COTEK S-M – Platform AC-DC Rack Mount Power Systems Installation Guide

June 6, 2024
COTEK

S/M – Platform installation guide
AC / DC Rack Mount Power Systems

Legal Provisions
Copyrights 2017 COTEK Electronic IND. CO. All Rights Reserved. Any part of this document may not be reproduced in any form for any purpose without the prior written permission of COTEK Electronic IND. CO. For the conditions of the permission to use this manual for publication, contact COTEK Electronic IND. CO., LTD. In all related COTEK product activities, Neither COTEK Electronic IND. CO., LTD. nor its distributors or dealers be liable to anyone for indirect, incidental, or consequential damages under any circumstances. Specifications are subject to change without notice. Every attempt has been made to make this document complete, accurate, and up-to-date. COTEK Electronic IND. CO., LTD reserve the right to make changes without notice and shall not be responsible for any damages, including indirect, incidental or consequential damages, caused by reliance on the material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the content material. All trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand is not a registered trademark.

Introduction of COTEK DC power system

System overview

COTEK Switching Mode Rectifier (SMR) system provides uninterruptible and reliable DC power to wide variety of devices which require high quality DC source. With its high efficiency and compact size, COTEK RA-3048 rectifier module saves energy and space for system installers, which means more flexibility and less OPEX.
Multiple rectifiers can be configured by central control unit CE-R1 , which makes sure identical parameters setting and load sharing. Meanwhile, charging parameters monitoring and setting are completely considered in CE-R1, to make sure battery charging condition is optimized. In COTEK DC power system, protection mechanisms such as Input voltage protection and temperature protection are included. Hardware protection such as circuit breaker, SPD (Surge Protection Device- available with M system or above) and Low voltage Disconnect (LVDS) with battery can protect system further when necessary.
A complete COTEK DC power system is consisted of below elements in terms of function blocks:

How COTEK DC power system works

AC input distribution includes AC Switch (MNFB) and AC input terminals. All SMRs are in parallel and all DC outputs are connected to DC loads and batteries (Paralleled Battery modules) via DC distribution.
SMRs are charging Batteries when AC grid is present under the setting by CE-R1. When AC grid is not available, DC loads will be powered by batteries which avoid system downtime. LVDS meanwhile can reduce the risk of battery deep discharge when AC grid is lost longer than expected. All system status and parameters can be monitored by CE-R1, and system alarm is triggered by dry contact relays on back panel.

Pre-configured stock models

|
---|---
S-Platform
19″ 2RU Rack| M-Platform
19″ 4RU Rack
| S-Platform| M-Platform
---|---|---
COTEK Part Number| 01-C101-0001| 01-C101-0002
Output Power (N+1)| 6KW| 12KW
Maximum Output DC Current (N+1)| 125 A| 250 A
Total Height Controller Slots| 2U (3.51| 4U (7″)
1| 1
Rectifier Slots| 3| 5
Protected Load Outputs| Up to 4| Up to 10
Protected Battery Sets Surge Protection Device| Up to 2| Up to 2
No| Yes
LVDS Switch| Up to 1| Up to 2
Additional Distribution Panel Option| No| Yes
Distribution Dimensions
DC terminal type| Height: 2U (3.5″) Width: 19′ (rack) Depth: 10.12″| Height: 4U (7″)
Width: 19″ (rack)
Depth: 10.12″
1. TB Terminal 2. Euroblock terminal

  • N+1 means a spare module is used for redundant supply, not regular output supply. 6
S / M Platform output power capability guide

Below table indicates the future expansion capability of COTEK DC power system, M/S platform. If more output power is required, please contact COTEK distribution partners.
Below table does NOT consider N+1 situation and only shows full capacity output. However, a N+1 redundancy is always needed when any single SMR fails, in order to prevent system failure.

Platform| No. SMR| Present d| Future| IMaximum|
---|---|---|---|---|---
No. SMR| W
S-platform| 1| 3000| 2| 6000| 3| 9000
2| 6000| 1| 3000
3| 9000| 0| 0
M-platform| 1| 3000| 4| 12000| 5| 15000
2| 6000| 3| 9000
3| 9000| 2| 6000
4| 12000| 1| 3000
5| 15000| 0| 0

Configuration List

Below indicates the devices configuration included in each pre-configured stock systems, which can be ordered on a regular basis.

| | S-Platform| M-Platform
---|---|---|---
Photo| Component| Quantity
| RA-3048 (Rectifiers)| 3| 5
| CE-R1 (Central control unit)| 1| 1
| AC Input Breaker| 1| 1
| Battery Breaker| 2| 2
| DC Load Breakers| 4| 10
(100A x 2, 50Ax
6, 30A x 2)
| SPD| N/A| 1
| Load Breaker Alarm DIP Switch| 1| 1

Operation Procedure

Please follow below steps for initial installation and operation.

STEP 1:
Please check AC input no short condition before power ON , and check AC input whether 230VAC. If not, please check AC supply.
STEP 2:
Please check if battery wiring is proper, Red line is positive connect to terminal block (P BAR), Blue line is negative, please check all connect point will be screw tight. If Yes, please turn ON the battery switch.
STEP 3:
Please check PDU LOAD wiring is proper, check all connect point will be screw tight. If Yes, turn ON the PDU switch. Complete Set up procedure.
STEP 4:
Please turn ON AC switch (MNFB).
After power ON 5 to 10 sec. Please check CE-R1 LED green light is ON. And no alarm message. Please check CE-R1 display condition: normal. Please check all SMR LED green light is ON, and yellow light is NOT flashing.

Introduction of RA-3048 / CE-R1

RA-3048 Rectifiers
  • With 95% typical efficiency
  • Input voltage range: 100 – 275 VAC
  • 3000W DC output (constant power)
  • 1U in height; 4.25″ in width
  • Hot-swap / hot-plug functionality
  • Automatic active load sharing
Input RA-3048
Voltage Wide Input Range: 100-275 Vac, Max 3kW (100-184 Vac at de-rated

output power)
Current (maximum)| 16 ARMS
Frequency| 45-66 Hz
Power Factor| >0.99 at 50-100% load
Input Protection Efficiency| Fuse

95% (Load 40%-80%)
Surge Protection| IEEEE C 62.41 / IEC 61000-4-5 / IEC 61000-4-4
Output|
Voltage| 54 Vdc (adjustable range : 45-58 Vdc )
Static Regulation| ±1.0% (10-100% load)
Current (maximum)| 62.5 A (@ 48 Vdc)
Power (Max)| 3000W @ 220Vac; 1000W © 100Vac
Current sharing (10-100% load)
Protection| ±5% of maximum current from 10 to 100% load sharing from CE-R1
Overvoltage-only faulty unit shuts down; Overcurrent-can sustain short circuit at output terminals indefinitely; Over-temperature – gradual reduction of current limit if heat-sink temperature exceeds pre-set limit
Dynamic Regulation| ±5.0% for 10-90% or 90-10% load variation, output voltage regulation time < 2.5%. 1-/-1% within2ms of step change.
Output Noise Ripple| < 10mVrms 10kHz – 100MHz; < 100mV peak to peak 0-30MHz bandwidth
< 100 mV peak to peak, 30 MHZ bandwidth
Other Specifications|
Surge Protection| IEC 610004-4 / IEC 61000-4-51 IEEE C62.41
---|---
EMC
Inrush Current| Emission: EN 61000-6-3; EN 61000-3-2; EN 61000-3-3. Immunity: EN61000-6-1; EN 61000-6-2
<28.5 Arms peak at nominal mains voltage
Voltage Withstand Test| 3.0 kVac – input and output (4.25 kVDC primary- secondary); 1.5kVac – input earth (2.12kVDC primary-ground)
Safety Isolation| UL 60950-1, UL62368-1 3rd , IEC62368-13rd , EN62368-1 3rd
1.5 kVAC -input to earth, 500 VDC -output to earth
Environmental|
Acoustic noise, full load| < 55 dBA@ T ambient = 40°C
Operating temperature| Operating range -10°C — 70°C; derated power at 50°C — 70°C ; humidity 5-95% RH non-condensing
Storage temperature Cooling| -40 to +85°C ; humidity 0-99% RH non-condensing
Fan (front to back airflow, temperature and output current regulated speed)
Mechanical|
Dimension (W x H x D)mm| 144 x 41 x 328 mm
Weight| 2.1 kg (4.6 Ibs)

*For details, please refer to RA-3048 spec.

CE-R1 Central control unit
  • Easy setting and intuitive warning message display
  • Comprehensive rectifier system monitoring and setting in a single unit
  • Advanced battery-monitoring and temperature compensation

| CE-R1
---|---
Input Voltage| 18 — 70 VDC
Alarm Inputs Output Relays| 7
5
Computer Interface| RS232 or TCP/IP
Front Display| Graphic 144 x 32 dots
Temperature Sense Input Battery Current Monitor Input| 1 Ambient and 2 Battery temperature
2
Fuse Fail Monitor Input| 1
LVDS Control| 1
Dimensions (W x H x D)| 90 mm (3.54″) x 45 mm (1.77″) x 230 mm (9.05″)

*For details, please refer to CE-R1 UM.

Instruction to replace RA-3048 and CE-R1

RA-3048

RA-3048 rectifier is design for hot pluggable while AC grid is present. Please see below steps for proper rectifier replacement:

  1. Insert RA-3048 rectifier
    STEP 1: Make sure the handle is at “OPEN” position, and pull it out from the shelf.
    If you plug in RA-3048 into rack system when handle is at “OFF” position, the handle might be damaged.
    STEP 2: Insert the replacement rectifier module fully into the shelf () until it fits the slot tightly. Wait for few seconds until the LED on replacement rectifier shows solid GREEN. STEP 3: Turn the handle to “Lock” position
    STEP 4: CE-R1 will display “communication fail” due to one module is inserted. Please enter the menu tree and change rectifier number to match latest rectifier quantity.

CAUTION:

  1. The modules may be warm, but do not hand-carry them by their handles. Open the handles before inserting them into the power shelves (hot-pluggable). Please apply blind panels in unused module locations
  2. No address setting is needed for each SMR. When plug the SMR into the power shelf, CE-R1 will assign corresponding address. However, correct SMR quantity needs to be input in CE-R1 after remove/add rectifiers in order for CE-R1 to calculate correct parameters.
CE-R1

STEP 1: Use the side handle to remove CE-R1 from the shelf. RA-3048 rectifier modules are operating normally even without CE-R1.
STEP 2: Insert the replacement control unit fully into the shelf () until it fits the slot tightly. Wait for few seconds until the LED on replacement CE-R1 shows solid GREEN.
STEP 3: Please set desired parameters on replacement CE-R1 , or the settings will follow factory default value when inserting new control unit.
In case of any error message or warning LED indicators are on (ex. Flashing orange), please refer to user manual for trouble shooting, or contact COTEK local distributor for assistance.

No.33, Sec. 2, Renhe Rd., DaxiDist., Taoyuan City 33548, Taiwan
Phone+886-3-3891999 FAX+886-3-3802333
http://www.cotek.com.tw
2021.9._A0