LUDLUM 4525-5000 Generation Iv Series Radiation Portal Monitor Installation Guide
- June 6, 2024
- LUDLUM
Table of Contents
4525-5000 Generation Iv Series Radiation Portal Monitor
LUDLUM MODEL 4525 GENERATION IV SERIES RADIATION PORTAL MONITOR MODELS
4525-5000 4525-7500 4525-10000 4525-12500 4525-15000
INSTALLATION MANUAL
July 2021 Serial Number GM5179 and Succeeding
Serial Numbers
LUDLUM MODEL 4525 GENERATION IV SERIES RADIATION PORTAL MONITOR MODELS
4525-5000 4525-7500 4525-10000 4525-12500 4525-15000
INSTALLATION MANUAL
July 2021 Serial Number GM5179 and Succeeding
Serial Numbers
STATEMENT OF WARRANTY
Ludlum Measurements, Inc. warrants the portal monitor covered in this manual
to be free of defects due to workmanship, material, and design for a period of
24 months from the date of delivery. The calibration of a product is warranted
to be within its specified accuracy limits at the time of shipment.
Accessories such as computers, Universal Power Supplies (UPSs), cameras,
network equipment, etc., are warranted by the individual manufacturer, and are
not covered by Ludlum Measurements.
This warranty excludes the replacement of instruments, detectors, or parts
that are broken due to excessive physical abuse, acts of nature such as
lightening, or used for purposes other than intended.
There are no warranties, express or implied, including without limitation any
warranty of merchantability or fitness, which extend beyond the description of
the face thereof. If the product does not perform as warranted herein, the
purchaser’s sole remedy shall be repair, recalibration, or replacement, at the
discretion of Ludlum Measurements. In no event will Ludlum Measurements be
liable for damages, lost revenue, lost wages, or any other incidental or
consequential damages, arising from the purchase, use, or inability to use
product.
RETURN OF GOODS TO MANUFACTURER
If equipment needs to be returned to Ludlum Measurements, Inc. for repair or
calibration, please send to the address below. All shipments should include
documentation containing return shipping address, customer name, telephone
number, description of service requested, and all other necessary information.
Your cooperation will expedite the return of your equipment.
LUDLUM MEASUREMENTS, INC. ATTN: REPAIR DEPARTMENT 501 OAK STREET SWEETWATER,
TX 79556
866-420-9732
325-235-9732 FAX
325-235-8768
PORTAL MONITOR TECH SUPPORT
800-717-9506 (24 hours) or
325-235-9732
LUDLUM MEASUREMENTS, INC.
501 Oak Street
P.O. Box 810 Sweetwater, Texas 79556
Website: www.ludlums.com
800-622-0828 /
325-235-5494
DESIGNER AND MANUFACTURER
OF
Scientific and Industrial
Instruments
Ludlum Model 4525 Site Preparation Checklist
This check list and the described photos must be submitted to
rsdtech@ludlums.com prior to scheduling the Commissioning and Startup of your
system. If no email is available these may be Faxed to
325-235-8768.
Please be aware there will be additional charges in the case of delays
incurred if site is not prepared by arrival.
Yes/No/NA
Pre-Commissioning & Start-up Site Preparation
Foundations placed where detectors have a 10 foot (3 M) “buffer zone” in all
directions (Installation Manual Drawings 4511-375).
Install detectors in approved stands, anchored in concrete and placed in an
approved configuration.
Stands must be diagonally square with one another within 0.5 inch (13 mm) .
Assure the 4525-7000 Series Control Box is to be mounted on the back of the
master detector (#1) stand leaving adequate space for technicians to perform
work safely.
AC power must be in an Isolated conduit with a dedicated, visibly
identifiable, breaker capable of “lock out tag out” locks.
Install Detector cable(s) (Belden 8774, 9 pair 100-foot (30 M) provided) in
conduit(s) between each detector and the control box, with 24 inches (61 cm)
over pull on each end. (Systems with more than 2 detectors, run cable and
conduit between the primary and secondary detectors.)
Mount Infrareds as shown in site layout drawings provided, in the installation
manual, and in locations specified on each IR assembly, determined by system
purchased.
Install Cat 5e Ethernet cable, 250 foot (72 M) provided, in conduit and pulled
from control system to computer location in office area with 24 inches (61 cm)
over pull on each end.
Computer and printer must be in an easily accessible location, (wall-mount
system purchased from Ludlum’s is to be mounted on a wall) with proper power
and UPS.
Auxiliary remote, mounted with conduit installed and cable pulled (Belden
9946, 10 conductors 100foot [30 m] provided)
Any additional accessories Camera(s), strobe/horn, traffic lights, P2P
wireless, etc., with cable(s), installed, according to recommended
specifications.
Customer is responsible to provide a man lift and an OSHA certified lift
operator for all overhead detectors. If not provided the technician will
arrange for each at customer’s expense.
Customer will provide a safe, stable and clean OSHA certified stepladder for
technician’s use.
Photos provided as described in the Photo Requirement List (Next Page)
Comments:
Company: __ Location: __ Signature/Date:
LMI/RSD Form Rev 1.1
jmg
6 Aug 2019
LUDLUM MEASUREMENTS, INC.
501 Oak Street
P.O. Box 810 Sweetwater, Texas 79556
Website: www.ludlums.com
800-622-0828 /
325-235-5494
DESIGNER AND MANUFACTURER
OF
Scientific and Industrial
Instruments
Ludlum Model 4525 Site Photo Requirements
This list of Photos and the Check List must be submitted to
rsdtech@ludlums.com prior to scheduling the Commissioning and Start-up of your
system. If no email is available these may be Faxed to
325-235-8768.
Please be aware there will be additional charges in the case of delays
incurred if site is not prepared by arrival.
Yes/No/NA
Pre-Commissioning & Start-up Site
3 different angles minimum–Photo(s) showing both detectors in relation to the
scale and to ensure the 10 Foot (3M) buffer zone is adequate. (REF:
Installation Manual 4511-375) .
1 each–showing the Control Box mounted on the back side of detector #1 stand
and height from ground for easy accessibility, as specified in Installation
Manual.
2 each–Face of each detector, with doors closed, showing the placement of all
infrared sensors.
2 each–Face of each detector, with doors Opened, showing cables pulled through
conduits and 24 inches (61cm) over pull.
2 each–interior of the control box showing the A/C power lines, both detector
cables, auxiliary remote cable, sensor wiring and the Cat-5e network cable
with 24 inches (61cm) over pull.
1 each–(If applicable) Photos of the horn/strobe unit and/or camera and/or
traffic light, and/or Wireless P2P system (both antenna mounted with
unobstructed signal path and connecting cables on each end), mounted with
conduit(s) and entering the control box.
2-4 each–Photo(s) showing the mounted computer, printer and network equipment
and cables with Cat5e cable connecting exterior detector, if using purchased
system from Ludlum. Photo(s) should reflect the placement of the computer,
monitor and printer after installation whether customer supplied or purchased
with the system(s). The system will be easily accessible and the monitor
should be at eye level seated or standing.
1 each–Photo of the interior auxiliary remote mounted in its location (if
purchased). The photo should also include the cable from the external detector
in proximity to the remote.
1 each–Photos of any additional equipment and its location with respect to its
function; such as wireless access points and antennas. These photos should
clearly depict the wiring has been installed to control these devices.
Additional photos– any obstacles, barriers, or other anomalies that could
possibly impact the installation and operation of the system as designed
should be documented and presented photographically with the required photos
and noted below in the comments field.
Comments:
Company: __ Location: __ Signature/Date:
LMI/RSD Form Rev 1.1
jmg
6 Aug 2019
Overview
Detector Stand Installation
Shipping Crates Stand Location Buffer Zone Lightning Protection Stand
Orientation Typical Stand Setup Setting Up The Stands Conduit Requirements
Cable Requirements Wiring Detector Wiring Remote Display Cat-5E LAN Cabling
Supervisor Computer Miscellaneous Requirements
Software and Network Installation
Software Installation Network Installation Software License Agreement
Drawings and Diagrams
Table of Contents
1
2
2-1 2-7 2-7 2-8 2-10 2-10 2-15 2-15 2-16 2-17 2-18 2-18 2-19 2-19
3
3-1 3-2 3-8
4
Ludlum Measurements, Inc.
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 1
Section
1
Overview
The Ludlum Model 4525 Radiation Portal Monitor or “gate monitor” is designed
to detect very low levels of radiation, typically in vehicle loads as they are
driven between the detectors. Usually the radiation detectors are placed right
before a weigh scale. This manual is intended to assist you in the
installation of the system.
Several different models and options are available of the Model 4525. The
Generation IV Series can be optimally arranged to monitor moving vehicles
entering into the system. Each detector system can be configured with two to
six large detectors.
In general, the full model number tells the number of detectors the Model
45255000 is a two-detector system, the Model 4525-7500 is a three-detector
system, the 4525-10000 system has four detectors, the Model 4525-12500 has
five detectors, and the Model 4525-15000 has six detectors. The model number
suffix reflects the total cubic inches of scintillation material used by the
combined system. Generation IV systems are upgradeable to more complex
configurations.
The detectors are normally mounted to the side of the vehicle, and also
sometimes above the vehicle. The detectors are centered around the typical
load; your situation or location might require the detectors to be higher or
lower than the dimensions shown in the back of this manual.
Each system comes with a wall-mount computer display, printer, and universal
power supply (UPS). This computer logs data and displays the current status of
the system. It is typically placed inside the scale house, or in close
proximity to the scale operator. A remote display, with status lights and a
reset button, is also provided. The remote can show the status and allow
someone to reset alarms whenever the main computer is inaccessible. It is
typically placed in the scale house, or sometimes under a weather-protected
porch.
Each system uses infrared sensors to detect the vehicle’s presence, and thus
switch from measuring the background radiation to checking for an alarm.
Multiple sets of sensors are used to measure the speed of the vehicle and to
ensure that the vehicle presence is sensed throughout the passage of the
vehicle. The range of vehicle sizes, from flatbed trailers to tall drop-off
boxes, necessitates some care in positioning the sensors. The drawings in the
back of the manual suggest some mounting heights that have worked at many
locations.
Ludlum Measurements, Inc.
Page 1-1
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Section
2
Detector Stand Installation
This procedure is intended to outline the stand installation of the Ludlum Model 4525-5000, 4525-7500, Model 4525-10000, Model 4525 12500, and Model 452515000 Radiation Detection Systems. It does not cover actual termination of cables, which is normally performed by Ludlum Measurements, Inc. (LMI) technicians. The stand installation covers the following items:
Shipping Crates
Stand Location Buffer Zone
Stand Orientation
Typical Stand Setup
Setting Up The Stands
Conduit Requirements
Cable Requirements
Remote Display
CAT-5E LAN Cabling
-
Supervisor Computer (optional)
-
Monitor Computer (optional)
-
Miscellaneous Requirements
Note:
Drawings of the model numbers listed above are located in the back of this
manual. Before building and installing the stands, please review the drawings
of the Model 4525 that you have ordered to assist in the installation process.
