Instrument description

The Sauermann Si-PM3 is a digital differential pressure manometer measuring instrument.
In addition to the measurement of pressure, the airflow and air velocity can be calculated.

A. – Pressure hose
B. + Pressure hose
C. LCD screen
D. On/Off & backlight button
E. Hold/Min/Max/Live value button
F. Clear tubes

sauermann Si-PM3 Digital Differential Pressure Manometer fig
1

Safety and environment

About this document
Please read this document and familiarize yourself with the product before putting it to use. Keep this document on hand so that you can refer to it when necessary. Pass this documentation on to any subsequent users of the product.

Avoid personal injury/damage to equipment

  • This device has been developed for pressure measurement and for indoor use. Please always use the device in accordance with its intended use
    and within parameters described in the technical features in order not to compromise the protection ensured by the device.

  •  Only the accessories provided with the device or available as an option must be used.

  • Never store the product together with solvents, acids or other aggressive substances.

  • Only carry out maintenance and repair work that is described in the documentation. Follow the detailed steps when doing so. Use only original spare parts from Sauermann.

  • If the device falls or in case of similar inconveniences, or if an irregular malfunction appears, please do not use the device and bring it back to your distributor to ensure your own safety.

  • The device must not be used in ATEX zones according to applicable standards.

  • Do not use the device next to explosive gases, vapor or dust.

  • The device does not contain any internal part repairable by the user. Do not open the instrument.

  • This device can pose a risk for wearers of pacemakers. Respect a distance of at least 10 cm (4’’) between the device and the wearer.

  • Observe safety distances to products that can be damaged by the magnetic field (e.g. monitors, computers, credit cards).

  • Do not authorise pressures beyond the device limits. Please refer to the technical features described in this user manual.

Exclusions and restrictions of liability
The application operation is under the exclusive customer or user entity responsibility, who acknowledges using this system at his/her own risks. The customer or user entity explicitly exclude Sauermann and every other company through which it could have been sold of any kind of responsibility
or warranty regarding any direct, indirect, accidental, consecutive or non- consecutive damage that could have been subjected, for some or all, by partial or total non-respect, voluntary or involuntary, of recommendations, conditions and prerequisites indicated hereafter.

Symbols used
For your safety and in order to avoid any damage of the device, please follow the procedure described in this user manual and read carefully the notes preceded by the following symbol:
The following symbol will also be used in this user manual, please read carefully the information notes indicated after this symbol:
The following symbol will also be used in this user manual, please read carefully the information notes indicated after this symbol:
Protecting the environment
Send back the device at the end of it’s life cycle to a waste collection center for electrical and electronic components (according to local regulations), or send it back to your distributor to ensure the device is properly disposed of with respect to the environment.

Standard

This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and the receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Changes or modifications not expressly approved by Sauermann could voice the user’s authority to operate the equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation.

Technical specifications

Pr essur e| |

hPa, mbar, Pa, mmH2O, inH2O, inHg, psi

| ±(1.5% of value

+0.2 hPa)

±(1.5% of value

+0.09 inH2O)

|

From -150 to +150 hPa

From -60 to 60 inH20

| 0.01 hPa / 0.001 psi / 0.01 inH20 / 1 Pa / 0.01 mbar /

0.1 mmH2O / 0.001 inHg

---|---|---|---|---|---

Air velocity displayed on the instrument is calculated at fixed conditions: L Pitot tube with a deprimogen coefficient of 1.0015, at 20°C (68°F) and 1013.25 hPa (29.92 inHg). When the app is used to display air velocity, these parameters can be modified.
All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.
Calculated values, only available on the app /
Calculated values

General features

sauermann Si-PM3 Digital Differential Pressure Manometer fig
8

*Battery life given at 20°C (68°F) with alkaline batteries
**If the instrument is stored outside the operating temperature (for example in a van, a warehouse, etc.), please wait for 10 minutes in its operating temperature before starting and using it.

Operating principle

Calculation of saturation pressure
This parameter must be calculated for air velocity calculation with the Si-PM3 differential pressure manometer instrument.
Psat: Saturation pressure (unit: Pa) H: Relative Humidity (unit: %RH) T: Temperature (unit: Kelvin K)

sauermann Si-PM3 Digital Differential Pressure Manometer fig
2 Calculation of air density
This parameter must be calculated for air velocity calculation with the Si-PM3 differential pressure manometer instrument.
ρ: Air density (unit: kg/m3)
Patm: Atmospheric pressure (unit: Pa) T: Temperature (unit : Kelvin K) Psat: Saturation pressure (unit: Pa)
sauermann Si-PM3 Digital Differential Pressure Manometer fig
3

Dimensions

sauermann Si-PM3 Digital Differential Pressure Manometer fig
4

Accessories

sauermann Si-PM3 Digital Differential Pressure Manometer fig
5

Operating instructions

Insert the batteries

  • Unscrew the batteries compartment cover at the back of the device and remove the
  • Put the 3 alkaline AAA LR03 5V batteries supplied with the instrument.
  • Carefully respect the
  • To close the batteries compartment, push the batteries cover back on, starting with the upper
  • Screw the batteries compartment

Turn on the instrument

  • Press & hold the ON/OFF

Perform an autozero

  • Press & hold the HOLD

  • Connect a pressure hose on the ‘‘+’’ of the device and on the ‘‘+’’ of the installation.

