This is the first Device Profile screen. To return to this screen from another settings screen, click the Scaling tab.
  2. These are the settings:Electro Industries Shark 100S 200S Meter - Program CT, PT Ratios a. CT Numerator (enter the value you want), Denominator (display only), Multiplier (1, 10, or 100), CT Fullscale (Calculated automatically)
    b. PT Numerator (enter value you want), Denominator (enter the value you want), Multiplier (1, 10, 100, or 1000), PT Fullscale (Calculated automatically)

NOTE: Voltage Full Scale = PT Numerator x PT Multiplier Current Full Scale = CT Numerator x CT Multiplier
IMPORTANT! Specify Primary and Secondary Voltage in Full Scale (NOT Ratios).
NOTE: You can also enter the Ratios for CT/PT Numerator and Denominator and click the Update CT/
Update PT buttons to let the software calculate the Numerator, Denominator, and Multiplier for you.
You can then empty the Ratio fields and click the Update Ratio buttons to confirm the calculated settings: you will see the same ratios you initially entered.
See Chapter 8 (200S) or Chapter 9 (100S) in the software manual for additional screen settings instructions (see page QS-1; alternatively, you can click Help>Contents from the CommunicatorPQA TM software’s Main screen).

Program Communications:

  1. Click the Communication tab.
  2. The settings shown on the screen are the default settings for the meter’s IrDA (COM1 and RS485 (COM2) ports. You can change the settings, if necessary for your application. To revert to the default RS485 port settings, click Set COM2 to default (the 200S meter does not have this option).
    NOTE: If you do not have the RS485 option, you can ignore those settings.

Electro Industries Shark 100S 200S Meter - Program
Communications Program Meter Time: The meter is preset to Eastern time. To change the meter time:

  1. From the Main screen’s Title bar, click Tools>Set Device Time.
  2. You can either enter the time in the Time fields or click Use PC Time to set the time using your PC’s time.
  3. Click Send.

Electro Industries Shark 100S 200S Meter - Program Meter
Time Program Meter Name:

To enter a name/ID for the meter:

  1. From the Device Profile screen, click the Settings tab.
  2. Input a new meter designation into the Device/Meter Designation field. Note that it is important to name each meter individually since the meter name is used to name the log databases when logs are downloaded. See Chapter 8 (200S) or Chapter 9 (100S) in the software manual for an explanation of the other settings on this screen.

IMPORTANT! When you have made changes to the meter’s Device Profile, click Load Profile at the bottom of the Device Profile screen to send the new settings to the meter. The meter will reboot and then you can reconnect to it. Note that you can also click Save Profile to save your changes without sending them to the meter.

Electro Industries Shark 100S 200S Meter - Load
ProfileShark® is a registered trademark of Electro Industries/GaugeTech. CommunicatorPQA TM , MeterManagerPQA TM are trademarks of Electro Industries/GaugeTech.
https://electroind.com/

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Electro Industries User Manuals

Related Manuals