Shipping Crates
Each system may be purchased with or without the steel stands that provide
protection to the radiation detectors. Purchase of the steel stands from
Ludlum Measurements, Inc. facilitates the installation process. The following
lists the contents of the shipping crates.
Ludlum Measurements, Inc.
Page 2-1
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
CRATE CONTENTS OF THE MODEL 4525-5000 WITHOUT STANDS
The system is shipped in one crate containing:
Two large (approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.})
white detector boxes labeled Detector 1 and Detector 2
One 30.5 m (100 ft) roll of cable for the detectors (Belden 8774 or
equivalent) One 76.2 m (250 ft) roll of CAT-5E cable for Ethernet connection
(Belden 1501A
or equivalent) One remote display with 30.5 m (100 ft) cable (Belden 9946 or
equivalent) One hardware mounting kit containing the following:
8 qty. ½-inch x 2 ¼-inch long hex bolts 8 qty. ½-inch hex nuts 8 qty. ½-inch
lock washers 16 qty. ½-inch flat washers If a computer is purchased with the
system, it will be inside the crate. Any other optional items will be packed
in the crate with the detectors. The total shipping weight of the crate is
approximately 681 kg (1500 lb).
CRATE CONTENTS OF THE MODEL 4525-7500 WITHOUT STANDS
The system is shipped in two crates. The first crate contains: Detector 1 and
Detector 2.
Two large (approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.})
white detector boxes labeled Detector 1 and Detector 2.
The second crate contains: Detector 3 and peripherals. One large
(approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.}) white
detector boxes labeled Detector 3. One 30.5 m (100 ft) roll of cable for the
detectors (Belden 8774 or equivalent) One 76.2 m (250 ft) roll of CAT-5E cable
for Ethernet connection (Belden 1501A
or equivalent) One remote display with 30.5 m (100 ft) cable (Belden 9946 or
equivalent) One hardware mounting kit containing the following:
12 qty. ½-inch x 2 ¼-inch long hex bolts 12 qty. ½-inch hex nuts 12 qty.
½-inch lock washers 24 qty. ½-inch flat washers
Ludlum Measurements, Inc.
Page 2-2
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
If a computer is purchased with the system, it will be inside the crate. Any
other optional items will be packed in the crate with the detectors. One crate
is approximately 681 kg (1500 lb), and the other is approximately 454 kg
(1000 lb).
CRATE CONTENTS OF THE MODEL 4525-10000 WITHOUT STANDS
The system is shipped in two crates.
The first crate contains: Detector 1 and Detector 2 and peripherals.
Two large (approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.})
white detector boxes labeled Detector 1 and Detector 2
One 30.5 m (100 ft) roll of cable for the detectors (Belden 8774 or
equivalent) One 76.2 m (250 ft) roll of CAT-5E cable for Ethernet connection
(Belden 1501A
or equivalent) One remote display with 30.5 m (100 ft) cable (Belden 9946 or
equivalent) Four infrared sensor components with conduit One hardware mounting
kit containing the following:
16 qty. ½-inch x 2 ¼-inch long hex bolts 16 qty. ½-inch hex nuts 16 qty.
½-inch lock washers 32 qty. ½-inch flat washers If a computer is purchased
with the system, it will be inside the crate. Any other optional items will be
packed in the crate with the detectors. One crate is approximately 681 kg
(1500 lb), and the other is approximately 454 kg (1000 lb).
The second crate contains: Detector 3 and Detector 4.
Two large (approximately (meters)m {46 in x 46 in x 9 in.}) white detector
boxes labeled Detector 3 and 4.
Ludlum Measurements, Inc.
Page 2-3
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
CRATE CONTENTS OF THE MODEL 4525-12500 WITHOUT STANDS
The system is shipped in two crates.
The first crate contains: Detector 1 and Detector 2 and peripherals.
Two large (approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.})
white detector boxes labeled Detector 1 and Detector 2
One 30.5 m (100 ft) roll of cable for the detectors (Belden 8774 or
equivalent) One 76.2 m (250 ft) roll of CAT-5E cable for Ethernet connection
(Belden 1501A
or equivalent) One remote display with 30.5 m (100 ft) cable (Belden 9946 or
equivalent) Four infrared sensor components with conduit One hardware mounting
kit containing the following:
20 qty. ½-inch x 2 ¼-inch long hex bolts 20 qty. ½-inch hex nuts 20 qty.
½-inch lock washers 40 qty. ½-inch flat washers If a computer is purchased
with the system, it will be inside the crate. Any other optional items will be
packed in the crate with the detectors. One crate is approximately 681 kg
(1500 lb), and the other is approximately 908 kg (2000 lb).
The second crate contains: Detector 3 and Detector 4 and Detector 5.
Three large (approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.})
white detector boxes labeled Detector 3, 4 and 5.
Ludlum Measurements, Inc.
Page 2-4
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
CRATE CONTENTS OF THE MODEL 4525-15000 WITHOUT STANDS
The system is shipped in two crates.
The first crate contains: Detector 1 and Detector 2 and peripherals.
Two large (approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.})
white detector boxes labeled Detector 1 and Detector 2
One 30.5 m (100 ft) roll of cable for the detectors (Belden 8774 or
equivalent) One 76.2 m (250 ft) roll of CAT-5E cable for Ethernet connection
(Belden 1501A
or equivalent) One remote display with 30.5 m (100 ft) cable (Belden 9946 or
equivalent) Four infrared sensor components with conduit One hardware mounting
kit containing the following:
24 qty. ½-inch x 2 ¼-inch long hex bolts 24 qty. ½-inch hex nuts 24 qty.