  • Connect the other pressure hose on the ‘‘-’’ of the device and on the ‘‘-’’ of the

  • The device displays the pressure

Select the unit

  • With the device turned
  • Long press simultaneously ON/OFF & HOLD keys to switch to the required measurement unit : Pa, hPa, mbar, inH2O, mmH2O, inHg, psi, m/s, fpm

Activate/deactivate the wireless communication

  • With the device turned Press simultaneously ON/OFF & HOLD keys to activate or deactivate the wireless communication.

  • When activated, the wireless communication icon flashes on the instrument screen.

  • The icon becomes fixed when the instrument is paired to a tablet or

Activate/deactivate the Backlight

  • With the device turned
  • Press ON/OFF key to activate or deactivate the

Activate/deactivate the Auto shut-off

  • * The device has an automatic shut-off set to 10

When the device starts, all the segments are During this time, press & hold the ON/OFF key to enter the “Power down menu“.

  • Press HOLD to activate/deactivate the auto shut-off.
  • Press & hold the ON/OFF key to exit the “Power down menu“.

Display Hold/Min/Max/Live values

  • *       * With the device turned on and measured values are
    • Press HOLD key to successively:
      • Freeze the display of measurement values
      • Display the minimum measured values
      • Display the maximum measured values
      • Restore the live display

Key operation

KEY SHOR T PRESS LONG PRESS (3 seconds)
ON/OFF Backlight ON/OFF Device ON/OFF
HOLD Hold / Min / Max / Live value Autozero
ON/OF F an d HOLD Wireless communication ON/OFF Pa /

hPa/ mbar / inH2O / mmH2O / inHg / psi / m/s

/ fpm

Use with a pitot tube

The Pitot tube is introduced perpendicular ipe by pre-determined points by the user.
The antenna is composed of an ellipsoidal nose (bow) maintained in parallel and in front of the flow to control.
The Tp total pressure (+) is picked up by the bow and is connected to the + sign of the manometer.
The Sp static pressure (-) picked up by the small holes located around the antenna is connected to the – sign of the manometer.
The difference between these two pressures is the pressure indicated on the Si-HVACR Measurement MobileApp and is equal to the dynamic pressure Dp = Tp- Sp.

sauermann Si-PM3 Digital Differential Pressure Manometer fig
6

Maintenance

Change batteries

  •  With the device turned off.
  • Unscrew the battery compartment at the back of the device and remove the cover.
  • Remove used batteries and insert new batteries (3 alkaline batteries AAA LR03 1.5 V) respecting the polarity.
  • To close the battery compartment, push the battery cover back on starting with the upper part.
  • Screw the battery compartment cover.

Clean the instrument

  • Clean the housing with a damp cloth (soap suds) if it gets dirty.
  • Do not use aggressive cleaning agents or solvents.

Warranty

Instruments have 2-year guarantee for any manufacturing defect.

Mobile App

The Si-HVACR Measurement MobileApp allows to view and record measurements in real-time.
Main features:

  • Easily view different parameters
  • Browse saved measurements history and data graphs (average, min & max values, etc.)
  • Create reports (PDF, CSV or XML format) and add up to four (4) photos

sauermann Si-PM3 Digital Differential Pressure Manometer fig
7

Sauermann Industrie
ZA Bernard Moulinet
24700 Montpon
France
T. +33 (0)5 53 80 85 00
services@sauermanngroup.com
Sauermann NA
140 Fell Court, Ste. 302 Hauppauge, New York 11788
T. (+1) 631-234-7600
F. (+1) 631-234-7605
info.usa@sauermanngroup.com
Sauermann GmbH
Leibnizstraße 6
D – 74211 Leingarten
T. +49 (0)7131/399990
F. +49 (0)7131/399992
info.germany@sauermanngroup.com
Sauermann UK
Units 7-9, Trident Business Park Amy Johnson Way
Blackpool – FY4 2RP
T. +44 (0) 870 950 6378
F. +44 (0) 870 950 6379
info.uk@sauermanngroup.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals