APC SURT8000XLI Uninterruptible Power Supply Tower Rack-Mount 6U Installation Guide
- June 6, 2024
- APC
Table of Contents
Installation and Operation
Smart-UPS™
RT
Uninterruptible Power Supply
SURT8000XLI
SURT10000XLI
220/230/240 Vac
Tower/Rack-Mount 6U
For Professional Business Applications – Not For Consumer Use
Smart-UPS™
RT
Uninterruptible Power Supply
SORT 8000/10000 VA
200-240 Vac
Tower/Rack-Mount 6U
Introduction
The APC ™ by Schneider Electric Smart-UPS ™ RT is a high-performance,
uninterruptible power supply (UPS). The UPS protects electronic equipment from
utility power blackouts, brownouts, sags, and surges and small utility
fluctuations and large disturbances. The UPS also provides battery backup
power for connected equipment until utility power returns to safe levels or
the batteries are fully discharged.
This user manual is available on the enclosed Documentation CD and on the APC
by Schneider Electric website, www.apc.com.
**INSTALLATION
**
Read the safety information sheet before installation.
Unpacking
Inspect the UPS upon receipt. Notify the carrier and dealer if there is
damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
- UPS (with batteries disconnected)
- Two front bezels
- Literature kit containing:
- XLT/XLTW models only: Software CD Smart-UPS User Manuals CD
- XLI model only: Six output power cords Serial cable
- Product documentation, safety and warranty information Network Management Card documentation
Removing the Batteries
The unit is heavy. To lighten the unit, remove the batteries. Refer to the
unpacking instructions on the carton in which the unit is shipped.
Specifications
TEMPERATURE
OPERATING
STORAGE| 32° to 104° F (0° to 40° C)
5° to 113° F (-15° to 45° C) charge UPS battery every six months| This unit is
intended for indoor use only. Select a location sturdy enough to handle the
weight.
Do not operate the UPS where there is excessive dust or the temperature and
humidity are outside the specified limits.
Ensure the air vents on the front and rear of the UPS are not
blocked.
---|---|---
MAXIMUM
ELEVATION
OPERATING
STORAGE| 10,000 ft (3,000 m)
50,000 ft (15,000 m)
HUMIDITY| 0% to 95% relative humidity, non-condensing
WEIGHT
UPS
UPS WITH
PACKAGING| 244 lbs (111 kg)
284 lbs (129 kg)|
Hardwiring
Wiring must be performed by a qualified electrician.
- Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring.
- Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.
- Remove the access panel (see B).
- Remove circular knockouts.
- Run wires through the access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. (See tables and graphics.)
- Use appropriate strain relief on the hardwired input and output power cables.
XLT, XLJ, AND XLTW M ODELS
Input Connection| Output Connection (optional)
Wire to L1, L2, and.| Wire to L1A, L2A, and.
System| Wiring| Voltage| Current Full Load (Nominal)|
External Input Circuit Breaker (typical)| Wire Size (typical)
---|---|---|---|---|---
SURT8000XLJ, SURT8000XLT, SURT8000XLTW| Input & Output| 200/208/220/240 V| 40
A| 50 A / 2-pole
for Input Wiring only
| 10mm2 *
8 AWG
SURT10000XLJ, SURT10000XLT, SURT10000XLTW| Input & Output| 200/208/220/240 V| XLJ-50 A XLT-48 A XLTW-48 A| 60 A or 63 A / 2-pole for Input Wiring only| 16mm2 *
6 AWG
XLI M ODELS
Input Connections| Output Connection (optional)
Single-Phase: Wire to L1, N, and .
Three-Phase: Wire to L1, L2, L3, N, and .
| Wire to L1A, N1, and .
System| Wiring| Number of Phases| Voltage| Current Full
Load (Nominal)| External Input Circuit Breaker (typical)| Wire Size
(typical)
---|---|---|---|---|---|---
SURT8000XLI| Input| 1| 220/230/240 V| 40 A| 50 A / 2-pole| 10mm2 *
Input| 3+
Neutral
| 380/400/415 V| 15 A / phase when online
40 A on L1 in bypass
| 50 A / 4-pole| 10mm2
Output| 1| 220/230/240 V| 40 A| (not required)| 10mm2
SURT10000XLI| Input| 1| 220/230/240 V| 50 A| 63 A / 2-pole| 16mm2 *
Input| 3+
Neutral
| 380/400/415 V| 18 A / phase when online
50 A on L1 in bypass
| 63 A / 4-pole| 16mm2
Output| 1| 220/230/240 V| 50 A| (not required)| 16mm2
- Recommended wire sizes are typical. Actual wire size must comply with required ampacity and local and national electrical codes.
7. XLI model only: For three-phase input, set the Input Phase Selector switch (see C) to ‘3’. For single-phase input, leave the switch in the default position of ‘1’.
XLT/XLJ/XLTW MODELS
8. Switch the circuit breakers ON.
9. Check line voltages.
10. Replace the access panel.
CONNECTING POWER AND EQUIPMENT TO THE UPS
-
Hardwire the UPS (see Hardwiring).
-
Connect the equipment to the UPS (cables not included for XLT/XLJ/XLTW models).
-
Turn on all connected equipment. To use the UPS as a master on/off switch, be sure that all connected equipment is switched ON.
-
Press the button on the front panel to power up the UPS.
• The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during this initial charge period. -
Configure the Network Management Card (optional).
OPTIONS
Refer to the APC by Schneider Electric website,
www.apc.com for available accessories.
- External Battery Pack SURT192XLBP
- Rail Kit SURTRK2
- Isolation Transformer
- Service Bypass Panel
CIRCUIT BREAKERS
Input Circuit Breaker 8000/10000 VA XLI/XLJ/XLT/XLTW
__
| The UPS is protected from extreme overloads when in an ON position. The
breaker must be on for the UPS to operate.
---|---
Output Circuit Breaker
8000/10000 VA
XLJ/XLT/XLTW|
---|---
Output Circuit Breaker
8000/10000 VA XLI|
B ASIC C ONNECTORS
Serial Port| Power management software and interface kits can be used
with the UPS.
Use only APC by Schneider Electric approved or supplied interface.
Ethernet Port| Connect the UPS to the network.
(Located on the Network Management Card.)
EPO Terminal| The optional Emergency Power Off (EPO) feature allows
connected loads to be immediately de-energized from a remote location, without
switching to battery operation (see EPO Option).
TVSS Screw| The UPS features a transient voltage surge suppression
(TVSS) screw for connecting the ground lead on surge suppression devices such
as telephone and network line protectors.
When connecting grounding cable, disconnect the unit from the utility power
outlet.
External Battery Pack Connectors| Optional external battery packs
provide extended runtime during power outages. These units support up to 10
external battery packs. Refer to the APC by Schneider Electric website,
www.apc.com for the information on the external battery
pack, SURT192XLBP.
OPERATION
Indicator | Description |
---|
Online
__
| The UPS is drawing utility power and performing double conversion to supply
power to connected equipment (see Troubleshooting).
On Battery
__
| The UPS is supplying battery power to the connected equipment.
Bypass
__
__
__
__
| The UPS is in bypass mode, sending utility power directly to connected
equipment. Bypass mode operation is the result of an internal UPS fault, an
overload condition or a user-initiated command either through an accessory or
the manual bypass switch. Battery operation is not available while the UPS is
in bypass mode (see Troubleshooting).
Fault
__
| The UPS detects an internal fault (see Troubleshooting).
Overload
__
| The connected loads are drawing more power than the UPS power rating (see
Troubleshooting).
Replace Battery
| The battery is disconnected or must be replaced (see Troubleshooting).
Feature| Function
---|---
Power On
__
| Press this button to turn on the UPS. Read on for additional capabilities.
Power Off
__
| Press this button to turn off the UPS.
Feature| Function
---|---
Normal /Bypass
__
| Manually switch connected equipment to bypass mode, so that utility power is
sent directly to connected equipment. Battery operation is not available while
the UPS is in bypass mode. (See Troubleshooting.)
Cold Start| This is not a normal condition. Supply immediate battery power to
the UPS and connected equipment (see Troubleshooting). Press and hold the
button to power up the UPS and connected equipment. The UPS will emit two
beeps. During the second beep, release the button.
Self-Test| Automatic: The UPS performs a self-test automatically when
turned on, and every two weeks thereafter (by default). During the self-test,
the UPS briefly operates the connected equipment on the battery. Manual:
Press and hold the button for a few seconds to initiate the self-test.
Diagnostic Utility Voltage
__
| The UPS has a diagnostic feature that displays the utility voltage. Plug the
UPS into the normal utility power.
The UPS starts a self-test as part of this procedure. The self-test does
not affect the voltage display. Press and hold the button to view the
utility voltage bar graph display. After a few seconds, the five-LED, Battery
Charge display on the right of the front panel shows the utility input
voltage. Refer to the figure at left for the voltage reading (values are not
listed on the UPS). The display indicates the voltage is between the displayed
value on the list and the next higher value.
On Battery Operation
The UPS switches to battery operation automatically if the utility power
fails. While running on battery, an alarm beeps four times every 30 seconds.
Press the button to silence this alarm. If the utility power does not return,
the UPS continues to supply power to the connected equipment until the battery
is fully discharged.
When two minutes of runtime remain the UPS emits a continuous beep. If
PowerChute or the Network Management Card is not being used, files must be
manually saved and the computer must be properly shut down before the UPS
fully discharges the battery.
The UPS battery life differs based on usage and environment.
Refer to the APC by Schneider Electric website,
www.apc.com for on battery runtimes.
USER CONFIGURABLE ITEMS
N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE , N ETWORK M ANAGEMENT CARD , OPTIONAL S MART S LOT ACCESSORY CARDS, OR T ERMINAL M ODE .
F UNCTION| F ACTORY D EFAULT| USER-SELECTABLE
C HOICES| D ESCRIPTION
Automatic Self-Test| Every 14 days (336 hours)| Every 7 days (168 hours),
Every 14 days (336 hours), On Startup Only, No Self-Test| Set the interval at
which the UPS will execute a self-test.
UPS ID| UPS_IDEN| Up to eight characters to define the UPS| Uniquely identify
the UPS, (i.e. server name or location) for network management purposes.
Date of Last Battery Replacement| Manufacture Date| mm/dd/yy| Reset this date
when you replace the battery modules.
Minimum Capacity Before Return from Shutdown| 0 percent| 0, 15, 25, 35, 50,
60, 75, 90 percent| Specify the percentage to which batteries will be charged
following a low-battery shutdown before powering connected equipment.
Alarm Delay After Line Failure| 5 second delay| 5-second delay, 30-second
delay, At Low Battery, Never| Mute ongoing alarms or disable all alarms
permanently.
Shutdown Delay| 20 seconds| 0, 20, 60, 120, 240, 480, 720, 960 seconds| Set
the interval between the time when the UPS receives a shutdown command and the
actual shutdown.
Duration of Low Battery Warning.| 2 minutes PowerChute software provides
automatic, unattended shutdown when approximately two minutes of battery
runtime remains.| 2, 5, 7, 10, 12, 15, 18, 20 minutes.| The low battery
warning beeps become continuous when two minutes of runtime remains. Change
the warning interval to a higher setting if the operating system requires a
longer interval for the shutdown.
Synchronized Turn-on elay| 0 seconds| 0, 20, 60, 120, 240, 480, 720, 960
seconds| Specify the time the UPS will wait after the return of utility power
before turn on (to avoid branch circuit overloads).
N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER
C HUTE SOFTWARE , N ETWORK M ANAGEMENT CARD ,
OPTIONAL S MART S LOT ACCESSORY CARDS OR T ERMINAL
M ODE .
F UNCTION| F ACTORY D EFAULT| U SER
S ELECTABLE C HOICES| D ESCRIPTION
High Bypass Point| +10% of output voltage setting| +5%, +10%, +15%, +20%| The
maximum voltage that the UPS will pass to connected equipment during internal
bypass operation.
Low Bypass Point| -30% of output voltage setting| -15%, -20%, -25%, -30%|
Minimum voltage that the UPS will pass to connected equipment during internal
bypass operation.
Output Voltage| XLJ models: 200 Vac
XLT models: 208 Vac *** XLTW models: 220 Vac XLI models: 230 Vac| XLJ
models: 200 Vac XLT models: 200, 208, 220, 230, 240 Vac XLTW models: 200, 208,
230, 40 VAC XLI models: 200, 208, 220, 230, 240 Vac Use the voltage setting
applicable to your region.| Allows the user to select the UPS output voltage
while on-line.
Output Frequency| Automatic (50 ± 3 Hz or 60 ± 3 Hz)| 50 ± 3 Hz 50 ± 0.1 Hz 60
± 3 Hz
60 ± 0.1 Hz
| Sets the allowable UPS output frequency. Whenever possible, the output
frequency tracks the input frequency.
Number of Battery Packs| 1| Number of Connected Batteries (four battery
modules per pack)| Defines the number of connected battery packs for proper
runtime prediction.
EPO (Emergency Power Off) Option
The output power can be disabled in an emergency by closing a switch connected
to the EPO.
Adhere to national and local electrical codes when wiring.
The switch should be connected in a normally open switch contact. External
voltage is not required; the switch is driven by 12V internal supply. In
closed condition, 2mA of current are drawn.
The EPO switch is internally powered by the UPS for use with non-powered
switch circuit breakers.
The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a
SELV circuit (IEC standard).
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do
not connect any circuit to the EPO terminal block unless it can be confirmed
that the circuit is Class 2 or SELV.
If the circuit standard cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the UPS to the EPO switch:
- CL2: Class 2 cable for general use
- CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
- CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
- CLEX: Limited use cable for use in dwellings and for use in raceways.
- For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
- For installation in other countries: Use standard low voltage cable in accordance with local regulations.
Terminal Mode to Configure UPS Parameters
Terminal Mode is a menu-driven interface that enables enhanced configuration
of the UPS.
Connect the serial cable to the serial port on the back of the UPS.
-
Open a terminal program. Example: HyperTerminal
• From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal. -
Double-click on the HyperTerminal icon.
• Follow the prompts to choose a name and select an icon. Disregard the message, “…must install a modem,” if it is displayed. Click OK.
• Select the COM port that is connected to your UPS. The port settings are:
√ bits per second – 2400
√data – bits 8
√parity – none
√stop bit – 1
√flow control – none
• Press ENTER -
Example for setting the number of external battery packs (SURT192XLBP):
Once the blank terminal window is open, follow these steps to enter the number of battery packs:
• Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User
Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears on the screen prior to typing the next character.
Network Management Card defaults:
• User Name: APC
• Password: APC
• Press 1 and ENTER to select Device Manager.
• Select the model by entering the corresponding number, then press ENTER.
• Press 3 and ENTER to select Configuration.
• Press 1 and ENTER to select Battery.
• Press 2 and ENTER to change the Battery Settings.
• Type in the number of external battery packs (four battery modules per pack), then press ENTER. (Number of packs: 1= internal battery module, 2 = 1 SURT192XLBP, 3 = 2 SURT192XLBP, etc.)
• Press 3 and ENTER to accept the changes.
• Press ESC multiple times (5) to return to the main menu.
• Press 4 and ENTER to log out.
REPLACE BATTERY MODULES
Replace the Battery Module(s)
This UPS has easy to replace, hot-swappable battery modules. Replacement is a
safe procedure, isolated from electrical hazards. You may leave the UPS and
connected equipment on during the procedure. See your dealer or contact APC by
Schneider Electric website, www.apc.com for information
on replacement battery modules.
The battery replacement procedure must include replacing all battery modules
in the UPS and connected external battery pack (s).
Upon battery disconnection, equipment is not protected from power
outages.
Use caution when handling heavy battery modules.
Refer to Installing and Connecting the Batteries and Attaching the Front Bezel
for battery replacement procedure; reverse instructions for battery removal.
| Be sure to deliver the spent battery to a recycling facility or ship it to
APC by Schneider Electric in the replacement battery packing material.
---|---
TROUBLESHOOTING
Use the table below to solve minor installation and operation problems. Refer to the APC by Schneider Electric website, www.apc.com for assistance with complex UPS problems.
P ROBLEM AND P OSSIBLE C AUSE | S OLUTION |
---|
UPS WILL NOT TURN ON
Batteries are not connected properly. button not pushed.
UPS not connected to the utility power supply. Very low or no utility
voltage.| Check that the battery connectors are fully engaged.
Press the button once to power the UPS and the connected equipment.
Check that the power cable from the UPS to the utility power supply is
securely connected at both ends.
Check the utility power supply to ensure proper voltage at the receptacle.
UPS WILL NOT TURN OFF
button not pushed. Internal UPS fault.| Press the button once to turn the UPS
off.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
UPS BEEPS OCCASIONALLY
Normal UPS operation when running on battery.| None. The UPS is protecting the
connected equipment.
UPS DOES NOT PROVIDE EXPECTED BACKUP TIME
The UPS battery module(s) are weak due to a recent outage or are near the end
of service life.| Charge the battery module(s). Modules require recharging
after extended outages and wear faster when put into service often or when
operated at elevated temperatures. If the battery module(s) are near the end
of service life, consider replacing, even if the Replace Battery LED is not
illuminated.
FRONT PANEL LED S FLASH SEQUENTIALLY
The UPS has been shut down remotely through software or an optional accessory
card.| None. The UPS will restart automatically when utility power returns.
ALL LED S ARE OFF AND THE UPS IS CONNECTED TO UTILITY
POWER
The UPS is shut down and the battery is discharged from an extended outage.|
None. The UPS will return to normal operation when the power is restored and
the battery has a sufficient charge.
BYPASS AND OVERLOAD LED S ILLUMINATE , UPS EMITS A
SUSTAINED ALARM TONE
The UPS is overloaded.| The connected equipment exceeds the specified “maximum
load” as defined in Specifications on the APC by Schneider Electric web site,
www.apc.com.
The alarm remains on until the overload is removed. Disconnect nonessential
equipment from the UPS to eliminate the overload condition.
P ROBLEM AND P OSSIBLE C AUSE| S OLUTION
---|---
BYPASS LED ILLUMINATES
The bypass switch has been turned on manually or through an accessory.| If
bypass is the chosen mode of operation, ignore the illuminated LED.
If bypass is not the chosen mode of operation move the bypass switch on the
back of the UPS, to the normal position.
FAULT AND OVERLOAD LED S ILLUMINATE ; UPS EMITS A SUSTAINED
ALARM TONE
The UPS has ceased sending power to connected equipment.| The connected
equipment exceeds the specified “maximum load” as defined in Specifications on
the APC by Schneider Electric web site, www.apc.com.
Disconnect nonessential equipment from the UPS to eliminate the overload
condition.
Press the OFF button, then the ON button to restore power to connected
equipment.
FAULT LED ILLUMINATES
Internal UPS fault.| Do not attempt to use the UPS. Turn the UPS off and have
it serviced immediately.
REPLACE BATTERY LED ILLUMINATES
Replace Battery LED flashes and a short beep is emitted every two seconds to
indicate the battery is disconnected.| Check that the battery connectors are
fully engaged.
Weak battery.| Allow the battery to recharge for 24 hours. Then, perform a
self-test. If the problem persists after recharging, replace the battery.
Failure of a battery self-test.| The UPS emits short beeps for one minute and
the Replace Battery LED illuminates. The UPS repeats the alarm every five
hours. Perform the self-test procedure after the battery has charged for 24
hours to confirm the Replace Battery condition. The alarm stops and the LED
clears if the battery passes the self-test.
UPS OPERATES ON BATTERY ALTHOUGH LINE VOLTAGE EXISTS
Very high, low, or distorted line voltage. (Inexpensive fuel-powered
generators can distort the voltage.)| Move the UPS to a different line
circuit. Test the input voltage with the utility voltage display.
DIAGNOSTIC UTILITY VOLTAGE
All five LEDs are illuminated.| The line voltage is extremely high and should
be checked by an electrician.
There is no LED illumination.| If the UPS is plugged into a properly
functioning utility power outlet, the line voltage is extremely low.
ONLINE LED
There is no LED illumination.| The UPS is running on battery, or it is not
turned on.
The LED is blinking.| The UPS is running an internal self-test.
TRANSPORT
- Shut down and disconnect all connected equipment.
- Disconnect the unit from utility power.
- Disconnect all internal and external batteries (if applicable).
- Follow the shipping instructions outlined in the Service section of this manual.
SERVICE
If the unit requires service, do not return it to the dealer. Follow these steps:
-
Review the Troubleshooting section of the manual to eliminate common problems.
-
If the problem persists, contact APC by Schneider Electric Customer Support through the APC by Schneider Electric website, www.apc.com.
a. Note the model number and serial number and date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
b. Call Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric website, www.apc.com for country- specific instructions. -
Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.
a. Note: When shipping within the United States, or to the United States always DISCONNECT ONE UPS BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The internal batteries may remain in the UPS.
b. Batteries may remain connected in the XBP during shipment. Not all units utilize XLBPs. -
Write the RMA# provided by Customer Support on the outside of the package.
-
Return the unit by the insured, prepaid carrier to the address provided by Customer Support.
LIMITED FACTORY WARRANTY
Schneider Electric IT Corporation (SEIT) warrants its products to be free from
defects in materials and workmanship for a period of two (2) years from the
date of purchase. The SEIT obligation under this warranty is limited to
repairing or replacing, at its own sole option, any such defective products.
Repair or replacement of a defective product or parts thereof does not extend
the original warranty period.
This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase. Products may be registered
online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination
disclose that the alleged defect in the product does not exist or was caused
by an end-user or any third person misuse, negligence, improper installation,
testing, operation or use of the product contrary to SEIT recommendations or
specifications. Further, SEIT shall not be liable for defects resulting from:
- unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on-site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO THE ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUTES, CLAIMS BY THIRD PARTIES, OR OTHERWISE. NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CAN NOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claim issues may access the SEIT worldwide customer support network through the APC by Schneider Electric website: www.apc.com. Select your country from the country selection drop-down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.
APC by Schneider Electric Worldwide Customer Support
Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways:
- Visit the APC by Schneider Electric website, www.apc.com to access documents in the APC Knowledge Base and to submit customer support requests.
- www.apc.com (Corporate Headquarters) Connect to localized APC by Schneider Electric website for specific countries, each of which provides customer support information.
- ww.apc.com/support/ Global support searching APC Knowledge Base and using e-support.
- Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
- Local, country specific centers: go to www.apc.com/support/contact for contact information.
- For information on how to obtain local customer support, contact the APC by Schneider Electric representative or other distributors from whom you purchased your APC by Schneider Electric product. © 2021 APC by Schneider Electric. Smart-UPS and PowerChute are owned by
- Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.
Reference:APC SURT8000XLI Uninterruptible Power Supply Tower Rack-Mount 6U Installation Guide- device.report
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>