½-inch lock washers 48 qty. ½-inch flat washers If a computer is purchased
with the system, it will be inside the crate. Any other optional items will be
packed in the crate with the detectors. One crate is approximately 681 kg
(1500 lb), and the other is approximately 908 kg (2000 lb).
The second crate contains: Detector 3 and Detector 4 and Detector 5 and
Detector 6.
Four large (approximately 116.8 x 116.8 x 22.9 cm {46 in x 46 in x 9 in.})
white detector boxes labeled Detector 3, 4, 5, and 6.
Ludlum Measurements, Inc.
Page 2-5
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Pallet Contents of the Model 4525-5000 and 10000 with stands It is shipped on
one pallet that contains two large yellow I-beam frame assemblies with white
detectors attached. For a M 4525-5000, the pallet holds one detector per frame
assembly. For the M 4525-10000, the pallet holds 2 detectors per frame
assembly. The following items are strapped onto the pallet.
One 30.5 m (100 ft) roll of cable for the detectors (Belden 8774 or
equivalent) One 76.2 m (250 ft) roll of CAT-5E cable for Ethernet connection
(Belden 1501A
or equivalent) One remote display with 100 foot cable (Belden 9946 or
equivalent) The Model 4525-12500 and 4525-15000 will have four infrared
components with
conduit If a computer is purchased with the system, it will be shipped in a
smaller box
strapped to the pallet. Any other optional items. The total shipping weight of
the pallet with the Model 4525-5000 is approximately
1362 kg (3000 lb), Model 4525-10000 is 2270 kg (5000 lb).
PALLET CONTENTS OF THE MODEL 4525-7500, 12500, AND 15000 WITH STAND
The system comes on two pallets. The smaller pallet contains two large yellow
I-beam frame assemblies with white detectors attached. For a Model 4525-7500,
the pallet holds one detector per frame assembly. For the Model 4525-12500 and
15000, the pallet holds 2 detectors per frame assembly. On a Model 4525-7500,
the pallet contains Detector 1 and 2. For the Model 4525-12500 and 15000, the
pallet contains Detectors 1, 2, 3, and 4.
The large pallet contains a large yellow I-beam frame assembly with multiple
white detectors attached Also strapped to the large pallet are four leg
extensions to suspend the overhead frame over the scale or lane. On a Model
4525-7500 the pallet contains Detector 3. For the Model 4525-12500, the pallet
contains detector 5. For the Model 4525-15000, the pallet contains Detectors 5
and 6.
The following items are strapped onto the smaller pallet.
One 30.5 m (100 ft) roll of cable for the detectors (Belden 8774 or
equivalent) One 76.2 m (250 ft) roll of CAT-5E cable for Ethernet connection
(Belden 1501A
or equivalent) One remote display with 100 foot cable (Belden 9946 or
equivalent) The Model 12500 and 15000 will have four infrared components with
conduit. If a computer is purchased with a system, the computer and white
control box
enclosure will be shipped in smaller crates strapped to the pallet.
Ludlum Measurements, Inc.
Page 2-6
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Any other optional items.
The total shipping weight of both pallets for the Model 4525-7500 is
approximately 2043 kg (4500 lb), Model 4525-12500 is 3405 kg (7500 lb), Model
4525-15000 is 4086 kg (9000 lb).
UNPACKING
- Remove the cardboard and shrink wrap from the stand.
- Remove the peripherals from the crate. Store the peripherals in a safe location.
- On Models 4525-7500, 4525-12500, and 4525-15000, remove the Ibeam extensions and keep them accessible for preassembly.
Stand Location Buffer Zone
For best operation, locate the stands in an area where a 3 m (10 ft) buffer
zone can be maintained around the detectors. Typically the stands are mounted
about 3 m (10 ft) before the weigh scale. It is important that vehicles stay
out of this buffer zone except when they are moving slowly between the
detectors. Placing a stop sign at the entrance to this buffer zone is
recommended, as well as painting a line on the pavement. See Drawing 511 x
928P. Failure to correctly locate the system or failure to enforce the buffer
zone will result in more frequent false alarms. These false alarms are caused
by the system having an incorrect measurement of the true background radiation
level.
Lightning Protection
Ludlum Measurements offers an optional lightning protection setup to reduce
damage from a lightning strike. See drawing 511 x 1067 in the back of the
manual for an example. Contact an LMI representative for more information.
Ludlum Measurements, Inc.
Page 2-7
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Stand Orientation
Detector 1 is connected to the office supervisor computer and mains power.
Detector 1 should go on the side with the four conduits coming out of the pad.
The other detectors are only connected to Detector 1. See figures below for
layout.
MODEL 4525-5000
MODEL 4525-7500
Ludlum Measurements, Inc.
Page 2-8
July 2021
Model 4525 Generation IV Series
Installation Manual
MODEL 4525-10000
Section 2
MODEL 4525-12500
MODEL 4525-15000
Ludlum Measurements, Inc.
Page 2-9
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Typical Stand Setup
To see a typical installation of the gate monitors, see the following
drawings: Model 4525-5000: Drawings 511 x 928 and 511 x 928A
Model 4525-7500: Drawings 511 x 928C and 511 x 928D Model 4525-10000: Drawings
511 x 928F and 511 x 928G
Model 4525-12500: Drawings 511 x 928I and 511 x 928J Model 4525-15000:
Drawings 511 x 928L and 511 928M
Notice:
In high background areas, it may be necessary to install additional steel or
lead behind the detector enclosure to reduce background.
