Laserliner 083.011A ActiveFinder Voltage Tester Instruction Manual

June 6, 2024
Laserliner


ActiveFinder

ActiveFinder

**** Completely read through the operating instructions, the „Warranty and Additional Information“ booklet as well as the latest information under the internet link at the end of these instructions. Follow the instructions they contain. This document must be kept in a safe place and passed on together with the device.

Function/Application

Contactless test device for localizing electrical voltage (230 V AC) in cables, sockets, lamp holders, and fuses. Visual and acoustic signals indicate whether a voltage is present.

Safety instructions

  • The device must only be used in accordance with its intended purpose and within the scope of the specifications.
  • The measuring tools and accessories are not toys. Keep out of reach of children.
  • Modifications or changes to the device are not permitted, this will otherwise invalidate the approval and safety specifications.
  • Do not expose the device to mechanical stress, extreme temperatures or significant vibration.
  • If you are working with voltages higher than 24 V/AC / 60 V/DC, exercise extreme caution. Touching the electrical conductors at such voltages poses a risk of life-threatening electric shocks.
  • If the device comes into contact with moisture or another conductive residue, work must not be carried out under voltage. At and above voltages of 24 V/AC / 60 V/DC, the presence of moisture creates the risk of life-threatening electric shocks.
  • Clean and dry the device before use.
  • When using the device outdoors, make sure that the weather conditions are appropriate and/or that suitable protection measures are taken.
  • In overvoltage category III (CAT III – 1000 V), the voltage between the test device and earth must not exceed 1000 V.
  • Before taking any measurements, make sure that both the area to be tested (e.g. a line), the test device and the accessories used (e.g. connection cable) are in proper working order. Test the device by connecting it to known voltage sources (e.g. a 230 V socket in the case of AC testing).
  • The device must no longer be used if one or more of its functions fail or the battery charge is weak.
  • Observe the safety precautions of local and national authorities relating to the correct use of the device and any prescribed safety equipment (e.g. electrician‘s safety gloves).
  • Do not work alone in the vicinity of hazardous electrical installations and only under the guidance of a qualified electrician.
  • The measuring device must not be used as a substitute for a two-pole zero potential test.
  • The device measures the presence of electrostatic fields of sufficient strength.

If the field strength is too low voltage may still be applied although no warning signal is given. The following list of factors that influence the field strength does not claim to be complete: shielding, cable insulation (type, thickness), measurement distance, insulation between user and earth, special socket designs,condition of tester and of batteries.
Additional information on the use
Observe the technical safety regulations for working on electrical systems, especially:

  1. Safely isolated from the power supply,
  2. Securing to prevent the system from being switched on again,
  3. Checking zero potential, two-pole,
  4. Earthing and short-circuiting,
  5. Securing and covering adjacent live components.

Using artificial, optical emission (OStrV)
LED outlet (see Fig. A)
– The device works with LEDs of risk group RG 0 (exempt, no risk) in accordance with the latest versions of applicable standards relating to photo- biological safety (EN 62471:2008-09ff / IEC/TR 62471:2006-07ff).
Radiation power: Peak wavelength equals 456 nm. Mean radiance is below the limit values of risk group RG 0. When used for the intended purpose and under reasonably
foreseeable conditions, the accessible radiation of the LEDs is safe for the human eye and skin.
Safety instructions
Dealing with electromagnetic radiation and electromagnetic disruptions
– The measuring device complies with electromagnetic compatibility
regulations and limit values in accordance with EMC-Directive 2014/30/EU.
– The measuring device complies with safety and electromagnetic compatibility regulations and limit values in accordance with Directive 2014/35/EU
(Low Voltage Directive / LVD) and 2014/30/EU (Electromagnetic Compatibility Directive / EMC).
– Umarex GmbH & Co. KG hereby declares that the ActiveFinder complies with the essential requirements and other provisions of the European Low Voltage Directive 2014/35/EU (LVD) and the Electromagnetic Compatibility Directive 2014/30/EU. The EU Declaration of Conformity can be found in its entirety at the following address: http://laserliner.com/info?an=AAB
– Local operating restrictions – for example, in hospitals, aircraft, petrol stations or in the vicinity of people with pacemakers – may apply. Electronic devices can potentially cause hazards or interference or be subject to hazards or interference.
Symbols
Fig. B: Warning about hazardous electrical voltage: Unprotected live components inside the device housing are capable of posing a risk of electric shock.
Fig. C: Protection class II: The test device has reinforced or double insulation.
Fig. D: Overvoltage category III: Equipment in fixed installations and for applications where specific requirements with regard to the reliability and availability of equipment have to be met, e.g. circuit-breakers in fixed installations and devices used in industrial applications which are permanently connected to the fixed installation.
1 Insertion of batteries (see Fig. E)
Open the battery compartment and insert batteries according to the symbols.
Be sure to pay attention to polarity.
** The device is ready for use immediately once the batteries have been inserted. It does not have a separate ON/OFF switch and is therefore always active.
Device description (see Fig. F)**

  1. Detector tip
  2. ZOOM function ON/OFF
  3. Pocket clip
  4. Battery lamp ON/OFF
  5. Battery lamp
  6. The battery compartment on the rear of the device

** Before using the device, you should always test it on the main circuit you know to be operational within the specified voltage range. To avoid inaccurate measurements, check the device batteries prior to use by switching on the built-in battery lamp. (see Fig. A)
2. Localising electrical voltages
Fig. G: Position the detector tip in the area to be tested (e.g. cable, socket. etc.).
Fig. H: If voltage is present, the detector tip lights up, and a signal sounds.
**
For safety, check all three-phase conductors (L1, L2, L3) for the presence of voltage!
** If the acoustic signal is weak or the battery lamp is not as bright as it should be, replace the batteries.
3 ZOOM function
Fig. I: Press the ZOOM button to increase the sensitivity of the device (24 V AC to 1000 V AC). This enables voltage fields to be located at a significant distance by moving the device over the area to be tested.
Fig. J: If voltage is present, the detector tip lights up, and a signal sounds.
**
Please be aware that even if a visual signal is not displayed, the voltage may still be present. Differences in the design of the connection socket or the nature of the insulation (thickness and type) can affect functionality. Voltage cannot be detected behind panels and metal covers.
Information on maintenance and care
Clean all components with a damp cloth and do not use cleaning agents, scouring agents, and solvents. Remove the battery(ies) before storing it for longer periods. Store the device in a clean and dry place.

Technical data

Subject to technical alterations. 19W36

Indicator LED
Voltage range 24 V AC — 1000 VAC

Frequency 50 … 60 Hz
Overvoltage category| CAT III – 1000 V (non-condensing)
Pollution degree 2
Power supply| 2 x 1,5V LRO3 (AAA)
Operating conditions| 0°C … 50°C, Max. humidity 80% RH,
no condensation, max. altitude 2000 m
Storage conditions| -10°C … 60°C, Max. humidity 80% RH
Dimensions (W x H x D)| 21 x 158 x 25 mm
Weight| 48 g (incl. batteries)

EU directives and disposal (see Fig. K)
This device complies with all necessary standards for the free movement of goods within the EU. This product is an electric device and must be collected separately for disposal according to the European Directive on waste electrical and electronic equipment. Further safety and supplementary notices at: http://laserliner.com/info?an=AAB

ActiveFinder

SERVICE
Umarex GmbH & Co. KG
– Laserliner –
Möhnestraße 149, 59755 Arnsberg, Germany
Tel.: +49 2932 638-300,
Fax: +49 2932 638-333
info@laserliner.com
Umarex GmbH & Co. KG
Sonnenfeld 2
59757 Arnsberg, Germany
Tel.: +49 2932 638-300, Fax: -333
www.laserliner.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Laserliner User Manuals

Related Manuals