DMP 714 Zone Expansion Module Installation Guide

June 6, 2024
DMP

DMP 714 Zone Expansion Module

GET STARTED

714 and 715 zone expander modules allow you to increase the number of reporting zones available on DMP panels. The modules connect to the panel Keypad Bus or LXBus and are set to an address that determines the reporting zone number. The 714 provides four 5 VDC Class B, Style A zones for use with burglary and nonpowered fire devices. The 715 provides four 12 VDC Class B zones for use with burglary, nonpowered, or powered fire devices.

What’s Included
  • One 714 Zone Expansion Module or One
  • 715 Zone Expansion Module
  • (714) Four 1K Ohm Resistors
  • (715) Four 3.3K Resistors
  • 12Wire Harness
  • Hardware Pack
Compatibility
  • XT30/XT50 Panels
  • XR150/XR550 Panels

INSTALLATION

Program the Panel

Program the zones on 714 or 715 zone expander modules with any of the panel’s burglary or fire zone types. You can also program zones as an Arming zone type when they are being used with key switches. For more information, refer to the appropriate panel programming guide.

Mount the Module

The 714/715 comes in a highimpact plastic housing that you can mount directly to a wall, backboard, or other flat surface. For easy installation, the housing base contains holes that allow you to mount the module on a singlegang switch box or ring. Mount the module outside the panel enclosure.

  1. Remove the housing fastener screws and separate the top housing from the base.

  2. Insert screws through the desired mounting holes on the housing base. Refer to Figure 1 for mounting hole locations.

  3. Tighten the screws into place.

  4. After wiring and addressing the module, attach the housing top to the mounted base with the housing fastener screws. Refer to Figure 2

Wire the Module

Connect the 714 to the LX-Bus
To wire the 714, join the red, yellow, green, and black wires to a 4wire harness and connect it to the LXBus.

Connect the 714 to the Keypad Bus

  1. Connect the red, yellow, green, and black wires to panel Terminals 7, 8, 9, and 10 respectively.
  2. Observe polarity and wire zones 14.
  3. Install the included 1K Ohm EOL resistors.

Table 1: 714 and 715 Modules Specifications

SPECIFICATIONS

| 714 MODULE|

715 MODULE

---|---|---
Normal Operating Range| 650-2100 Ohms| 1200-6000 Ohms
Zone Resistors| 1k Ohm EOL| 3.3k Ohm EOLc
Max Line Impedence| 100 Ohms| 100 Ohms
Zone Ground Fault| 1500 Ohms or less| 80 Ohms or less
Zone Supervision| All Zones| All Zones

Connect the 715 to the LX-Bus
To wire the 715, connect the red wire to panel Terminal 11 (Smoke power terminal). This allows Sensor Reset to drop power to the module and devices connected to its zones. Join the yellow, green, and black wires to a 4wire harness and connect it to the LXBus.

Connect the 715 to the Keypad Bus

  1. Connect the red wire to panel Terminal 11 (Smoke power terminal). This allows Sensor Reset to drop power to the module and devices connected to its zones. Alternately, connect red to a regulated, power limited power supply listed for Fire Protective Signaling through a Model 716 relay. Use the Sensor Reset Output programming to drop power to the 715 module.
  2. Connect the yellow, green, and black wires to panel Terminals 8, 9, and 10 respectively.
  3. Observe polarity and wire zones 14.
  4. Install the included 3.3K Ohm EOL resistors.

A 714 Module:
Connect Red to LX-Bus Wire or Panel Terminal 7

715 Module:
Connect Red to Panel Terminal 11 or a regulated, power limited power supply listed for Fire Protective Signaling through a Model 716 relay

B To Keypad Bus or LX-Bus

Set the Module Address

714 and 715 Zone Expansion Modules use two rotary switches (TENS and ONES) to set the module address. For keypad bus addresses, set the switches to match the device address. For LXBus addresses, set the switches to match the last two digits of the addresses. For example, for address 02 set the switches to TENS 0 and ONES 2 as shown in Figure 4. For more information, refer to Table 2 and Table 3.

Table 2:Lx-Bus Addresses and Corresponding Zone Numbers

SWITCH| XR150 SERIES| | XR550 SERIES|
---|---|---|---|---
TENS| ONES| LX500| LX500| LX600| LX700| LX800| LX900
0| 0| 500| 500| 600| 700| 800| 900
0| 1| 501| 501| 601| 701| 801| 901
0| 2| 502| 502| 602| 702| 802| 902
0| 3| 503| 503| 603| 703| 803| 903
0| 4| 504| 504| 604| 704| 804| 904
…| …| …| …| …| …| …| …
9| 5| 595| 595| 695| 795| 895| 995
9| 6| 596| 596| 696| 796| 896| 996
9| 7| 597| 597| 697| 797| 897| 997
9| 8| 598| 598| 698| 798| 898| 998
9| 9| 599| 599| 699| 799| 899| 999