Setting up the Stands
ANCHOR BOLT PATTERN Due to the close tolerances of the anchor bolt holes, the
anchor bolts must be placed according to the dimensions specified on the
Anchor Bolt Template drawing: 511 x 997.
LIFTING
There are 1 x 4 inch rectangular cutouts in the frame pieces that can be used
for lifting. Insert a properly rated nylon lifting strap through the cutout.
These can be used instead of lifting eyes or clevises.
The weight of the frame pieces vary depending on number and configuration of
detectors. See pages 2-2 through 2-7 for approximate weights of your specific
system.
Ludlum Measurements, Inc.
Page 2-10
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Note:
LMI recommends the use of a template to be sure the anchor bolt holes are
placed in the correct locations. These can be supplied by LMI. The part
numbers are: Models 4525-5000 template part number 7511-997 (2 each needed)
The notch on the templates should be placed toward the center of the lane. The
anchor bolt holes are a tight tolerance fit for the ¾-inch anchor bolt;
therefore, care must be taken when the anchor bolts are placed in the
concrete. Double-nut the anchor bolt to the template before the concrete cures
to ensure proper anchorbolt alignment.
LEVELING
- Once the concrete is dry and all the bolts are straight, the mounting points will need to be leveled. Shims may be used, but the following instructions assume the use of leveling nuts.
- Run a set of leveling nuts on the bolts as low as allowable (one nut per bolt).
- Place the flat template for the concrete holes on the leveling nuts.
- Start leveling from the highest nut, using a 0.61 m (2 ft) (or larger)
level in the pattern described below. The stands should be level and plumb
within 0.17 cm (1/16 of an inch) over a 0.61 m (2 ft) distance.
Model 4525 Generation IV Series Individual Stand Leveling
Ludlum Measurements, Inc.
Page 2-11
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
LIFTING
Systems purchased without stands:
Each detector weighs approximately 340 kg (750 lb).
For side detectors, position lifting straps around and under the detector and
carefully raise them into position. Use straps that are capable of holding the
weight and that will not scratch or otherwise damage the detectors when being
lifted into position. As an alternate method, the detector can be mounted to
the back plate, and then the detector and back plate can be lifted together
and set into place with a crane or other suitable device, using straps that
are properly rated. The weight of one detector and back plate is approximately
680 kg (1500 lb).
For overhead detectors, the detector can be carefully positioned on its door,
and then carefully lifted into place with a forklift or other lifting device.
As an alternate method, the detector can be mounted to the back plate, and
then the detector and back plate can be lifted together and set into place
with a crane or other suitable device, using straps that are properly rated.
The weight of one detector and back plate is approximately 680 kg (1500 lb).
Systems purchased with stands:
Model 4525-5000 and 4525-7500 side stands
The weight of one side of the stand assembly with one detector and one back
plate attached is approximately 907 kg (2000 lb). Attach properly rated
lifting lugs to the top of the stand I-beam legs and carefully lift each side
into position. Ensure that each leg is level and plumb and square with the
other side before securing it to the concrete pad.
Model 4525-10000, 12500, and 15000 side stands
The weight of one side of the stand assembly with two detectors and two back
plates attached is approximately 1588 kg (3500 lb). Attach properly rated
lifting lugs to the top of the stand I-beam legs and carefully lift each side
into position. Ensure that each leg is level and plumb and square with the
other side before securing it to the concrete pad.
Ludlum Measurements, Inc.
Page 2-12
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Model 4525-7500, 12500 and 15000 side stand leg extensions The weight of each
leg extension is approximately 34 kg (75 lb), and the system comes with 4
extensions. Attach properly rated lifting lugs to the top of the extension and
carefully lift it into position. Ensure that the extension is square with the
top of the leg and attach with the appropriate bolts.
Model 4525-7500, 12500, and 15000 overhead frame 4525-7500 and 12500
The weight of one overhead frame with one detector and one back plate attached
is approximately 907 kg (2000 lb). Position properly rated lifting straps
around and under the frame and carefully lift it into position. Attach the
frame with the appropriate bolts.
4525-15000
The weight of one overhead frame with two detectors and two back plates
attached is approximately 1588 kg (3500 lb). Position properly rated lifting
straps around and under the frame and carefully lift it into position. Attach
the frame with the appropriate bolts.
TORQUE SPECS FOR ¾-INCH BOLTS/NUTS (NOT SUPPLIED) The below estimated torque
specifications are offered as the suggested maximum torque values for threaded
products and are only a guide.
The recommended bolts for attaching the stands to the concrete stands are ¾
inch Grade 3 steel anchor bolts or better. Typical tightening torque is 234
ft-lb.
The recommended bolts for attaching the stands together and mounting the back
plates to the stand are 5/8 inch, either Grade 3 zinc plated steel or
stainless steel or better. Typical tightening torque is 96 ft-lb.
Ludlum Measurements, Inc.
Page 2-13
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
The recommended bolts for mounting the detectors to the stands are ½ inch, either Grade 3 zinc plated steel or stainless steel or better. Typical tightening torque is 69 ft-lb.
SQUARING
The opposing front outside corners of the stands should be within a half-inch
of each other on the diagonal reading. Be sure to take the readings at the
base of each set of stands (see figures below).
Ludlum Measurements, Inc.
Page 2-14
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Conduit Requirements
The bottom of each detector is pre-drilled for conduit connections. Refer to
Drawing 511 x 928Q for conduit sizes and locations in the concrete pad.
Note:
All additional conduit, from out of the concrete up to the enclosures, should
be LIQUID-TIGHT METALLIC.
Cable Requirements
AC POWER Incoming power from the breaker box for the control box enclosure
will be #14gauge wire for the “hot” and neutral connections, and a # 6-gauge
wire for the ground connection. OVER PULL FOR TERMINATION All wires will be
pulled, leaving a 0.61 m (24 in.) tail past the end of the conduit.
Caution:
Caution must be used when closing the electronics enclosures. Excessive force
could damage the electronic components.
Ludlum Measurements, Inc.
Page 2-15
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Wiring I/O Relay Board to Interconnect
I/O RELAY BOARD 5396-555 4 Pin MTA (Det 1, 2, or 3)
BELDEN CABLE 8774 OR EQUIVALENT
INTERCONNECT BOARD 5396-933 14 Pin MTA (to electronics)
4
Red from Red/White
14
3
White from Red/White
13
2
Black from Brown/Black
12
1
Brown from Brown/Black 11
10 Pin MTA (Det 1, 2, or 3) 10 9 8 7 6 5 4 3 2 1
Black from Black/Yellow 10
Yellow from Black/Yellow 9
Black from Blue/Black
8
Blue from Blue/Black
7
Black from Green/Black
6
Green from Green/Black 5
Black from White/Black
4
White from White/Black
3
Black from Red/Black
2
Red from Red/Black
1
Retain Orange/Black and Red/Green pairs for future use by folding them back against the insulated section of the cable, and secure them with electrical tape or zip ties.
Ludlum Measurements, Inc.
Page 2-16
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Detector Wiring
Primary and Secondary Preamp Cable
TO PREAMP
TO INTERCONNECT BOARD
6 Pin MTA Labeled Detector Primary, etc.
10 N/C
9 N/C
8 N/C
7 N/C
6 Green
6 Black from Green Black
5 Black from Green Black
5 Green
4 Black from Red Black
4 Black from White Black
3 Black from White Black
3 White
2 White
2 Black from Red Black
1 Red
1 Red
Black from Yellow Black, Yellow and Black from Blue Black, and Blue wire pairs are cut off and not used.
Interconnect to IR Sensor Wiring
This is for units with 2 sets of IRs. For units with 4 sets, duplicate this wiring for the other sensors.
Master/Primary (#1) Receiver Incoming Side “B”
Wire Color Blue/Grey White Brown
MTA# #3 #2 #1
Label Cut Black Wire Incoming Side
Receiver Outgoing Side Blue
3
“A”
White
2
Brown/Grey
1
Cut Black Wire Outgoing Side
Slave/Secondary (#2 on 4525-5000, 7500 #3 on 4525-10000, 12500, or 15000)
Transmitter Incoming Side
“B”
Blue/Grey
3
Blank
2
Brown
1
Cut Black Wire Incoming Side Cut White Wire
Transmitter Outgoing Side
“A”
Blue
3
Blank
2
Brown/Grey
1
Cut Black Wire Outgoing Side Cut White Wire
Ludlum Measurements, Inc.
Page 2-17
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Remote Display
MOUNTING The remote box must be securely attached to the wall using at least
two screws. Four holes have been provided to ensure proper attachment. Sound
judgment must be used to provide a secure platform for the depression of the
reset button. Refer to Drawing 511 × 207A (Model 4525 REMOTE/AUDIO BOX)
Locations of the remote box will be determined by the Location Supervisor (or
equivalent) at each location.
CABLING
The 30.5 m (100 ft) of cable for the remote is provided by the manufacturer
and should be Belden 9946 or equivalent.
Cabling will be run in conduit to the office or booth where the remote display
is mounted. Once inside, conduit is not required, but could be requested by
the Location Supervisor.
Cables outside of conduit will be secured every 0.30 m (1 ft) to prevent
entanglement and possible damage to the cable. The cable will be run into the
remote box leaving a 0.61 cm (2 ft) tail past the inside of the box
CAT-5E LAN Cabling
The 76.2 m (250 ft) of the cable for the CAT-5E (Ethernet) shall be provided
by the manufacturer and shall be Belden 1501A or equivalent.
AT THE ELECTRONICS
The CAT-5E cabling must be run in separate conduit from the power cabling. All
wires will be pulled, leaving a 0.61 cm (2 ft) tail past the end of the
conduit (electronics side only).
IN THE OFFICE OR LAN ROOM
The cables must be long enough to reach the dedicated network switch or
computer neatly.
Ludlum Measurements, Inc.
Page 2-18
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 2
Supervisor Computer
The supervisor computer provides a common link from the monitor(s) to a common
screen. This allows the printing of alarms, adjusting of set points, and the
monitor of multiple systems at one time. The Supervisor Computer also records
data seen from all the systems for further analysis.
Miscellaneous Requirements
AC-MAINS POWER REQUIREMENTS Each system requires a 2-amp power source of
120240 Vac.
LMI recommends dedicated 10-20 amp breakers for each lane and clearly labeling
each breaker.
AC power should be delivered to the Master Detector and to the computer in
accordance with code requirements, which supersede these instructions. Such
requirements, for example, may require a disconnect device in clear sight of
the hard-wired control box.
Power entering the Master Detector must be grounded to a ground lug bushing
before connecting the ground to the equipment.
CONDUIT REQUIREMENTS All flexible conduit must be liquid-tight, metallic. All
connections to the system must be metallic fittings. All wiring must be inside
conduit except when inside buildings.
Ludlum Measurements, Inc.
Page 2-19
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
Section
3
Software & Network Installation
Software Installation
Hardware Requirements:
Windows XP Pro with SP3 or Windows 7 Pro (32-bit or 64-bit), Enterprise, or
Ultimate
Minimum PC Requirements:
1.6 GHz processor or greater
1 GB of memory (2 GB recommended)
64 GB hard drive for storing the database and the images
SVGA monitor capable of a resolution of 640 x 480 or greater
Sound card with speakers for audible voice alarms
Note:
Before installing any new software, please read the Ludlum Measurements
software license agreement at the end of this section and un-install all
previous versions.
The Supervisor will install automatically when the CD is loaded in the drive. To install the Data Viewer, navigate to the Data Viewer folder on the CD and doubleclick on “setup.exe.”
Ludlum Measurements, Inc.
Page 3-1
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
Network Installation
The software uses both UDP (User Datagram Protocol) and TCP (Transmission
Control Protocol) to communicate with the Model 4525. For communication
between the Supervisor software and the Model 4525, port 23 (TCP) and port
20034 (UDP) are used.
TOOLS REQUIRED
Wire Strippers
Network Cable Tester Network Cable Crimper
RJ-45 connectors appropriate for cable conductor type Category 5E Network
Cable, Stranded or Solid conductor. Stranded cable is generally used where the
network cable can be moved, such as patch cables. Solid cable is used where
the cable will be fixed, such as internal wiring in walls.
NETWORK EQUIPMENT
A 100 mega-bit switch with enough ports is needed to connect all Model 4525s,
workstations, and cameras (optional). Each computer workstation must have a
100 MB Ethernet network interface card (NIC) installed.
IP ADDRESSES
Each device on a network has a unique address. This number is called the
Internet Protocol (IP) Address. This number can either be dynamically or
statically assigned. A static IP address is assigned to the device and will
not change. A dynamic IP address is assigned by a Dynamic Host Configuration
Protocol (DHCP) server and will not always have the same IP address. The
format is a 32 bit numeric address written as four numbers separated by
periods (dot). Each of the four numbers range from 0 to 255.
Note:
The Model 4525s DO NOT support Dynamic IP Addresses and must be configured for
a static IP Address.
The Model 4525s, workstations, and cameras (optional) normally exist on a
separate network from any other computers/devices. The network is set up using
a Class C address range, which limits the total number of addresses
Ludlum Measurements, Inc.
Page 3-2
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
from 192.168.200.2 to 192.168.200.254 (192.168.200.1 is reserved for default.) Workstation IP addresses begin at 192.168.200.2. Model 4525 IP addresses begin at 192.168.200.4. Camera IP addresses begins at 192.168.200.20. Any other device will use IP addresses beginning at 192.168.200.200. The IP addresses are assigned as follows:
Workstation 1 Workstation 2
192.168.200.2 192.168.200.3
Model 4525 #1 Model 4525 #2 Model 4525 #3 Model 4525 #4
192.168.200.4 192.168.200.5 192.168.200.6 192.168.200.7
Camera #1 Camera #2 Camera #3 Camera #4
192.168.200.20 192.168.200.21 192.168.200.22 192.168.200.23
Wireless A Wireless B
192.168.200.228 192.168.200.229
MODEL 4525 NIC CONFIGURATION
If the Model 4525s have never been configured, use the IP Setup Tool.exe to
search for and display the current IP address configuration. Select each Model
4525 found and set the IP address according to the table above. The network
mask is always 255.255.255.0. The Gateway and DNS can be left at their default
values. The baud rate should be set to 57600. Click Set to save the settings
to the Model 4525 NIC.
WORKSTATION CONFIGURATION
1. Select Start/Control Panel/Network and Internet Connections. 2. Click on Network Connections. 3. Right click on Local Area Connection and select Properties. 4. Select Internet Protocol (TCP/IP) and click Properties. 5. Select “Use the following IP Address.” 6. Type in the IP address for this workstation. 7. Type in the subnet mask (255.255.255.0). 8. Leave all other fields set to the default values and click OK. 9. Click OK to close the Local Area Connection Properties window.
Ludlum Measurements, Inc.
Page 3-3
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
To check the IP address on a workstation, open a command prompt (Start/All
Programs/Accessories/Command Prompt) and type “ipconfig” and press [Enter].
The current network configuration for the Local Area Connection will be
displayed.
To test the network connection to any other device on the network, use the
“ping” command. This command will transmit data to the specified IP address
and display the time it takes to reach the remote address. If the destination
is unreachable, the remote address may not be on the network, or the
workstation may not be connected to the network.
CABLE TERMINATION Technical Specification for TIA/EIA 568A & 568B Standard for
CAT-5E Cable
T568A and T568B are the two color codes used in wiring RJ45 eight-position
modular plugs. The American National Standard Institute/Telephone Industry
Association/Electronics Industry Association (ANSI/TIA/EIA) wiring standards
allow both of these color codes. The only difference is that the orange and
green pairs are interchanged.
Because it provides backward compatibility for both one pair and two pair of
Universal Service Order codes (AT&T) and USOC wiring schemes, the T568A wiring
pattern is recognized as the preferred wiring pattern for this standard. This
standard should be used in all new installations; however, it makes absolutely
no functional difference which you choose.
The T568B standard is the most widely used wiring scheme, as it matches the
older AT&T 258A color code. It is also permitted by the ANSI/TIA/EIA standard,
but it provides only a single pair backward compatibility to the USOC wiring
scheme.
U.S. Government regulations require the use of the preferred T568A standard
for wiring done under federal contracts.
Ludlum Measurements, Inc.
Page 3-4
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
T-568A STRAIGHT-THROUGH ETHERNET CABLE
The T-568A Standard should be used in all new installations. T-568B STRAIGHT- THROUGH ETHERNET CABLE
Ludlum Measurements, Inc.
Page 3-5
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
RJ-45 CROSSOVER ETHERNET CABLE
A crossover cable is required to connect two devices directly without using a
hub or switch or when connecting two hubs together. A crossover cable is made
by wiring one end to the T-568A standard and the other end to the T-568B
standard.
Ethernet Cable Instructions
Note:
Do not deform, bend, stretch, staple, run parallel with power cables, or run
Ethernet cables near noise, inducing components!
The total length of wire segments between a device and a hub/switch or between
two devices cannot exceed 100 meters (328 ft) for 100Base-TX and 300 m (984
ft) for 10Base-T.
Looking at the connector with the pins at the top and facing you, pin 1 is on
the left and pin 8 is on the right.
Pin 1 White/Green Pin 2 Green Pin 3 White/Orange Pin 4 Blue Pin 5
White/Blue Pin 6 Orange Pin 7 White/Brown Pin 8 Brown
Ludlum Measurements, Inc.
Page 3-6
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
1. Strip off approximately 2.5 cm (1 in.) of the cable jacket. Be careful not
to nick any of the wires or you will need to start over.
2. Untwist the four pairs and straighten them out.
3. Arrange them in a fan shape following the color order above with the
White/Green wire on the left and the Brown wire on the right.
4. Bring the wires together until they touch. Double-check the order.
5. Cut the wires to make a 90 angle approximately 1.3 cm (0.5 in.) from the
end of the jacket. The wires must be cut straight so that they fit all the way
into the connector to make good contact with the pins.
6. Align Pin 1 of the cable with Pin 1 of the connector and insert the cable
into the connector. Push firmly so the wires go all the way to the top of the
connector, and the jacket goes into the connector by about 0.48 cm (0.19 in.).
Again, check to make sure the colors are in the right order. No more than 1.3
cm (0.5 in.) of the Ethernet cable should be untwisted; otherwise, it will be
susceptible to crosstalk.
7. Place the connector into the crimp tool and squeeze the handle hard.
8. Inspect the connector to make sure all pins were crimped.
9. Repeat steps 1-8 for the other end.
10. Use a cable tester to test the cable for shorts and crossed wires.
Note:
A straight-through cable is used to connect the Model 4525 to a computer when
a hub or switch is used. A crossover cable is used to connect the Model 4525
directly to a computer WITHOUT a hub or switch.
Ludlum Measurements, Inc.
Page 3-7
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
Ludlum Measurements, Inc.
Page 3-8
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
Ludlum Measurements, Inc.
Page 3-9
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 3
Ludlum Measurements, Inc.
Page 3-10
July 2021
Model 4525 Generation IV Series
Installation Manual
Section 4
Section
4
Model 4525-5000 system
Model 4525–7500 system
Model 4525–10000 system
Model 4525–12500 system
Model 4525–15000 system
Applicable to 4525-5000, 45257500, 4525-10000, 4525-12500, and 4525-15000
Drawings & Diagrams
Model 4525-5000 TYPICAL INSTALLATION, Drawing 511 x 928 Model 4525-5000
DETECTOR ELEVATION, Drawing 511 x 928A Model 4525-5000 RAIN SHIELD, Drawing
511 x 928Y Model 4525-5000 POST HOLE INSTALLATION, Drawings 517 x 9 through
517 x 9F (7 drawings) Model 4525-5000 SENSITIVE AREA, Drawing 511 x 928B
Model 4525-7500 TYPICAL INSTALLATION, Drawing 511 × 928C Model 4525-7500
DETECTOR ELEVATION, Drawing 511 × 928D Model 4525-7500 SENSITIVE AREA, Drawing
511 x 928E
Model 4525-10000 TYPICAL INSTALLATION, Drawing 511 × 928F Model 4525-10000
DETECTOR ELEVATION, Drawing 511 X 928G Model 4525-10000 SENSITIVE AREA,
Drawing 511 x 928H
Model 4525-12500 TYPICAL INSTALLATION, Drawing 511 × 928I Model 4525-12500
DETECTOR ELEVATION, Drawing 511 × 928J Model 4525-12500 SENSTIVE AREA, Drawing
511 x 928K
Model 4525-15000 TYPICAL INSTALLATION, Drawing 511 x 928L Model 4525-15000
DETECTOR ELEVATION, Drawing 511 x 928M Model 4525-15000 SENSITIVE AREA,
Drawing 511 x 928N
Model 4525 AREIAL VIEW (Buffer Zone), Drawing 511 x 928P Model 4525 Series
PLAIN VIEW, Drawing 511 x 928Q Model 4525 STAND RIGHT LEG, Drawing 511 x 928R
Model 4525 STAND LEFT LEG, Drawing 511 x 928S Model 4525 STAND EXETNSION,
Drawing 511 x 928T Model 4525 STAND BACK PLATE, Drawing 511 x 928U Model 4525
STAND OVERHEAD, Drawing 511 x 928V Model 4525 Series BLOCK OPTIONS, Drawing
511 x 998 Model 4525 REMOTE CABLE, Drawing 511 x 140 Model 4525 CONT-PRIM &
PREAMP CBL, Drawing 511 x 413 Model 4525 REMOTE, Drawing 511 x 207A
Ludlum Measurements, Inc.
Page 4-1
July 2021
Model 4525 Radiation Portal Monitor
Installation Manual
Section 4
Model 4525 COMPUTER, Drawing 396 x 850 Model 4525 ANCHOR BOLT TEMPLATE, Drawing 511 x 997 Model 4525 ANCHOR BOLT AND CONCRETE, Drawing 511 x 836 Model 4525 GEN IV LIGHTNING PROTECTION, Drawing 511 x 1067
Ludlum Measurements, Inc.
Page 4-2
July 2021
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>