Table 3:Keypad Bus Addresses and Corresponding Zone Numbers

KEYPAD BUS ADDRESS| SWITCH| ZONE NUMBERS|
---|---|---|---
TENS| ONES| XT30/XT50 AND XR150 SERIES| XR550 SERIES
1| 0| 1| 11 to 14| 11 to 14
2| 0| 2| 21 to 24| 21 to 24
3| 0| 3| 31 to 34| 31 to 34
4| 0| 4| 41 to 44| 41 to 44
5| 0| 5| 51 to 54| 51 to 54
6| 0| 6| 61 to 64| 61 to 64
7| 0| 7| 71 to 74| 71 to 74
8| 0| 8| 81 to 84| 81 to 84
9| 0| 9| N/A| 91 to 94
10| 1| 0| N/A| 101 to 104
11| 1| 1| N/A| 111 to 114
12| 1| 2| N/A| 121 to 124
13| 1| 3| N/A| 131 to 134
14| 1| 4| N/A| 141 to 144
15| 1| 5| N/A| 151 to 154
16| 1| 6| N/A| 161 to 164

ADDITIONAL INFORMATION

Wiring Specifications

DMP recommends using 18 or 22 AWG for all LXBus and Keypad Bus connections. The maximum wire distance between any module and the DMP Keypad Bus or LXBus circuit is 1,000 feet. To increase the wiring distance, install an auxiliary power supply, such as a DMP Model 50512. Maximum voltage drop between a panel or auxiliary power supply and any device is 2.0 VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit.

To maintain auxiliary power integrity when using 22gauge wire on Keypad Bus circuits, do not exceed 500 feet. When using 18gauge wire, do not exceed 1,000 feet. Maximum distance for any bus circuit is 2,500 feet regardless of wire gauge. Each 2,500 foot bus circuit supports a maximum of 40 LXBus devices.

For additional information refer to the following documents:

  • LXBus/Keypad Bus Wiring Application Note (LT2031)
  • 710 Bus Splitter/Repeater Module Installation Guide (LT0310)
Optional Accessories

You can replace the standard wiring harness with the optional 718T Plugin Screw Terminal. The enclosure base can also accommodate the 719T Terminal Boards for the 714 or the 720T Terminal Boards for the 715, both of which pass through panel LXBus wiring. The 719T includes 1k EOL resistors. The 720T includes 3.3k EOL resistors.

LED Operation

The LED on the zone expanders flashes each time the module responds to a poll from the panel. If there is a problem with the hardware, panel programming, or the green data wire between the panel and the zone expander module, the LED stops flashing and System Trouble appears in the keypad display.

COMPLIANCE INFORMATION

UL Commercial Burglary

To comply with ANSI/UL 365 PoliceConnected Burglary System or ANSI/UL 609 Local Burglary Alarm Systems, the module must be mounted in the supplied, UL listed enclosure with a tamper.

UL Commercial Fire

See the panel installation guide for details for selecting compatible 2wire smoke detectors. Any auxiliary power supply used must be regulated, power limited and listed for Fire Protective Signaling.

ULC Commercial Burglary (XR150/XR550 Series Panels)

Place the zone expander module in a listed enclosure and connect a DMP Model 307 Clipon Tamper Switch to the enclosure programmed as a 24hour zone.

The 714/715 zones can be installed in medium or high risk applications when two zones are used as shown in the Dual Zone Protection diagram in the XR150/XR550 Canadian Installation Guide. Otherwise, 714/715 zones can only be used in low risk applications.

ULC Residential Fire (XR150/XR550 Series Panels)

Refer to the appropriate panel compliance listing guide for the complete list of UL approved smoke detectors.

SPECIFICATIONS

Operating Voltage 12 VDC
714 Operating Current 7 mA + 1.6 mA per zone
714 Zone Voltage 5 VDC, max 2 mA
715 Operating Current 7 mA + 4 mA per active zone + 30 mA per smoke in alarm
  • 58 mA per zone shorted
    715 Zone Voltage| 2 VDC, max 58 mA
    Dimensions| 4.50 W x 2.75 H x 1.75 D in 11.43 W x 6.99 H x 4.45 D cm
    Zones| 4 Supervised Class B Style A Power Limited

CERTIFICATIONS

  • California State Fire Marshal (CSFM)
Underwriters Laboratory (UL) Listed

ANSI/UL 365                Police Station Connect Burglar Alarm Systems
ANSI/UL 609                Local Burglar Alarm Units & Systems
ANSI/UL 864                Fire Protective Signaling Systems
ANSI/UL 985                Household Fire Warning System Units
ANSI/UL 1023              Household Burglar Alarm System Units
ANSI/UL 1076              Proprietary Burglar Alarm Units & Systems
ANSI/UL 1610              Central Station Burglar Alarm Units
ANSI/UL 1635              Digital Alarm Communication System Units
ULC Subject-C1023       Household Burglar
ULC/ORD-C1076         Proprietary Burglar
ULC S304                      Central Station Burglar
ULC S545                       Household Fire

Designed, engineered, and manufactured in Springfield, MO using U.S. and global components.
LT-0161 1.06 21344 © 2021

INTRUSION · FIRE · ACCESS · NETWORKS
2500 North Partnership Boulevard Springfield, Missouri 65803-8877 800.641.4282 |DMP.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals