GENERAC 7179 60 Hz Air-Cooled Generators Installation Guide
- June 6, 2024
- Generac
Table of Contents
7179 60 Hz Air-Cooled Generators
®
Installation Guidelines
60 Hz Air-Cooled Generators
15kW EcoGenTM
WARNING
Loss of life. This product is not intended to
be used in a critical life support application.
Failure to adhere to this warning could result
in death or serious injury.
(000209b)
Register your Generac product at: WWW.GENERAC.COM 1-888-GENERAC
(888-436-3722)
Para español, visita: http://www.generac.com/service-support/product-support-
lookup Pour le français, visiter : http://www.generac.com/service-support
/product-support-lookup
SAVE THIS MANUAL FOR FUTURE REFERENCE
Use this page to record important information about this generator.
Model: Serial: Production Date: Volts: LPV Amps: NG Amps: Hz:
Record the information found on the unit data label on this page. For the
location of the unit data label, see owner’s manual. The unit has a label
plate affixed to the inside partition, to the left of the control panel
console.
Always supply the complete model and serial numbers of the unit when
contacting an Independent Authorized Service Dealer (IASD) about parts and
service.
Operation and Maintenance: Correct maintenance and care of the generator
ensures a minimum number of problems, and keeps operating expenses at a
minimum. It is the operator’s responsibility to perform all safety checks, to
verify all maintenance for safe operation is performed promptly, and to have
the equipment inspected periodically by an IASD. Normal maintenance, service,
and replacement of parts are the responsibility of the owner/operator and are
not considered defects in materials or workmanship within the terms of the
warranty. Individual operating habits and usage may contribute to the need for
additional maintenance or service.
Phase: Controller P/N:
When the generator requires servicing or repairs, Generac recommends contacting an IASD for assistance. Authorized service technicians are factory- trained and are capable of handling all service needs. To locate the nearest IASD, please visit the dealer locator at:
www.generac.com/Service/DealerLocator/.
STA MAC ID:
SSID:
WARNING
CANCER AND REPRODUCTIVE HARM www.P65Warnings.ca.gov.
(000393a)
ii
Installation Guidelines For 60 Hz EcoGenTM Generators
Table of Contents
Section 1: Safety Rules & General Information
Introduction …………………………………………………………1 Read This Manual Thoroughly ………………………………1
Safety Rules ………………………………………………………..1 How to Obtain Service ………………………………………….2
General Hazards …………………………………………………..2 Exhaust Hazards ………………………………………………….3
Electrical Hazards ………………………………………………..3 Fire Hazards ………………………………………………………..3
Explosion Hazards ……………………………………………….4 Battery Hazards ……………………………………………………4
General Rules ………………………………………………………5
Before You Begin ………………………………………………..5 NEC Requirements ………………………………………………5
Standards Index ………………………………………………….6
Section 2: Unpacking and Inspection
General ………………………………………………………………..7 Required Tools …………………………………………………….7
Unpacking ……………………………………………………………7
Opening the Lid …………………………………………………..8 Enclosure Panel Removal
…………………………………….8
Remove Front Access Panel …………………………………8 Intake Side Panel Removal
…………………………………..9 Customer Connections and Loose Parts ……………….9 Rear
Connections ………………………………………………..9 Generator Main Line Circuit Breaker
……………………10 Parts Shipped Loose ………………………………………….10 Auxiliary Shutdown Switch
…………………………………11
Water Ingress Avoidance ……………………………………17 Proximity to Utilities
…………………………………………..17
Verify Wi-Fi Range …………………………………………….17 Transportation Recommendations
……………………..17 Suitable Mounting Surface ………………………………….17 Placement on Roofs,
Platforms, and Other Supporting Structures ………………………………………..17
Section 4: Generator Placement
Generator Placement ………………………………………….19 Fascia Installation
………………………………………………19
Section 5: Fuel Conversion / Gas Connections
Fuel Requirements and Recommendations …………21 BTU Content
……………………………………………………..21 Fuel Pressure ……………………………………………………21
Fuel Conversion …………………………………………………21 Fuel Consumption ……………………………………………..22
Fuel Line Sizing ………………………………………………….22
Natural Gas Pipe Sizing ……………………………………..23 LP Gas Pipe Sizing
……………………………………………23 Installing and Connecting Fuel Lines ………………….24 Fuel
Shutoff Valve ……………………………………………..24 Flexible Fuel Line ………………………………………………24
Sediment Trap …………………………………………………..24 Checking Fuel Line Connections
………………………..25 Checking Fuel Pressure ……………………………………..25 Performing Fuel System
Leak Test ………………………25 Natural Gas Installation (Typical) ………………………..26 LP Gas
(Vapor) Installation (Typical) …………………..27
Section 3: Site Selection and Preparation
Site Selection …………………………………………………….13 Carbon Monoxide ……………………………………………….13
Carbon Monoxide Detectors ………………………………..13 Potential CO Entry Points
……………………………………14 Protect the Structure ………………………………………….14
Fire Prevention …………………………………………………..15 Distance Requirements
………………………………………15 Fire Codes, Standards, and Guidelines …………………16 Generator
Maintenance ………………………………………16
Fresh Air for Ventilation and Cooling ………………….17
Section 6: Electrical Connections
Generator Connections ………………………………………29 Control Wiring ……………………………………………………30
Main AC Wiring ………………………………………………….31 Service Entrance Decals
…………………………………….31 Common Alarm Relay (Option) ……………………………31 Battery
Requirements …………………………………………32 Battery Installation ……………………………………………..32
Connecting Battery …………………………………………….32 Battery Disposal …………………………………………………32
Installation Guidelines For 60 Hz EcoGenTM Generators
iii
Section 7: Control Panel Startup/Testing
Control Panel Interface ……………………………………… 33 Using the AUTO/MANUAL/OFF Buttons
…………….. 33
Generator Setup ……………………………………………….. 33 Activation ………………………………………………………… 33
Cold Smart Start ………………………………………………. 35 Setting The Exercise Timer
………………………………… 35
Before Initial Startup …………………………………………. 35 Install Wizard
…………………………………………………… 35 Interconnect System Self Test Feature ………………… 35
Before starting, complete the following: ……………….. 36
Check Manual Transfer Switch Operation ………….. 39 Electrical Checks
………………………………………………. 39 Generator Tests Under Load ……………………………… 40 Checking
Automatic Operation ………………………….. 41 Installation Summary ………………………………………… 41
Shutting Generator Down While Under Load or During a Utility Outage
………………………………….. 41
Section 8: Troubleshooting
Generator Troubleshooting ……………………………….. 43
Section 9: Quick Reference Guide
System Diagnosis ……………………………………………… 45
Section 10: Accessories
Section 11: Diagrams
Installation Drawing (10000037315 rev A–1 of 2) … 49 Installation Drawing
(10000037315 rev B–2 of 2) … 50 Off-Grid Mode Application Schematic ………………… 51
Oil Make Up System Schematic …………………………. 52
iv
Installation Guidelines For 60 Hz EcoGenTM Generators
Safety Rules & General Information
Section 1: Safety Rules & General Information
Introduction
Thank you for purchasing this compact, high performance, air-cooled, engine-
driven generator. In off-grid applications as part of an alternative energy
system, the generator starts when the inverter or battery charger detects the
normal power source voltage has dropped below a preset level. The generator
powers the inverter and, once battery voltage rises to an acceptable level,
the generator shuts down. Another off-grid application may be for use in
remote locations where the generator powers a water pump for a village,
campground, or livestock.
This unit is factory installed in an all-weather, metal enclosure intended
exclusively for outdoor installation. This generator will operate using either
vapor withdrawn liquid propane (LP) or natural gas (NG).
NOTE: When sized correctly, this generator is suitable for supplying typical
residential loads such as induction motors (sump pumps, refrigerators, air
conditioners, furnaces, etc.), electronic components (computer, monitor, TV,
etc.), lighting loads, and microwaves. This unit is also equipped with a Wi-
Fi® module, which enables the generator owner to monitor generator status from
anywhere they have Internet access.
NOTE: Wi-Fi® is a registered trademark of Wi-Fi Alliance®.
The information in this manual is accurate based on products produced at the
time of publication. The manufacturer reserves the right to make technical
updates, corrections, and product revisions at any time without notice.
Read This Manual Thoroughly
SAVE THESE INSTRUCTIONS for future reference. This manual contains important
instructions that must be followed during placement, operation, and
maintenance of the unit and its components. Always supply this manual to any
individual that will use this unit.
Safety Rules
The manufacturer cannot anticipate every possible circumstance that might
involve a hazard. The alerts in this manual, and on tags and decals affixed to
the unit, are not all inclusive. If using a procedure, work method, or
operating technique that the manufacturer does not specifically recommend,
verify that it is safe for others and does not render the equipment unsafe.
Throughout this publication, and on tags and decals affixed to the unit,
DANGER, WARNING, CAUTION, and NOTE blocks are used to alert personnel to
special instructions about a particular operation that may be hazardous if
performed incorrectly or carelessly. Observe them carefully. Alert definitions
are as follows:
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
(000001)
WARNING
Indicates a hazardous situation which, if not avoided, could result in death
or serious injury.
(000002)
WARNING
Consult Manual. Read and understand manual completely before using product.
Failure to completely understand manual and product could result in death or
serious injury.(000100a)
If any section of this manual is not understood, contact the nearest
Independent Authorized Service Dealer (IASD) or Generac Customer Service at
1-888-436-3722 (1-888-GENERAC), or
visit www.generac.com for starting, operating, and servicing procedures. The
owner is responsible for correct maintenance and safe use of the unit.
This manual must be used in conjunction with all other supporting product
documentation supplied with the product.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor
or moderate injury.
(000003)
NOTE: Notes contain additional information important to a procedure and will
be found within the regular text of this manual.
These safety alerts cannot eliminate the hazards that they indicate. Common
sense and strict compliance with the special instructions while performing the
action or service are essential to preventing accidents.
Installation Guidelines For 60 Hz EcoGenTM Generators
1
Safety Rules & General Information
How to Obtain Service
When the unit requires servicing or repairs, contact Generac Customer Service
at 1-888-GENERAC (1-888-4363722) or visit www.generac.com for assistance. When
contacting Generac Customer Service about parts and service, always supply the
complete model and serial number of the unit as given on its data decal
located on the unit. Record the model and serial numbers in the spaces
provided on the front cover of this manual.
General Hazards
DANGER
Loss of life. Property damage. Installation must always
comply with applicable codes, standards, laws and
regulations. Failure to do so will result in death
or serious injury.
(000190)
DANGER
Automatic start-up. Disconnect utility power and render unit inoperable before
working on unit. Failure to do so will result in death or serious injury.
(000191)
WARNING
Electrocution. Potentially lethal voltages are generated by this equipment.
Render the equipment safe before attempting repairs or maintenance. Failure to
do so could result in death or serious injury.
(000187)
WARNING
Loss of life. This product is not intended to
be used in a critical life support application.
Failure to adhere to this warning could result
in death or serious injury.
(000209b)
WARNING
Accidental Start-up. Disconnect the negative battery
cable, then the positive battery cable when working
on unit. Failure to do so could result in death
or serious injury.
(000130)
WARNING
Equipment damage. Only qualified service personnel may
install, operate, and maintain this equipment. Failure to follow
proper installation requirements could result in death, serious
injury, and equipment or property damage.
(000182a)
WARNING
Equipment damage. This unit is not intended for use as a
prime power source. It is intended for use as an intermediate
power supply in the event of temporary power outage only.
Doing so could result in death, serious injury, and
equipment damage.
(000247a)
WARNING
Electric shock. Only a trained and licensed electrician should perform wiring
and connections to unit. Failure to follow proper installation requirements
could result in death, serious injury, and equipment or property damage.
(000155a)
WARNING
Moving Parts. Do not wear jewelry when starting or operating this product.
Wearing jewelry while starting or operating this product could result in death
or serious injury.
(000115)
WARNING
Moving Parts. Keep clothing, hair, and appendages away from moving parts.
Failure to do so could result in death or serious injury.
(000111)
WARNING
Hot Surfaces. When operating machine, do not
touch hot surfaces. Keep machine away from
combustibles during use. Hot surfaces could
result in severe burns or fire.
(000108)
WARNING
Equipment and property damage. Do not alter
construction of, installation, or block ventilation for
generator. Failure to do so could result in unsafe
operation or damage to the generator.
(000146)
WARNING
Risk of injury. Do not operate or service this machine
if not fully alert. Fatigue can impair the ability to service
this equipment and could result in death or serious
injury.
(000215)
WARNING
Environmental Hazard. Always recycle batteries at an official recycling center
in accordance with all local laws and regulations. Failure to do so could
result in environmental damage, death or serious injury.
(000228)
2
Installation Guidelines For 60 Hz EcoGenTM Generators
Safety Rules & General Information
WARNING
Injury and equipment damage. Do not use generator
as a step. Doing so could result in falling, damaged
parts, unsafe equipment operation, and could result
in death or serious injury.
(000216)
· Inspect the generator regularly, and contact the nearest IASD for parts
needing repair or replace-
ment.
Exhaust Hazards
DANGER
Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not avoided, will result in death or
serious injury.
(000103)
WARNING
Equipment and property damage. Do not alter
construction of, installation, or block ventilation for
generator. Failure to do so could result in unsafe
operation or damage to the generator.
(000146)
WARNING
Asphyxiation. Always use a battery operated carbon monoxide alarm indoors and
installed according to the manufacturer’s instructions. Failure to do so could
result in death or serious injury.
(000178a)
· The generator must be installed and operated outdoors only.
Electrical Hazards
DANGER
Electrocution. Contact with bare wires, terminals, and connections while
generator is running will result in death or serious injury.
(000144)
DANGER
Electrocution. Never connect this unit to the electrical system of any
building unless a licensed electrician has installed an approved transfer
switch. Failure to do so will result in death or serious injury. (000150)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator from the normal power source.
Failure to do so will result in death, serious injury,
and equipment damage.
(000237)
DANGER
Electrocution. Verify electrical system is
properly grounded before applying power.
Failure to do so will result in death or serious
injury.
(000152)
DANGER
Electrocution. Do not wear jewelry while
working on this equipment. Doing so will
result in death or serious injury.
(000188)
DANGER
Electrocution. Water contact with a power source, if not avoided, will result
in death or serious injury.
(000104)
DANGER
Electrocution. In the event of electrical accident,
immediately shut power OFF. Use non-conductive
implements to free victim from live conductor. Apply
first aid and get medical help. Failure to do so will
result in death or serious injury.
(000145)
Fire Hazards
WARNING
Fire risk. Fuel and vapors are extremely flammable. Do not operate indoors.
Doing so could result in death, serious injury, or property or equipment
damage. (000281)
WARNING
Fire hazard. Do not obstruct cooling and ventilating airflow around the
generator. Inadequate ventilation could result in fire hazard, possible
equipment damage, death or serious injury. (000217)
Installation Guidelines For 60 Hz EcoGenTM Generators
3
Safety Rules & General Information
WARNING
Fire and explosion. Installation must comply with all local, state, and
national electrical building codes. Noncompliance could result in unsafe
operation, equipment damage, death or serious injury.
(000218)
DANGER
Risk of fire. Allow fuel spills to completely dry before starting engine.
Failure to do so will result in death or serious injury.
(000174)
WARNING
Fire hazard. Use only fully-charged fire extinguishers rated “ABC” by the
NFPA. Discharged or improperly rated fire extinguishers will not extinguish
electrical fires in automatic standby generators.
(000219)
WARNING
Risk of Fire. Hot surfaces could ignite combustibles, resulting in fire. Fire
could result in death or serious injury.
(000110)
WARNING
Electrocution. Refer to local codes and
standards for safety equipment required when
working with a live electrical system. Failure
to use required safety equipment could result
in death or serious injury.
(000257)
WARNING
Risk of Fire. Unit must be positioned in a manner that prevents combustible
material accumulation underneath. Failure to do so could result in death or
serious injury. (000147)
Comply with regulations the Occupational Safety and Health Administration
(OSHA) has established, or with equivalent standards. Also, verify that the
unit is applied, used, and maintained in accordance with the manufacturer’s
instructions and recommendations. Do nothing that might alter safe
application/usage and render the unit in noncompliance with the aforementioned
codes, standards, laws, and regulations.
Explosion Hazards
DANGER
Explosion and fire. Fuel and vapors are extremely flammable and explosive. No
leakage of fuel is permitted. Keep fire and spark away. Failure to do so will
result in death or serious injury. (000192)
DANGER
Explosion and fire. Connection of fuel source must be completed by a qualified
professional technician or contractor. Incorrect installation of this unit
will result in death, serious injury, and property and equipment damage.
(000151a)
Battery Hazards
DANGER
Electrocution. Do not wear jewelry while
working on this equipment. Doing so will
result in death or serious injury.
(000188)
WARNING
Explosion. Do not dispose of batteries in a fire. Batteries
are explosive. Electrolyte solution can cause burns and
blindness. If electrolyte contacts skin or eyes, flush with water
and seek immediate medical attention.
(000162)
WARNING
Explosion. Batteries emit explosive gases while charging.
Keep fire and spark away. Wear protective gear when
working with batteries. Failure to do so could result in
death or serious injury.
(000137a)
WARNING
Electrical shock. Disconnect battery ground
terminal before working on battery or battery
wires. Failure to do so could result in death
or serious injury.
(000164)
WARNING
Risk of burns. Batteries contain sulfuric acid and can cause severe chemical
burns. Wear protective gear when working with batteries. Failure to do so
could result in death or serious injury.
(000138a)
4
Installation Guidelines For 60 Hz EcoGenTM Generators
Safety Rules & General Information
WARNING
Risk of burn. Do not open or mutilate batteries.
Batteries contain electrolyte solution which can
cause burns and blindness. If electrolyte contacts
skin or eyes, flush with water and seek immediate
medical attention.
(000163a)
WARNING
Environmental Hazard. Always recycle batteries at an official recycling center
in accordance with all local laws and regulations. Failure to do so could
result in environmental damage, death or serious injury.
(000228)
Always recycle batteries in accordance with local laws and regulations.
Contact your local solid waste collection site or recycling facility to obtain
information on local recycling processes. For more information on battery
recycling, visit the Battery Council International website at:
http://batterycouncil.org
General Rules
DANGER
Loss of life. Property damage. Installation must always
comply with applicable codes, standards, laws and
regulations. Failure to do so will result in death
or serious injury.
(000190)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator from the normal power source.
Failure to do so will result in death, serious injury,
and equipment damage.
(000237)
WARNING
Equipment damage. Only qualified service personnel may
install, operate, and maintain this equipment. Failure to follow
proper installation requirements could result in death, serious
injury, and equipment or property damage.
(000182a)
WARNING
Electrocution. Refer to local codes and
standards for safety equipment required when
working with a live electrical system. Failure
to use required safety equipment could result
in death or serious injury.
(000257)
WARNING
Consult Manual. Read and understand manual completely before using product.
Failure to completely understand manual and product could result in death or
serious injury.(000100a)
· Follow all safety precautions in the owner’s manual, installation guidelines
manual, and other documents included with the equipment.
· Never energize a new system without opening all disconnects and breakers.
· Always consult local code for additional requirements for where unit is
being installed.
· Incorrect installation can result in personal injury and damage to the unit.
It may also result in the warranty being suspended or voided. All instructions
listed below must be followed including location clearances and pipe sizes.
Before You Begin
· Contact local inspector or city hall to be aware of all federal, state, and
local codes which could impact installation. Secure all required permits
before installing.
· Fully comply with all relevant NEC, NFPA, and OSHA standards, as well as all
federal, state, and local building and electric codes. This unit must be
installed in accordance with current NFPA 37 and NFPA 70 standards, and any
other federal, state, and local codes for minimum distances from other
structures.
· Verify capacity of NG meter or LP tank in regards to providing sufficient
fuel for both the unit and other household and operating appliances.
NEC Requirements
Local code enforcement may require Arc Fault Circuit Interrupters (AFCIs) to
be incorporated into the transfer switch distribution panel. The transfer
switch provided with this generator has a distribution panel which will accept
AFCIs (pre-wired transfer switches only).
Siemens Part No. Q115AF – 15A or Q120AF – 20A can be obtained from a local
electrical wholesaler and will simply replace any of the single pole circuit
breakers supplied in the pre-wired transfer switch distribution panel.
Installation Guidelines For 60 Hz EcoGenTM Generators
5
Safety Rules & General Information
Standards Index
WARNING
Loss of life. This product is not intended to
be used in a critical life support application.
Failure to adhere to this warning could result
in death or serious injury.
(000209b)
Strictly comply with all applicable national, state, and local laws, as well
as codes or regulations pertaining to the installation of this engine-
generator power system. Use the most current version of applicable codes or
standards relevant to the local jurisdiction, generator used, and installation
site.
NOTE: Not all codes apply to all products and this list is not all-inclusive.
In the absence of pertinent local laws and standards, the following
publications may be used as a guide (these apply to localities which recognize
NFPA and IBC).
1. National Fire Protection Association (NFPA) 70: The NATIONAL ELECTRIC CODE
(NEC)
2. NFPA 10: Standard for Portable Fire Extinguishers
3. NFPA 30: Flammable and Combustible Liquids Code
4. NFPA 37: Standard for Stationary Combustion Engines and Gas Turbines
5. NFPA 54: National Fuel Gas Code
6. NFPA 58: Standard for Storage and Handling Of Liquefied Petroleum Gases
7. NFPA 68: Standard On Explosion Protection By Deflagration Venting
8. NFPA 70E: Standard For Electrical Safety In The Workplace
9. NFPA 110: Standard for Emergency and Standby Power Systems
10. NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel
Burning Appliances
11. NFPA 220: Standard on Types of Building Construction
12. NFPA 5000: Building Code
13. International Building Code **
14. Agricultural Wiring Handbook ***
15. Article X, NATIONAL BUILDING CODE
16. ASAE EP-364.2 Installation and Maintenance of Farm Standby Electric Power
17. ICC:IFGC
This list is not all-inclusive. Check with the Authority Having Local
Jurisdiction (AHJ) for any local codes or standards which may be applicable to
your jurisdiction. The above listed standards are available from the following
internet sources:
- www.nfpa.org
** www.iccsafe.org
* www.rerc.org Rural Electricity Resource Council P.O. Box 309 Wilmington, OH 45177-0309
** www.asabe.org American Society of Agricultural & Biological Engineers 2950 Niles Road, St. Joseph, MI 49085
6
Installation Guidelines For 60 Hz EcoGenTM Generators
Unpacking and Inspection
Section 2: Unpacking and Inspection
General
NOTE: Carefully inspect contents for damage after unpacking. Unpack and
inspect unit immediately upon delivery to identify any damage which may have
occurred in transit. Any claims for shipping damage need to be filed as soon
as possible with the freight carrier. This is especially important if the unit
will not be installed for a period of time.
· This standby generator set is ready for installation with a factory supplied
and pre-mounted base pad and has a weather protective enclosure intended for
outdoor installation only.
· If any loss or damage is noted at time of delivery, have delivery person(s)
note all damage on the freight bill, or affix their signature under
consignor’s memo of loss or damage.
· If a loss or damage is noted after delivery, separate damaged materials and
contact carrier for claim procedures.
· “Concealed damage” is understood to mean damage to contents of a package not
evident at time of delivery, but discovered later.
Required Tools
· General SAE and Metric hand tools
Wrenches
Sockets
Screwdrivers
· Standard electrician’s hand tools
Drill and bits for mounting and routing conduits
· 4 mm hex key (for access to customer connections)
· 3/16 in hex key (test port on fuel regulator) · Manometer (for fuel pressure
checks) · Meter capable of measuring AC/DC voltage and
frequency
· Torque wrenches
Unpacking
1. Remove outer shipping carton. 2. See Figure 2-1. Remove wood frame.
000427
Figure 2-1. Crated Generator 3. See Figure 2-2. Lid will be locked. A set of
keys is
attached to the cardboard sheet on top of the unit. An additional set is
attached to the pallet bracket on the front intake end of the unit. Remove
keys from cardboard and pallet bracket.
006729
Figure 2-2. Keys As Shipped NOTE: The enclosed keys provided with this unit
are intended for service personnel only.
Installation Guidelines For 60 Hz EcoGenTM Generators
7
Unpacking and Inspection
IMPORTANT NOTE: DO NOT perform next step until generator has been transported
to installation site.
4. See Figure 2-3. Remove bolts and pallet brackets (A). Exercise caution
when removing generator. Dragging it off pallet will damage base. The unit
must be lifted from wooden pallet to remove.
NOTE: Bolts and pallet brackets are provided only for shipping purposes and
can be discarded after removal.
Enclosure Panel Removal
Generator installation requires removal of front panel and intake side panel.
Remove these panels when necessary. Proceed as follows to remove the panels.
Remove Front Access Panel
See Figure 2-5. Remove front access panel (A) by lifting straight up and out
once lid is open.
NOTE: Always lift front access panel straight up before pulling away from
enclosure (B and C). Do not pull panel away from the enclosure before lifting
up (D).
B
A
A
000426
Figure 2-3. Pallet Bracket Locations
Opening the Lid
1. Use keys to open generator lid.
C
2. See Figure 2-4. Two locks (A) secure lid; one on each side. Press down on
lid above side lock, and
unlock latch to correctly open lid.
A
A
Figure 2-4. Opening the Lid
009209
3. Repeat for other side. Lid may appear stuck if pressure is not applied
from the top.
NOTE: Always verify side locks are unlocked before attempting to lift lid.
D
009210
Figure 2-5. Remove Front Access Panel
8
Installation Guidelines For 60 Hz EcoGenTM Generators
Unpacking and Inspection
Intake Side Panel Removal
See Figure 2-6. The intake side panel (A) must be removed to access battery
compartment, fuel regulator, and sediment trap.
1. Raise lid and remove front panel.
2. Use a hex key to remove two mounting screws (B) and the hex screw on the
L-bracket.
3. Lift intake panel up and away from generator.
4. Inspect for any hidden freight damage. Contact freight carrier if damage
is present.
NOTE: Always lift intake side panel straight up before pulling away from
enclosure. Do not pull panel away from enclosure before lifting up (D).
Customer Connections and Loose Parts
See Figure 2-7 and Figure 2-8 for customer connections and loose parts
location. Figure 2-10 illustrates parts shipped loose.
E
C
B A
C D
A
D
B
001800
A Customer electrical connection area (behind access panel)
B Fuel regulator with sediment trap C Battery compartment (battery not
supplied) D Positive (+) and negative (-) battery cables E Location of “Loose
Shipped Parts”
Figure 2-7. Customer Connection Area and Loose Parts Location
Rear Connections
E
A
002961
B
Figure 2-6. Intake Side Panel Removal
C
Installation Guidelines For 60 Hz EcoGenTM Generators
D
001802
A Wi-Fi module B Main AC/Control wiring hole for 1-1/4 in conduit C Main
AC/Control wiring hole for 3/4 in conduit D Fuel connection hole E Auxiliary
shutdown switch
Figure 2-8. Rear Connections
NOTE: The generator is equipped with a Wi-Fi module. See Wi-Fi module owner’s
manual for further instruction.
9
Unpacking and Inspection
Generator Main Line Circuit Breaker Parts Shipped Loose
See Figure 2-9. The 2-pole circuit breaker (generator disconnect) (A) is rated according to relevant specifications.
F
E
B
B
A
001810
Figure 2-9. Generator Main Line Circuit Breaker
Breaker can be locked in OFF (OPEN) position for security during maintenance
or transfer switch service. Use an appropriately-sized padlock (not included)
with a shackle long enough to pass through both lock tabs (B).
NOTE: DO NOT leave breaker disconnect locked in the OFF (OPEN) position during
normal generator operation. Leaving breaker in the OFF (OPEN) position will
prevent generator from powering structure during a power outage when placed in
AUTO mode.
C
D
A
003599
A Keys B Flexible fuel line C Battery terminal cap D Rubber mounts E Fascia F
Oil Drain Pump Kit G Decal–Service entrance warning (not shown) H
Decal–Through conductors warning (not shown) J Decal–Service disconnect (not
shown) K Owner’s and Installation manuals (not shown) L Wi-Fi manual (not
shown) M Wi-Fi Quick Start Guide (not shown)
Figure 2-10. Parts Shipped Loose
10
Installation Guidelines For 60 Hz EcoGenTM Generators
Auxiliary Shutdown Switch
CAUTION
Equipment Damage. The auxiliary shutdown switch is
not to be used to power down the unit under normal
operating circumstances. Doing so will result in
equipment damage.
(000399)
All generators are equipped with an external means of shutting down the
generator which complies with the latest NEC code requirement. The primary
generator shutdown sequence is described in Control Panel Startup/ Testing.
See Figure 2-11. An auxiliary shutdown switch is provided on the exterior of
the generator back panel. This switch shuts down the generator and disables
restarts.
005491
Figure 2-11. External Auxiliary Shutdown Switch
NOTE: Whenever possible, perform primary shutdown procedure before disabling
generator with auxiliary shutdown switch.
See Figure 2-12. There is also an auxiliary shutdown switch located inside the
generator.
005492
Figure 2-12. Internal Auxiliary Shutdown Switch
Generator will not start if either switch is OPEN (O). Controller displays an
“Auxiliary Shutdown” alarm, and red LED “Alarm” light illuminates until switch
or switches are CLOSED (I), and alarm is cleared by pressing OFF mode button,
and then ENTER. Once cleared, generator can be placed back in AUTO or MANUAL.
Installation Guidelines For 60 Hz EcoGenTM Generators
Unpacking and Inspection 11
Unpacking and Inspection
This page intentionally left blank.
12
Installation Guidelines For 60 Hz EcoGenTM Generators
Site Selection and Preparation
Section 3: Site Selection and Preparation
Site Selection
Site selection is critical for safe generator operation. It is important to
discuss these factors with the installer when selecting a site for generator
installation:
· Carbon monoxide
· Fire prevention
· Fresh air for ventilation and cooling
· Water ingress prevention
· Proximity to utilities
· Suitable mounting surface
The following pages describe each of these factors in detail.
NOTE: The term “structure” is used throughout this section to describe the
home or building where generator is being installed. Illustrations depict a
typical residential home. However, instructions and recommendations presented
in this section apply to all structures regardless of type.
Carbon Monoxide
DANGER
Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not avoided, will result in death or
serious injury.
(000103)
IMPORTANT NOTE: Move to fresh air immediately and seek medical attention if
you feel sick, dizzy, or weak while the generator is running or after it
stops.
Generator exhaust contains carbon monoxide (CO)–a poisonous, potentially
lethal gas that cannot be seen or smelled. The generator must be installed in
a well ventilated area away from windows, doors, and openings. The selected
location should not allow exhaust gases to be drawn into structures where
people or animals may be present.
Carbon Monoxide Detectors
See Figure 3-1. CO detectors (K) must be used to monitor for CO and to warn
individuals about the presence of CO. CO detectors should be installed and
tested in accordance with the CO detector manufacturer’s instructions and
warnings. Contact local building inspection department for any applicable
requirements concerning CO detectors.
IMPORTANT NOTE: Common smoke alarms do NOT detect CO gas. Do not rely on smoke
alarms to protect residents or animals from CO. The only way to detect CO is
to have functioning CO alarms.
Installation Guidelines For 60 Hz EcoGenTM Generators
13
Site Selection and Preparation
Potential CO Entry Points
See Figure 3-1. Generator exhaust can enter a structure through large
openings, such as windows and doors. However, exhaust and CO can also seep
into the structure through smaller, less obvious openings.
Protect the Structure
Verify structure itself is correctly caulked and sealed to prevent air from
leaking in or out. Voids, cracks, or openings around windows, doors, soffits,
pipes, and vents can allow exhaust gas to be drawn into the structure.
Some examples of potential entry points are described and included in, but not
limited to, the accompanying table.
C
K
C
A
A
B
A A A
H
F
D
E A
J
G
Figure 3-1. Carbon Monoxide–Potential Entry Points
A
008781
ID
Entry Point
Description / Comments
A Windows and doors Architectural details which can be (or are) opened to admit fresh air into the structure.
B Garage door
CO can leak into garage if door is open, or does not seal correctly when closed.
C Attic vent
Attic vents, ridge vents, crawl space vents, and soffit vents can all admit generator exhaust.
D Basement windows Windows or hatches allowing ventilation to or from lower level of a structure.
E
Furnace intake / exhaust vent
Air intake and exhaust pipes for furnace.
F Wall cracks
Includes (but not limited to) cracks in wall, foundation, mortar, or air gaps around doors, windows, and pipes. See Protect the Structure.
G Dryer vent
Exhaust duct for clothes dryer.
H Airflow restrictions
Structural corners and locations with heavy vegetation restrict airflow. Exhaust gases can collect in such areas.
IMPORTANT NOTE: Mechanical and gravity outdoor air intake openings for HVAC supply
J
Make up air system
air systems shall be located not less than 10 feet (3048mm) horizontally from the generator enclosure. See Section 401 in the ICC Mechanical Code for any additional
requirements.
14
Installation Guidelines For 60 Hz EcoGenTM Generators
Site Selection and Preparation
Fire Prevention
The generator must be installed at a safe distance away from combustible
materials. Engine, alternator, and exhaust system components become very hot
during operation. Fire risk increases if unit is not correctly ventilated, is
not correctly maintained, operates too close to combustible materials, or if
fuel leaks exist. Also, accumulations of flammable debris within or outside
the generator enclosure may ignite.
Distance Requirements
See Figure 3-2. Minimum clearances must be maintained around the generator
enclosure. These clearances are primarily for fire prevention, but also to
ensure sufficient room for removing front and end panels for maintenance
purposes.
C
D F
B A
A
A
G
C
C
C
E
008782
Figure 3-2. Generator Distance Requirements
ID
Description
Definition
A
Front and end clearance
Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes shrubs, bushes, and trees.
B Rear clearance
Fuel and electrical connections are made here. 18 in (457 mm) minimum clearance per NFPA testing, labeling, and listing, unless state or local codes dictate otherwise.
C
Windows, vents, and openings
No operable windows, doors, vents, window wells, or openings in the wall are permitted near any point of the generator. See Potential CO Entry Points for more information.
D Existing wall
The generator should not be placed closer than 18 in (457 mm) from existing walls.
E Removable fence
A removable barrier (non-permanent; without footings) installed as a visual surround. Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in front of the generator.
F
Overhead clearance
5 ft (1.52 m) minimum distance from any structure, overhang, or projections from wall. DO NOT install under wooden decks or structures.
G
Maintenance and servicing
Maneuvering space around generator for performing routine maintenance tasks such as battery replacement and engine service. Do not attempt to conceal generator with shrubs, bushes, or plants.
Installation Guidelines For 60 Hz EcoGenTM Generators
15
Site Selection and Preparation
Fire Codes, Standards, and Guidelines
Generator installation must comply strictly with ICC IFGC, NFPA 37, NFPA 54,
NFPA 58, and NFPA 70 standards. These standards prescribe the minimum safe
clearances around and above the generator enclosure.
NFPA 37
NFPA 37 is the The National Fire Protection Association’s standard for the
installation and use of stationary combustion engines. Its requirements limit
the spacing of an enclosed generator set from a structure or wall, and require
generator to be located where it is readily accessible for maintenance,
repair, and first responders.
NFPA 37, Section 4.1.4, Engines Located Outdoors: Engines, and their
weatherproof housings if provided, installed outdoors shall be located at
least 5 ft (1.52 m) from openings in walls and at least 5 ft (1.52 m) from
structures having combustible walls. A minimum separation shall not be
required where the following conditions exist:
1. The adjacent wall of the structure has a fire resistance rating of at
least one hour.
2. The weatherproof enclosure is constructed of noncombustible materials and
it has been demonstrated that a fire within the enclosure will not ignite
combustible materials outside the enclosure.
Annex A–Explanatory Material
A4.1.4 (2) Means of demonstrating compliance are by means of full scale fire
test or by calculation procedures.
Because of the limited spaces frequently available for installation, it has
become apparent that exception (2) would be beneficial for many residential
and commercial installations. The manufacturer contracted with an independent
testing laboratory to run full scale fire tests.
NOTE: The Southwest Research Institute (SwRI) is a nationally recognized third
party testing and listing agency. SwRI testing approves 18 in (457 mm)
installation minimum from the rear panel of the generator to an adjacent
structure for fire protection.
The criteria was to determine the worst case fire scenario within the
generator and to determine the ignitability of items outside the engine
enclosure at various distances. The enclosure is constructed of non-
combustible materials, and the results and conclusions from the independent
testing lab indicated that any fire within the generator enclosure would not
pose any ignition risk to nearby combustibles or structures, with or without
fire service personnel response.
002158
Figure 3-3. Southwest Research Institute Marking
http://www2.swri.org/www2/listprod/
DocumentSelection.asp?ProductID=973&IndustryID=2
Based on this testing and the requirements of NFPA 37, Sec 4.1.4, the
guidelines for installation of the generators listed above are changed to 18
in (457 mm) from the back side of the generator to a stationary wall or
building For adequate maintenance and airflow clearance, the area above the
generator should be at least 5 ft (1.52 m) with a minimum of 3 ft (0.91 m) at
the front and ends of the enclosure. This includes trees, shrubs, and bushes.
Vegetation not in compliance with these clearance parameters could obstruct
air flow. In addition, exhaust fumes from the generator could inhibit plant
growth. See Figure 3-2 and the accompanying descriptions.
Generator Maintenance
Regular maintenance is crucial for minimizing exhaust emissions and reducing
the risk of fire or equipment failure. For example:
· A dirty air filter or low engine oil level may cause engine to overheat.
· Incorrect spark plug gaps may cause engine backfiring and incomplete
combustion.
IMPORTANT NOTE: See Maintenance section of generator owner’s manual to view a
table of scheduled maintenance tasks and procedures. Perform all maintenance
tasks as directed.
16
Installation Guidelines For 60 Hz EcoGenTM Generators
Site Selection and Preparation
Fresh Air for Ventilation and Cooling
Install unit where air inlet and outlet openings will not become obstructed by
leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting,
consider using a windbreak at a safe distance to protect the unit.
Suitable Mounting Surface
See Figure 3-4. Prepare a rectangular area approximately 5 in (127 mm) deep
(A) and approximately 3 in (76.2 mm) longer and wider (B) than the generator
on all sides.
Water Ingress Avoidance
· Select a location on high ground where water levels will not rise and flood
the generator. This unit should not operate in, or be subjected to, standing
water.
· Install unit where rain gutter downspouts, roof runoff, landscape
irrigation, water sprinklers, or sump pump discharge does not flood unit or
spray enclosure, including any air inlet or outlet openings.
· Excess moisture can cause excess corrosion and decrease life expectancy of
the unit.
Proximity to Utilities
· Contact local utility providers and verify proposed site selection meets all
required utility placement requirements before installation. This could affect
warranty coverage.
· Remember, laws and or codes may regulate distance and location of unit to
specific utilities.
· It is recommended to pick a location where the generator is as close as
possible to the transfer switch and the fuel supply, while verifying the site
location conforms to the rest of the Site Selection section.
Verify Wi-Fi Range
See Wi-Fi manual shipped with the unit if planning to use the Wi-Fi feature.
Transportation Recommendations
Use a suitable cart or equipment to carry generator, including wooden pallet,
to installation site. Place cardboard between cart and generator to prevent
any damage or scratches to generator.
Do not lift, carry, or move generator by grasping the louvers. Doing so may
bend or damage the sheet metal.
B
A
000856
Figure 3-4. Compacted Gravel or Concrete Pad
Select base type as desired or as required by local laws or codes. The
generator is typically placed on pea gravel, crushed stone, or a concrete pad.
Follow all applicable codes if a concrete pad is required. Verify surface
where generator will be mounted is compacted, leveled, and will not erode over
time. Generator must be level within 0.5 in (13 mm) all around.
Placement on Roofs, Platforms, and Other Supporting Structures
Where required to place generator on a roof, platform, deck, or other
supporting structure, generator must be placed in accordance with the
requirements in NFPA 37, Section 4.1.3. Generator can be located 18 in (457
mm) from structures having combustible walls and 5 ft (1.52 m) from any
operable opening in the structure. Surface beneath the generator and beyond
must be noncombustible to a minimum distance of 12 in (30.5 cm). Contact local
Building Inspection Department or fire department to determine which
noncombustible materials are approved for installation.
Installation Guidelines For 60 Hz EcoGenTM Generators
17
Site Selection and Preparation
This page intentionally left blank.
18
Installation Guidelines For 60 Hz EcoGenTM Generators
Section 4: Generator Placement
Generator Placement
Generator Placement
See Figure 4-1. All air-cooled generators come with a composite pad. The
composite pad elevates the generator and helps prevent water from pooling
around base.
Three 3/8 in (or M10) lag bolts (not supplied) are recommended for securing
the generator to a concrete pad.
NOTE: The top of the generator carton has a template which can be used to mark
the concrete pad to pre-drill the mounting holes.
Figure 4-1. Composite Pad
000612
The composite pad allows the generator to be placed on two types of surfaces:
· on 5 in (127 mm) of compacted pea gravel or crushed stone
· on a concrete pad
See local codes to verify what type of site base is required. If a concrete
pad is required, all federal, state, and local codes must be followed. Place
generator, with composite pad attached, and position correctly as per
dimensional information given in Site Selection and Preparation.
NOTE: Generator must be level within 0.5 in (13 mm).
NOTE: See Figure 4-2. DO NOT remove composite pad for mounting generator to
concrete. The composite pad is pre-drilled to accommodate mounting bolts.
Fascia Installation
1. Locate the four threaded black rubber bumpers supplied with the loose
parts. (See Parts Shipped Loose.)
2. See Figure 4-3. Remove bumpers from bag and screw into threaded holes
located inside the end pieces of the fascia (two each) opposite one another
(A). B A
C
001804
Figure 4-2. Mounting Hole Locations
Three mounting holes are available if codes require securing generator to
concrete. Mounting holes are located inside the generator compartment–two in
front and one in back.
Installation Guidelines For 60 Hz EcoGenTM Generators
Figure 4-3. Fascia Installation
000614
3. Snap one of the end pieces into one of the front/ rear pieces of fascia.
Repeat this action with the other two remaining pieces of fascia (B).
NOTE: Do not assemble all four pieces together at this point.
4. Place both assemblies at the generator base and fit the rubber mounts into
the lifting holes in the generator base (C).
5. Once aligned, snap together the two remaining connection points.
19
Generator Placement
This page intentionally left blank.
20
Installation Guidelines For 60 Hz EcoGenTM Generators
Fuel Conversion / Gas Connections
Section 5: Fuel Conversion / Gas Connections
Fuel Requirements and Recommendations
DANGER
Explosion and fire. Fuel and vapors are extremely flammable and explosive. No
leakage of fuel is permitted. Keep fire and spark away. Failure to do so will
result in death or serious injury.
(000192)
NOTE: NG is lighter than air and will collect in high areas. LP gas is heavier
than air and will settle in low areas.
LP gas should only use a vapor withdrawal system. This type of system uses
vapors formed above liquid propane in the storage tank. The unit will run on
NG or LP gas, but has been factoryconfigured to run on NG.
NOTE: Should the primary fuel need to be changed to LP gas, the fuel system
needs to be reconfigured. See Fuel Conversion for instructions on converting
the fuel system.
BTU Content Recommended fuels should have a BTU content of at least 1,000
BTU/ft3 (37.26 MJ/m3) for NG; or at least 2,500 BTU/ft3 (93.15 MJ/m3) for LP
gas.
NOTE: BTU fuel content information is available from fuel supplier.
Fuel Pressure Required fuel pressure for NG is 3.57.0 in water column
(0.871.74 kPa) at the generator fuel inlet. Required fuel pressure for LP
vapor is 1012 in water column (2.49 2.99 kPa) at the generator fuel inlet.
NOTE: The primary regulator for the LP gas supply is NOT INCLUDED with
generator.
NOTE: All pipe sizing, construction, and layout must comply with NFPA 54 for
NG applications and NFPA 58 or ICC IFGC for LP gas applications. Verify fuel
pressure NEVER drops below required specification once generator is installed.
See the NFPA website at www.nfpa.org for further information regarding NFPA
requirements.
Always contact local fuel suppliers or fire marshal to verify codes and
regulations for correct installation. Local codes will mandate correct routing
of gaseous fuel line piping around gardens, shrubs, and other landscaping.
Piping strength and connections should be given special consideration for
installations in areas at risk for flooding, tornadoes, hurricanes,
earthquakes, and unstable ground. IMPORTANT NOTE: Use an approved pipe sealant
or joint compound on all threaded NPT fittings. NOTE: All installed gaseous
fuel piping must be purged and leak tested prior to initial startup in
accordance with local codes, standards, and regulations.
Fuel Conversion
Proceed as follows to convert from NG configuration to LP vapor: See Figure
5-1. The orange fuel conversion knob (A) is located above the fuel mixer (B).
Turn fuel conversion knob towards marked fuel source arrow until it stops to
select fuel type. Fuel conversion knob will rotate 180° and slide into mixer
body when converting to LP gas. NOTE: The fuel selection (LP/NG) must be
entered on the controller during initial startup using the Install Wizard Menu
Map navigation menu, or in EDIT menu under “Fuel Selection.”
B A
009091
Figure 5-1. Fuel Conversion Knob Location
Installation Guidelines For 60 Hz EcoGenTM Generators
21
Fuel Conversion / Gas Connections
Fuel Consumption
Generator
Natural Gas
1/2 Load
Full Load
1/2 Load
Propane
Full Load
15 kW
5.52 / 195
7.87 / 278
1.84 / 6.95 / 66.8
2.76 / 10.45 / 100
- Natural gas is in m3/h / ft3/h ** Propane is in gal/h (LP) / L/h (LP) / ft3/h (LPV) *** Values given are approximate These are approximate values. Use the appropriate spec sheet or fuel data decal for specific values. Verify gas meter is capable of providing enough fuel flow to include household appliances and all other loads.
NOTE: The fuel supply and pipe MUST be sized at 100% load BTU/h (Megajoule/h) rating.
Always see fuel data label for the correct BTU/h or Megajoule/h, and required
fuel pressures:
Natural Gas: BTU/h = ft3/h x 1000 Megajoules/h = m3/h x 37.26
Liquid Propane Gas (Vapor): BTU/h = ft3/h x 2500 Megajoules/h = m3/h x 93.15
Fuel Line Sizing
Selecting the correct size fuel line is crucial to correct operation of the
unit.
IMPORTANT NOTE: Generator inlet size DOES NOT dictate the size of gas pipe to
be used!
For further information see NFPA 54 for NG, or NFPA 58 or ICC IFGC for LP.
Measure distance from generator to fuel source.
IMPORTANT NOTE: The generator should be plumbed directly from the fuel source,
not off the end of an existing low pressure system.
22
Installation Guidelines For 60 Hz EcoGenTM Generators
Fuel Conversion / Gas Connections
Natural Gas Pipe Sizing
To determine correct NG pipe size, find the kW rating of generator in the left
column, and trace to the right. The number to the right is maximum length
(measured in ft / m) allowed for the pipe sizes on top. Pipe sizes are
measured by trade size diameter to include any fittings, valves (must be full
flow), elbows, tees, or angles.
NOTE: See Table B.3.2 in NFPA 54 or Table A.2.2 in the ICC IFGC, Equivalent Lengths of Pipe Fittings and Valves for the correct values to be added to overall fuel piping length. Tables are based on schedule 40 black pipe. If installing any other piping system, follow pipe sizing charts for selected piping system.
Table 5-1. NG Pipe Sizing
Pipe Size (in / mm)
For 57 in Water Column (1.241.74 kPa)
Allowable Pipe Distances (ft / m)
For 3.55 in water column (0.871.24 kPa)
0.75 / 19
1 / 25
1.25 / 32
1.5 / 38
2 / 51
1 / 25
1.25 / 32
1.5 / 38
15 kW
10 / 3.1
35 / 10.7 140 / 42.3 300 / 91.4
—
10 / 3.1
60 / 18.3 125 / 38.1
LP Gas Pipe Sizing
To determine correct LP gas pipe size, find the kW rating of generator in the
left column, and trace to the right. The number to the right is maximum length
(measured in ft / m) allowed for pipe sizes on top. Pipe sizes are measured by
trade size diameter to include any fittings, valves (must be full flow),
elbows, tees, or angles. See Table B.3.2 in NFPA 54 or Table A.2.2 in the ICC
IFGC, Equivalent Lengths of Pipe Fittings and Valves for the correct values to
be added to overall fuel piping length.
NOTE: Pipe sizes are from the outlet of the second stage regulator to the fuel
shutoff valve. Table is based on schedule 40 black pipe. If installing any
other piping system, follow the pipe size charts for the selected piping
system.
NOTE: Recommended minimum LP tank size is 250 gal (946 L). Contact LP provider
to correctly size LP tank to generator. Vertical tanks, which are measured in
pounds (or kilograms), are permitted if correctly sized for the generator. Do
not connect generator to a 20 or 30 lbs LP
tank.
Table 5-2. LP Gas Pipe Sizing
Pipe Size (in / mm)
For 1012 in water column (2.492.99 kPa)
Allowable Pipe Distances (ft / m)
0.75 / 19
1 / 25
1.25 / 32
15 kW
40 / 12.2
175 / 53.3
550 / 167.6
Installation Guidelines For 60 Hz EcoGenTM Generators
23
Fuel Conversion / Gas Connections
Installing and Connecting Fuel Lines .
DANGER
Explosion and fire. Fuel and vapors are extremely flammable and explosive. No
leakage of fuel is permitted. Keep fire and spark away. Failure to do so will
result in death or serious injury.
(000192)
IMPORTANT NOTE: NG and LP gas are highly volatile substances. Strictly adhere
to all safety procedures, codes, standards, and regulations. Fuel line
connections should be made by a certified contractor familiar with local
codes. Always use AGAapproved gas pipe and a quality pipe sealant or joint
compound. Verify capacity of NG meter or LP tank to provide sufficient fuel
for both the generator and other operating appliances.
Fuel Shutoff Valve See Figure 5-2. The generator will require an external
manual fuel shutoff valve (A) on the fuel line. NOTE: Fuel shutoff valve must
be installed at a readily accessible location, and within 6 ft (1.8 m) of
generator fuel inlet.
A
B C
001816
Figure 5-2. Sediment Trap, Fuel Shutoff Valve with Manometer Port, and
Flexible Fuel Line
Figure 5-3 illustrates a fuel shutoff valve with a manometer port for making
fuel pressure checks. This optional accessory fuel shutoff valve permits
making pressure checks for diagnostic purposes without going into the
generator enclosure.
000743
Figure 5-3. Fuel Shutoff Valve with Manometer Port
Fuel shutoff valves available through an IASD: · 1/2 in ball valve, part
number 0K8752 · 3/4 in ball valve, part number 0K8754 · 1 in ball valve, part
number 0K8184 · 1-1/4 in ball valve, part number 0L2844 · 1-1/2 in ball valve,
part number 0L2845
Flexible Fuel Line
See Figure 5-2. When connecting flexible fuel line (B) to generator, use a
listed assembly meeting the requirements of ANSI Z21.75/ CSA 6.27–Connectors
for Outdoor Gas Appliances and Manufactured Homes or AGAapproved flexible fuel
line in accordance with local regulations.
Flexible fuel line must not be connected directly to generator fuel inlet.
Always connect flexible fuel line to an approved gas fitting.
The purpose of flexible fuel line is to isolate vibration from the generator
to reduce possibility of a gas leak at one of the connection points.
NOTE: Follow all installation instructions and warnings provided with flexible
fuel line. Do not remove any labels or tags. Flexible fuel line must be
installed horizontally, and must be installed between fuel shutoff valve and
generator fuel inlet.
Sediment Trap
See Figure 5-2. Some local codes require a sediment trap (C). The fuel
regulator connection has an integrated sediment trap.
The sediment trap must be cleaned periodically according to local codes. See
owner’s manual for more information.
24
Installation Guidelines For 60 Hz EcoGenTM Generators
Fuel Conversion / Gas Connections
Checking Fuel Line Connections
Checking Fuel Pressure
Proceed as follows to check fuel pressure at the regulator in the generator:
1. Close fuel supply valve. 2. See Figure 5-4. Remove top fuel pressure test
port
from regulator and install fuel pressure tester (manometer).
3. Open fuel supply valve and verify fuel pressure is within specified
values.
4. Record static fuel pressure:
NOTE: Fuel pressure can also be tested at the manometer port on fuel shutoff
valve shown in Figure 5-2.
NOTE: See Fuel Data Decal or spec sheet for correct fuel pressure
specifications. If fuel pressure is not within specifications, contact local
fuel supplier.
5. Close fuel supply valve when completed, but keep manometer connected for
future tests of the generator while starting, running, and under loads.
Performing Fuel System Leak Test
DANGER
Explosion and fire. Fuel and vapors are extremely flammable and explosive. No
leakage of fuel is permitted. Keep fire and spark away. Failure to do so will
result in death or serious injury.
(000192)
All products are factory-tested before shipping to verify the performance and
integrity of the fuel system. However, it is important to perform a final fuel
system leak test before starting the generator. The entire fuel system should
be tested from supply to regulator. See Figure 5-5. Perform a final fuel
system leak test after generator installation. The test will identify possible
leaks at all connection points (A). It is best practice to perform a fuel
system leak test during normally-scheduled maintenance.
A
A
001807
Figure 5-4. Checking Pressure with Manometer A
004038
Figura 5-5. Connection Points to Leak Check Inspect for leaks by spraying all
connection points with a non-corrosive gas leak detection fluid. The solution
should not be blown away or form bubbles.
Installation Guidelines For 60 Hz EcoGenTM Generators
25
Fuel Conversion / Gas Connections
Natural Gas Installation (Typical)
A D
E I
F C
B
G
H
J
008965
NG BTU/h = ft3/h X 1000
Megajoules/h = m3/h X 37.26
A Fuel data decal
B Minimum distance from rear obstruction–see Distance Requirements
C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft (1.83 m) away from fuel inlet
D Pipe fittings (field supplied)
E Flexible fuel line
F Check clearance with gas provider
G Size gas meter for 100% generator load plus all appliance loads
H For underground installations, verify piping system for code compliance
I Reinforcing rod with clamps
J To gas main
Figure 5-6. Natural Gas Installation (typical)
26
Installation Guidelines For 60 Hz EcoGenTM Generators
LP Gas (Vapor) Installation (Typical)
A D
E
G
H
Fuel Conversion / Gas Connections
JK L
C B
F
008966
LPG BTU/h = ft3/h X 2500
Megajoules/h = m3/h X 93.15
A Fuel data decal
B Minimum distance from rear obstruction–see Distance Requirements
C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft (1.83 m) away from fuel inlet.
D Pipe fittings (field supplied)
E Flexible fuel line
F Verify minimum distance requirements for regulator vent according to local gas codes.
G Clamp
H Secondary fuel pressure regulator
J
Manual shutoff valve
K Primary fuel pressure regulator
L Fuel tank–sized large enough to provide required MJ/BTU for generator and ALL connected appliance loads. Be sure to correct for weather evaporation.
Figure 5-7. LP Gas (Vapor) Installation (typical)
Installation Guidelines For 60 Hz EcoGenTM Generators
27
Fuel Conversion / Gas Connections
This page intentionally left blank.
28
Installation Guidelines For 60 Hz EcoGenTM Generators
Section 6: Electrical Connections
Generator Connections
See Figure 6-1. The electrical wiring enclosure is located behind an access
panel on the intake end of the unit. Remove intake side panel as directed in
Intake Side Panel Removal, and then remove access panel. Connect wires
according to diagram and tables.
1. Remove main AC / control wiring knock-out plugs from back of generator.
2. Using appropriate wiring hole, install conduit and main AC and control
wires between generator and transfer switch.
3. Close unused hole with a NEMA 3R rated plug (field-supplied).
NOTE: All conductors are to be rated for minimum 300V. Control system
interconnections may consist of N1, N2, and T1, and leads 23 and 194. All of
the generator control wiring circuits are Class 1 remote control or signaling
circuits. Class 1 circuits are required to be installed in accordance with
Part 1 of NEC Article 300 and with a NEC recognized Chapter 3 wiring method.
The use of low voltage cables for the generator control circuit wiring is
prohibited. See instruction manual of the specific engine generator for wiring
connection details. Recommended wire gauge sizes for this wiring depends on
wire length, as recommended in Table 6-3.
Exception: Conductors of AC and DC circuits, rated 1000 volts nominal or less,
shall be permitted to occupy the same equipment, cable, or conduit. All
conductors shall have an insulation rating equal to at least the maximum
circuit voltage applied to any conductor within the equipment, cable, or
conduit. See NEC 300.3(C)(1).
4. See Figure 6-1. Strip insulation from wire ends. Do not remove excessive
insulation. Route sense wires through supplied wire tie (C1), and connect to
sense wire terminal block (B). Push down on spring loaded connection point
with a flat head screwdriver, insert wire, and release.
5. Using the same process, route control wires through second supplied wire
tie (C2), and connect to control wire terminal block (A).
6. When all wires are securely connected to correct terminals, tighten wire
ties and clip excess length.
NOTE: Only bare wire should be inserted into each terminal. Do not insert any
wire insulation into terminals.
NOTE: Damage caused by mis-wiring of the interconnect wires is not
warrantable.
Electrical Connections
Installation Guidelines For 60 Hz EcoGenTM Generators
29
Electrical Connections
Control Wiring
10
1
DC GROUND
2 194
2 + 12 VDC
3 23
3TRANSFER
1 N1
1 UTILITY
2
SENSE
N2
2
3 T1
VAC LOAD 3 SUPPLY
A E1
B
C1
C2
10
1
DC GROUND
2 194
2 + 12 VDC
3 23
3TRANSFER
1 N1
1 UTILITY 2 SENSE
N2
2
3 T1
VAC LOAD 3 SUPPLY
E2
J
H
D
F
Figure 6-1. Electrical Wiring Connections
ID Description A Control wire terminal block B Sense wire terminal block C1 Wire tie for sense wires
Table 6-1. Electrical Wiring Connection Points
ID Description
ID Description
C2 Wire tie for control wires
E2 Power lug E2
D Neutral lug
F Ground stud
E1 Power lug E1
G Ground lug
G
005810
ID Description H Neutral stud J Neutral bar —-
Table 6-2. Customer Wiring Connections
Terminal Numbering Decal
Wire Numbers
YELLOW ***
N1 & N2 – 240 VAC – Sensing for utility dropout and pickup. Required for battery heater and oil heater.
BLUE *
T1 – Fused 120 VAC for battery charger. Breather heater requires T1 connection to 120V.
Table 6-3. Control Wire Recommended Length and Size (Copper Conductors Only)
Maximum Wire Length
Recommended Wire Size
1115 ft (0.335 m)
No. 18 AWG
115185 ft (3556 m)
No. 16 AWG
185295 ft (5689 m)
No. 14 AWG
295460 ft (89140 m)
No. 12 AWG
BLACK **
0 – DC (-) Common ground wire
RED ***
194 – DC (+) 12 VDC for transfer controls
WHITE ***
23 – Transfer control signal wire
- Must be connected to keep battery charged whether unit is running or not. ** Required if generator is paired with optional Digital Power Management (DPM) smart technology. *** No connection required in off-grid mode.
30
Installation Guidelines For 60 Hz EcoGenTM Generators
Electrical Connections
Table 6-4. Ground and Neutral Connections (Copper or Aluminum Conductors)
See national and/or local codes to verify correct wire sizes.
No.
Description
Recommended Wire Size
Torque Spec
1
Power wire terminals
2/0 to 8 AWG
120 in-lb (13.56 Nm)
2
Large neutral lug
2/0 to 14 AWG
120 in-lb (13.56 Nm)
3 Large ground lug 2/0 to 14 AWG 120 in-lb (13.56 Nm)
4 Neutral bus bar
4-6 AWG 8 AWG 10-14 AWG
35 in-lb (3.95 Nm) 25 in-lb (2.82 Nm) 20 in-lb (2.26 Nm)
Wire 178
183
Table 6-5. Remote Start Connections
Connection
Location
Mated Fastons Two-Wire Start
Mated Fastons Two-Wire Start
Hanging from controller above battery compartment
Main AC Wiring
NOTE: Main AC wiring must be in accordance with local jurisdiction and codes.
NOTE: Generator lugs are rated at 167 °F (75 °C), copper or aluminum.
1. Strip insulation off wire ends. Do not remove excessive insulation.
2. See Figure 6-1. Loosen lugs at neutral (D), ground (G), and power wire
(mains) terminals (E1, E2).
3. Connect ground wire to ground lug and tighten to required specification.
See Table 6-4.
4. Connect neutral wire to neutral lug if applicable. Tighten to required
specification. See Table 6-4.
5. Insert power wires (E1 and E2) into corresponding lugs. Tighten to
required specification.
6. Verify factory-installed ground array and neutral connections are
correctly tightened to 25 in-lb (2.82 Nm).
NOTE: Neutral wire must remain connected to keep battery charged whether
generator is running or not.
NOTE: Neutral bonding For installations requiring neutral to be bonded to
ground, this is done on the customer connections terminals inside generator.
See Figure 6-1. Connect a suitably sized system bonding jumper in accordance
with NEC Table 250.102(C)(1) from neutral bar (J) to ground stud (F). Tighten
ground stud nut to 35 in-lbs (3.95 Nm). This is required when generator is
installed as a separately derived system. Generator will also require a
connection to a grounding electrode system in accordance with NEC Article
250.64. It is not required when generator is a backup source in a utility
supplied electrical system with a 2-pole transfer switch. Installation must be
made in accordance with NEC Articles 250.30 and 250.35(A) if generator will be
installed as a separately derived system.
NOTE: 120V loads can be connected across either E1 to Neutral or E2 to
Neutral. If running in this 120V configuration, limit load across either
connection to 50% of rated load to prevent damage to wires or main line
circuit breaker.
NOTE: Tighten all wiring lugs, bus bars, and connection points to required
torque specifications.
Conductors of AC and DC circuits, rated 1000 volts nominal or less, shall be
permitted to occupy the same equipment, cable, or conduit. All conductors
shall have an insulation rating equal to at least the maximum circuit voltage
applied to any conductor within the equipment, cable, or conduit. See NEC
300.3(C)(1).
Service Entrance Decals
See Figure 2-7. Locate service entrance-related decals in the loose parts bag.
· Place service disconnect decal next to main line circuit breaker (generator
disconnect) (if required by local code).
· Place service entrance warning decal in an appropriate location according to
instructions printed on decal.
Common Alarm Relay (Option)
Alarms relating to generator and engine performance appear on the controller
and in the Mobile LinkTM application (if used). The controller is equipped
with a common alarm relay providing contacts for an optional customersupplied
external alarm indicator.
The common alarm relay is normally open until an alarm occurs, triggering
relay to close contacts.
Terminals for the common alarm relay are provided in the wiring harness near
the controller plug (Wires 209 and 210).
Contact rating is for resistive load only:
Contact rating
200 mA at 12 VDC
Installation Guidelines For 60 Hz EcoGenTM Generators
31
Electrical Connections
Battery Requirements
12 volts, Group 26R Wet Cell 540CCA minimum, or Group 35 AGM 650CCA minimum.
If internal battery charger is not connected to utility power, controller will
drain the 12VDC battery if not correctly maintained. Total power usage of
controller and Wi-Fi module while generator is not running is 2.5 W.
NOTE: A warning is displayed on the LCD when battery needs service.
NOTE: Do not use external battery chargers with OffGrid mode disabled and unit
equipped with a transfer switch.
NOTE: With Off-Grid mode enabled and unit equipped with a two-wire start, use
an external battery charger to maintain battery if T1 connection is not
connected to utility.
Battery Installation
WARNING
Explosion. Batteries emit explosive gases while charging.
Keep fire and spark away. Wear protective gear when
working with batteries. Failure to do so could result in
death or serious injury.
(000137a)
WARNING
Risk of burns. Batteries contain sulfuric acid and can cause severe chemical
burns. Wear protective gear when working with batteries. Failure to do so
could result in death or serious injury.
(000138a)
· (Group 26R batteries only): Fill battery with correct electrolyte fluid if
necessary.
· Fully charge battery before installing it. Complete the following steps
before installing and connecting battery:
1. Verify generator is OFF. 2. Turn off utility power supply to transfer
switch. 3. Remove 7.5A fuse from generator control panel.
Connecting Battery
WARNING
Explosion. Batteries emit explosive gases.
Always connect positive battery cable first to
avoid spark. Failure to do so could result in
death or serious injury.
(000133)
See Figure 6-2. Battery cables (A, B) were factory connected at the generator.
B
A
001832
Figure 6-2. Battery Cable Connections
Connect battery cables to battery posts as follows: 1. Connect red positive
battery cable (A: from starter contactor) to positive battery post. Tighten to
70 inlb (8 Nm). 2. Connect black negative battery cable (B: from frame ground)
to negative battery post. Tighten to 70 in-lb (8 Nm). 3. Install red battery
post cover (shipped with loose parts).
NOTE: Apply dielectric grease to battery posts to prevent corrosion.
NOTE: In areas where temperatures fall below 0 °F (-18 °C), a pad type battery
warmer is recommended to aid in cold climate starting. The battery warmer is
available as part of a cold weather kit from any IASD.
NOTE: Battery heater and oil heater require N1 and N2 connections to 240V
utility. Breather heater requires T1 connection to 120V.
A battery warmer is not necessary for AGM-style batteries.
Battery Disposal
WARNING
Environmental Hazard. Always recycle batteries at an official recycling center
in accordance with all local laws and regulations. Failure to do so could
result in environmental damage, death or serious injury.
(000228)
Always recycle batteries in accordance with local laws and regulations.
Contact your local solid waste collection site or recycling facility to obtain
information on local recycling processes. For more information on battery
recycling, visit the Battery Council International website at:
http://batterycouncil.org
32
Installation Guidelines For 60 Hz EcoGenTM Generators
Control Panel Startup/Testing
Section 7: Control Panel Startup/Testing
Control Panel Interface
The control panel interface is located under the enclosure lid. Verify both
left and right side locks are unlocked before attempting to lift enclosure
lid. Open lid as directed in Opening the Lid.
Using the AUTO/MANUAL/OFF Buttons
Button
Description of Operation
AUTO
Activates fully automatic system operation. Automatic operation allows unit to start automatically.
OFF
Shuts down engine and also prevents automatic operation of unit.
MANUAL Cranks and starts generator.
1. The display interface will launch Install Wizard upon first power-up of
the generator.
2. Follow on-screen instructions on the generator along with Quick Start
Guide supplied with the unit to connect generator to home Wi-Fi network.
3. Wait for on-line authentication of generator activation through connected
home Wi-Fi network.
4. Follow on-screen instructions to complete the Install Wizard.
NOTE: See Figure 7-2. If generator screen shows message shown below, press ESC
and then ENTER to reset to Install Wizard.
NOT ACTIVATED! XXX (H)
000425
Figure 7-1. Generator Control Panel
Generator Setup
The controller illuminates when battery power is applied to the generator
during the installation process. Generator must be activated before it will
automatically run in the event of a power outage.
Activation To activate the generator, go to www.activategen.com and follow the
instructions. Activation is a simple, one-time process. The generator will not
prompt to activate again once the unit is activated, even if the generator
battery, fuse, and battery charge circuit (T1) are disconnected.
NOTE: The generator must be connected to the home Wi-Fi network for automatic
authentication to be completed successfully. See Wi-Fi manual for more
information.
NOTE: If home Wi-Fi network is not available, follow instructions on
www.activategen.com.
Proceed as follows after activating generator on-line:
009102
Figure 7-2. Not Activated Screen
NOTE: Generator can only be placed in AUTO mode after completing activation
process.
IMPORTANT NOTE: Fuel selector knob must be set to the correct fuel for
generator to function correctly.
Installation Guidelines For 60 Hz EcoGenTM Generators
33
Control Panel Startup/Testing Display Reads
Language
–
English +
Enable Wi-Fi?
–
Yes
Activate me (ENT) or ESC to run in manual
To Activate go to www.activategen.com
Troubleshooting
Use arrow keys to scroll to desired language. Press ENTER to select.
Language can be changed later using the EDIT menu.
002227
Use arrow keys to either enable or disable Wi-Fi. If YES, see Wi-Fi manual. If
NO, continue.
004498
Press ENTER to begin activation process.
If ESCAPE is pressed instead of ENTER, generator will only run in manual mode (for test purposes) and NOT ACTIVATED will be displayed. Press ESC and then ENTER to reset Install Wizard.
002228
If unit has not been activated, go to www.activategen.com. If unit has been
activated, press ESC and then ENTER.
002229
34
Installation Guidelines For 60 Hz EcoGenTM Generators
Display Reads
Control Panel Startup/Testing Troubleshooting
Select Hour (0-23) – 6 +
Activation is complete when this screen is displayed. Follow controller prompts to complete installation.
002231
Cold Smart Start
The Cold Smart Start feature is factory-enabled, and can be disabled in the
EDIT menu. Generator will monitor ambient temperature and adjust its warm-up
delay accordingly when Cold Smart Start is enabled. If ambient temperature is
below a fixed temperature upon startup in AUTO mode (per chart below),
generator will warm up for 30 seconds, allowing engine to warm before load is
applied. If ambient temperature is at or above fixed temperature, generator
will start up with normal warm-up delay of six seconds. See Cold Smart Start
section in owner’s manual.
Table 7-1. Cold Smart Start Set Point
Generator Size
15 kW
Fixed Temperature
50 °F (10 °C)
NOTE: Cold Smart Start warmup is only available when off-grid mode is DISABLED.
Setting The Exercise Timer
This off-grid generator is not configurable to run in exercise mode. If an
exercise is desired, MANUAL mode may be used if connected loads are prepared
to accept electrical output while running. If using MANUAL mode, generator
will operate at the rated 3,600 rpm until OFF button is pressed.
NOTE: If using Wi-Fi, Mobile Link application should not be used to initiate
exercise mode if user does not wish generator to exercise.
IMPORTANT NOTE: Do not place generator in exercise mode if main line circuit
breaker is ON (CLOSED). An unexpected power surge may damage connected
equipment such as an inverter.
Before Initial Startup
CAUTION
Engine damage. Verify proper type and quantity of engine oil prior to starting
engine. Failure to do so could result in engine damage.
(000135)
NOTE: The unit has been run and tested at the factory prior to being shipped
and does not require any type of break-in.
NOTE: The unit comes filled with 5W-30 weight organic oil from the factory.
Check oil level and add appropriate viscosity and amount of oil if necessary.
Install Wizard See Figure 7-3. The Install Wizard immediately appears upon
initial startup. It allows user to input generator settings. The Install
Wizard starts every time AC and DC power are removed and reapplied to
generator.
Interconnect System Self Test Feature This controller goes through a system
self test at startup, which checks for utility voltage on DC circuits. This
check prevents damage if installer incorrectly connected AC utility power
sense wires into the DC terminal block. The controller will display a warning
message and lock out the generator if utility voltage is detected at the DC
terminal block, preventing damage to the controller. Power to controller must
be removed to clear this warning. Utility voltage must be turned on and
present at the N1 and N2 terminals inside the generator control panel for this
test to be performed and pass.
NOTE: All appropriate panels must be in place during any operation of
generator. This includes operation by a servicing technician, while conducting
troubleshooting procedures.
Installation Guidelines For 60 Hz EcoGenTM Generators
35
Control Panel Startup/Testing
Before starting, complete the following:
1. Verify generator is OFF.
2. Set generator main circuit breaker to OFF (OPEN).
3. Turn OFF all breakers to be powered by generator.
4. Verify auxiliary shutdown switch(es) are CLOSED (I).
5. Check engine crankcase oil level and, if necessary, fill to oil dipstick
FULL mark with recommended oil. Do not overfill.
6. Inspect fuel supply. Gaseous fuel lines must have been correctly purged
and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff
valves in the fuel supply lines must be open.
During initial start up only, generator may exceed normal number of start
attempts and experience an “OVERCRANK” fault. This is due to accumulated air
in the fuel system during installation. Reset control board by pressing OFF
mode button and ENTER button, and restart up to two more times if necessary.
If unit fails to start, contact an IASD for assistance.
36
Installation Guidelines For 60 Hz EcoGenTM Generators
37
Installation Guidelines For 60 Hz EcoGenTM Generators
Figure 7-3. Install Wizard Menu Map
Note: If language was previously programmed this goes directly to “Select Hour”
Power Up Unit
FIRMWARE V X.XX HARDWARE V X.XX
Language
+ English + Espanol + Francais + Portuguese –
+ …… –
ENTER
Install Wizard
Defaults to English. Select desired language by scrolling through list.
Setup Wi-Fi? Yes + Yes or No –
No
Follow setup process in
Wi-Fi manual
WIFI Signal XX%
Fuel Selection + NG or LP –
Fuel Selection + NG or LP –
Use UP and DOWN arrows to select fuel type, then press “ENTER”.
ENTER
Cold Smart Start? Å YES or NO Æ
Use UP and DOWN arrows. to select YES or NO. Press ENTER.
Update From: WIFI
ESC
SYSTEM
DATE/TIME
Select Hour (0-23)
- – 14 + ENTER
*Holding the Up or Down
arrow button for 2 seconds will speed dial through the selections
WIFI
SUB MENUS
+ UP ARROW =
– DOWN ARROW =
ENTER
Cold Smart Start? Å YES or NO Æ
ENTER
ENTER
Time Zone XXXXXX
WIFI Signal XX%
ENTER
Update From Server Continue? ENTER
Controller X.XX.XXX Server X.XX.XXX
Control Panel Startup/Testing
Control Panel Startup/Testing
38
Figure 7-4. Install Wizard Menu Map
ENTER
Select Minute (0-59) ENTER
- – 0 +
Select Month (1-12) ENTER
- – 2 +
Select Date (1-31) ENTER
- – 13 +
SYSTEM
DATE/TIME
SETUP WIFI SUB MENUS
ENTER
ESC USB OnlyNo WiFi
ENTER
ENTER
Select Year (0-99)
- – 13 +
ENTER
Switched to OFF Hours of Protection
0 (H)
Possible Message(s): Corrupted File Invalid File File Not Found
Unsupported Device*
- Re-try using a higher quality USB drive. File names on the USB cannot have more than 8 characters.
Firmware Update <- Insert USB ->
ENTER
Current: V X.XX USB: X.XX
ENTER
Are You Sure? – Yes or No +
ENTER
Select “Yes” then Press “Enter” to continue or Press “ESCAPE” to escape out of updating. During update process the Blue “Manual” light flashes, then the Green “Auto” light flashes. Sequence does this twice. When update is complete the unit returns to Install Wizard menu. When the controller powers up the very first screen displays the version number for a few seconds. When update is complete remove Thumb Drive, then follow the Install Wizard Menu.
Installation Guidelines For 60 Hz EcoGenTM Generators
008647
Control Panel Startup/Testing
Check Manual Transfer Switch Operation
DANGER
Electrocution. High voltage is present at transfer switch and terminals.
Contact with live terminals will result in death or serious injury.
(000129)
If installed with a transfer switch, see Manual Transfer Operation section of
owner’s manual for operating procedures.
Electrical Checks
DANGER
Electrocution. High voltage is present at transfer switch and terminals.
Contact with live terminals will result in death or serious injury.
(000129)
Proceed as follows to complete electrical checks if unit is equipped with a
transfer switch, and with off-grid mode DISABLED:
1. Verify generator is OFF. 2. Set generator main line circuit breaker
(generator
disconnect) to OFF (OPEN). 3. Turn off all circuit breakers/electrical loads
to be
powered by generator. 4. Turn on utility power supply to transfer switch using
the means provided (such as a utility main line circuit breaker). 5. Use a
calibrated AC voltmeter to verify utility power source voltage across transfer
switch terminals N1 and N2. Nominal line-to-line voltage should be 240 volts
AC. If voltage is incorrect, verify AC output and wiring from utility source
to N1 and N2 lugs at transfer switch. 6. Verify utility power source voltage
across terminals N1 and transfer switch neutral lug; then across terminal N2
and neutral. Nominal line-to-neutral voltage should be 120 volts AC (if wired
with a neutral). If voltage is incorrect, verify AC output and wiring from
utility source to N1 and N2 lugs at transfer switch. 7. Turn off utility power
supply to transfer switch when utility supply voltage is verified to meet
specification provided in Step 6. 8. Press MANUAL mode button on generator
panel. Engine will crank and start. Record cranking fuel pressure:
__. 9. Allow engine to warm up for approximately five minutes for
internal temperatures to stabilize. Then set generator MLCB (generator
disconnect) to ON
Installation Guidelines For 60 Hz EcoGenTM Generators
(CLOSED). Record running fuel pressure: __.
10. Connect a calibrated accurate AC voltmeter and a frequency meter across
transfer switch terminal lugs E1 and E2. Voltage should be 238242V at a
frequency of 59.560.5 Hz. If voltage is incorrect, verify generator main line
circuit breaker (generator disconnect) is closed and verify AC output and
frequency (Hertz or Hz) at generator main line circuit breaker (generator
disconnect). Verify wiring from generator to E1 and E2 lugs at transfer
switch.
11. Connect AC voltmeter test leads across terminal lugs E1 and neutral, then
across E2 and neutral (if wired with a neutral). In both cases, voltage
reading should be 119121 volts AC. If voltage is incorrect, verify generator
main line circuit breaker (generator disconnect) is closed and verify AC
output between E1 and E2 of the generator main line circuit breaker (generator
disconnect) and neutral at the generator.
12. Verify wiring from generator to E1, E2, and neutral lugs at transfer
switch.
13. Set generator main line circuit breaker (generator disconnect) to OFF
(OPEN).
14. Press generator OFF mode button. Engine will shut down.
Proceed as follows to complete electrical checks if unit is configured to run
without a transfer switch and with offgrid mode ENABLED:
1. Verify generator is OFF.
2. Set generator main line circuit breaker (generator disconnect) to OFF
(OPEN).
3. Turn off all circuit breakers and electrical loads to be powered by
generator.
4. Press MANUAL mode button on generator panel. Engine will crank and start.
Record cranking fuel pressure:____.
5. Allow engine to warm up for approximately five minutes to allow internal
temperatures to stabilize. Set generator MLCB (generator disconnect) to ON
(CLOSED). Record running fuel pressure: ____.
6. Connect AC voltmeter test leads across terminal lugs E1 and neutral, then
across E2 and neutral (if wired with a neutral). In both cases, voltage
reading should be 119121 volts AC. If voltage is incorrect, verify generator
main line circuit breaker (generator disconnect) is ON (CLOSED) and verify AC
output between E1 and E2 of generator main line circuit breaker (generator
disconnect) and neutral at the generator.
IMPORTANT NOTE: Do not proceed until generator AC voltage and frequency are
correct and within stated limits.
39
Control Panel Startup/Testing
Generator Tests Under Load
DANGER
Electrocution. Do not manually transfer under load. Disconnect transfer switch
from all power sources prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.
(000132)
Proceed as follows to test unit with electrical loads applied when unit is
equipped with a transfer switch and with off-grid mode DISABLED:
1. Verify generator is OFF. Set generator main line circuit breaker
(generator disconnect) to OFF (OPEN).
2. Turn off all breakers/electrical loads to be powered by generator.
3. Turn off utility power supply to transfer switch, using the means provided
(such as a main line utility breaker).
4. Manually set transfer switch to STANDBY, with load terminals connected to
generator E1/E2 terminals. Transfer switch operating lever should be down.
5. Push generator MANUAL button. Engine will crank and start immediately.
6. Verify fuel pressure while cranking. Record cranking fuel
pressure:____
7. Allow engine to stabilize and warm up for a few minutes.
8. Verify fuel pressure while running. Record running fuel pressure:____
9. Set generator main line circuit breaker (generator disconnect) to ON
(CLOSED). Loads are now powered by standby generator.
10. Turn on circuit breakers/electrical loads to be powered by generator one
by one.
11. Connect a calibrated AC voltmeter and a frequency meter across terminal
lugs E1 and E2. Voltage should be approximately 240 volts and frequency should
be approximately 60 Hz. If voltage and frequency are rapidly dropping as loads
are applied, generator may be overloading, or there may be a fuel issue.
Verify output current measurement of loads and/or fuel pressure.
12. Allow generator to run at full rated load for 2030 minutes. Listen for
unusual noises, vibration, or other indications of abnormal operation. Inspect
for oil leaks, evidence of overheating, etc.
13. Verify fuel pressure while under full load. Record loaded fuel pressure:
__.
14. Turn off electrical loads when testing under load is complete.
15. Set generator main line circuit breaker (generator disconnect) to OFF
(OPEN).
40
16. Allow engine to run at no-load for 25 minutes. 17. Press generator OFF
mode button. Engine will
shut down.
Proceed as follows to test unit with electrical loads applied when unit is
configured to run without a transfer switch and with off-grid mode ENABLED:
1. Verify generator is OFF. Set generator main line circuit breaker
(generator disconnect) to OFF (OPEN).
2. Turn off all breakers/electrical loads to be powered by generator.
3. Press MANUAL mode button on generator panel. Engine will crank and start.
4. Verify fuel pressure while cranking. Record cranking fuel
pressure:_____.
5. Allow engine to stabilize and warm up for a few minutes.
6. Set generator main line circuit breaker (generator disconnect) to ON
(CLOSED). Loads are now powered by standby generator.
7. Turn on circuit breakers and electrical loads to be powered by generator
one by one.
8. Connect a calibrated AC voltmeter and a frequency meter across terminal
lugs E1 and E2. Voltage should be approximately 240 volts and frequency should
be approximately 60 Hz. If voltage and frequency are rapidly dropping as loads
are applied, generator may be overloading, or there may be a fuel issue.
Verify output current measurement of loads and/or fuel pressure.
9. Allow generator to run at full rated load for 2030 minutes. Listen for
unusual noises, vibration, or other indications of abnormal operation. Inspect
for oil leaks, evidence of overheating, etc.
10. Verify fuel pressure while under full load. Record loaded fuel pressure:
__.
11. Turn off electrical loads when testing under load is complete.
12. Set generator main line circuit breaker (generator disconnect) to OFF
(OPEN).
13. Allow engine run at no-load for 25 minutes. 14. Press generator OFF mode
button. Engine will
shut down.
NOTE: If fuel pressure under full load is below minimum operating pressure
guideline, generator may not function correctly. Fuel pressure gauge needle
should also remain steady while testing. A fluctuating fuel pressure gauge
needle indicates gas piping may be undersized or restricted. It may also
indicate a step-down gas regulator is too small, or too close to the unit.
Installation Guidelines For 60 Hz EcoGenTM Generators
Control Panel Startup/Testing
Checking Automatic Operation
Proceed as follows to check system for correct automatic operation when unit
is equipped with a transfer switch and with off-grid mode DISABLED:
1. Verify generator is OFF.
2. Install front cover of transfer switch.
3. Turn on utility power supply to transfer switch using the means provided
(such as a utility MLCB).
NOTE: Transfer switch will transfer to utility position.
4. Set generator main line circuit breaker (generator disconnect) to ON
(CLOSED).
5. Press generator AUTO button. System is now ready for automatic operation.
6. Turn off utility power supply to transfer switch.
Generator is ready for automatic operation. Engine will crank and start when
utility power source is turned off after a five second delay (factory default
setting). After starting, transfer switch will connect load circuits to the
standby side after a 5 or 30 second delay (dealer programmable). See Cold
Smart Start. Allow system to operate through entire automatic sequence of
operation.
With generator running and loads powered by generator AC output, turn on
utility power supply to transfer switch. The following will occur:
· After approximately 15 seconds (dealer programmable), transfer switch will
transfer loads to utility power source.
· Approximately one minute after transfer, engine will shut down.
Proceed as follows to check the system for correct automatic operation when
configured to run without a transfer switch and with off-grid mode ENABLED:
1. Verify generator is OFF.
2. Press AUTO mode button. System is now ready for automatic operation.
3. Verify remote two-wire start test switch installed near the Alternative
Power Management System is set to ON (CLOSED). This causes generator to start
automatically.
4. With generator running and powering loads, set remote two-wire start test
switch to OFF (OPEN). Generator will shut down immediately (selectable to one
minute in the dealer menu) after two-wire remote start signal is OFF (OPEN).
3. Educate end-user on correct operation, maintenance, and service call
procedures.
Shutting Generator Down While Under Load or During a Utility Outage
DANGER
Automatic start-up. Disconnect utility power and render unit inoperable before
working on unit. Failure to do so will result in death or serious injury.
(000191)
IMPORTANT NOTE: To avoid equipment damage, follow these steps, in order,
during utility outages. Shutdowns may be required during utility outages to
perform routine maintenance or to conserve fuel.
To turn generator OFF: 1. Set main utility disconnect to OFF (OPEN). 2. Set
generator MLCB (generator disconnect) to OFF (OPEN). 3. Allow generator to run
for cool-down for approximately one minute. 4. Set generator to OFF at the
controller. 5. Remove 7.5A fuse from controller.
To turn generator back ON: 1. Install 7.5A fuse in controller. 2. Verify
generator MLCB (generator disconnect) is OFF (OPEN). 3. Set generator to AUTO
mode at the controller. 4. Generator will start and run. Allow generator to
run and warm up for a few minutes. 5. Set MLCB (generator disconnect) to ON
(CLOSED). 6. Set main utility disconnect to ON (CLOSED).
The system now operates in automatic mode.
Installation Summary
1. Verify installation has been performed correctly as outlined by the
manufacturer and that it meets all applicable laws and codes.
2. Test and verify correct operation of the system as outlined in the
appropriate installation and owner’s manuals.
Installation Guidelines For 60 Hz EcoGenTM Generators
41
Control Panel Startup/Testing
This page intentionally left blank.
42
Installation Guidelines For 60 Hz EcoGenTM Generators
Section 8: Troubleshooting
Troubleshooting
Generator Troubleshooting
Problem
Cause
Blown fuse.
Engine will not crank
Loose, corroded, or faulty battery cables. Faulty starter contact.
Faulty starter motor.
Discharged battery.
No fuel.
High fuel pressure.
Fuel selector in wrong position.
Engine cranks but
will not start
Faulty fuel solenoid (FS).
Faulty spark plug(s).
Valve clearance out of adjustment. Air cleaner clogged or damaged. Faulty spark plug(s).
Engine starts hard Incorrect fuel pressure. and runs rough
Generator is set to OFF, but engine continues to run
No AC output from generator
Fuel selector in wrong position. Valve(s) out of adjustment. Internal engine
issue. Controller wired incorrectly.
Faulty control board.
Main line circuit breaker (MLCB) (generator disconnect) is OFF (OPEN).
Generator internal failure. Engine may be warming up. See Cold Smart Start.
Correction Correct short circuit condition by replacing 7.5 A fuse in
generator control panel. Contact an IASD if fuse continues to blow.
Tighten, clean, or replace as necessary.*
Charge or replace battery. Replenish fuel / turn on fuel valve. Check and
adjust fuel pressure. Set fuel conversion valve to correct position. Replenish
fuel / turn on fuel valve. Clean; inspect gap; replace plug(s) if necessary.
Reset valve clearance. Inspect and clean air cleaner. Clean; inspect gap;
replace plug(s) as needed. Verify fuel pressure to regulator is 1012 in water
column (2.492.99 kPa) for LP gas, and 3.57.0 in water column (0.871.74 kPa)
for NG. Set fuel conversion valve to correct position. Adjust valve clearance.
Contact an IASD for assistance.
Contact an IASD for assistance.
Reset generator disconnect to ON (CLOSED).
Contact an IASD for assistance.
Check controller screen to verify status.
Installation Guidelines For 60 Hz EcoGenTM Generators
43
Troubleshooting
Problem
Cause
Correction
MLCB (generator disconnect) is OFF (OPEN). Reset generator disconnect to ON (CLOSED).
No transfer to standby after utility source failure **
Faulty transfer switch coil. Faulty transfer relay. Transfer relay circuit open. Faulty control logic board.
Contact an IASD for assistance.
Engine may be warming up. See Cold Smart Start.
Check controller screen to verify status.
Excessive engine oil.
Adjust oil to correct level.
Unit consumes large amounts of oil
Faulty engine breather. Incorrect type or viscosity of oil. Damaged gasket, seal, or hose.
Contact an IASD for assistance.
See Engine Oil Requirements in owner’s manual.
Inspect for oil leaks.
Restricted air filter.
Replace air filter.
Wi-Fi network connection broken or intermittent
Various.
See Wi-Fi module owner’s manual.
- Contact an IASD or visit www.generac.com for assistance. ** Not applicable with Off-Grid mode ENABLED.
44
Installation Guidelines For 60 Hz EcoGenTM Generators
Section 9: Quick Reference Guide
Quick Reference Guide
System Diagnosis
To clear an active alarm, press OFF mode button on control panel, then ENTER
button. Then press AUTO mode button. Contact an IASD if alarm reoccurs.
Active Alarm LED
Problem
Things to Check
Solution
NONE
FLASHING Unit running in AUTO but
GREEN
no power in house.
Check MLCB (generator disconnect).
Check MLCB. If it is ON, contact an IASD.
HIGH TEMPERATURE
RED
Unit shuts down during operation.
Check LED’s / Screen for alarms.
Inspect ventilation around generator, intake, exhaust, and rear of generator. If no obstructions are present, contact an IASD.
OVERLOAD REMOVE LOAD
RED
Unit shuts down during operation.
Check LED’s / Screen for alarms.
Clear alarm and remove household loads from generator. Put back in AUTO and restart.
RPM SENSE LOSS RED
Unit was running and shuts down, attempts to
restart.
Check LED’s / Screen for alarms.
Clear alarm and remove household loads from generator. Put back in AUTO and restart. If generator does not start, contact an IASD.
NOT ACTIVATED
NONE
Unit will not start in AUTO with utility loss.
Verify if screen says unit not activated.
See Activation section in owner’s manual.
NONE
GREEN
Unit will not start in AUTO with utility loss.
Check screen for start delay countdown.
If startup delay is greater than expected, contact an IASD to adjust between 2 to 1500 seconds.
LOW OIL PRESSURE
RED
Unit will not start in Check LED’s / Screen Check oil level and add oil as needed. If oil
AUTO with utility loss.
for alarms.
level is correct, contact an IASD.
RPM SENSE LOSS RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Clear alarm. Using control panel, check battery by navigating to BATTERY MENU option from MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace battery.
OVERCRANK
RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Verify fuel shutoff valve is ON. Clear alarm. Start unit in MANUAL. If it does not start, or starts and runs rough, contact an IASD.
LOW VOLTS REMOVE LOAD
RED
Unit will not start in Check LED’s / Screen Clear alarm and remove household loads
AUTO with utility loss.
for alarms.
from generator. Put into AUTO and restart.
OVERSPEED
RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Contact an IASD.
UNDERVOLTAGE
RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Contact an IASD.
UNDERSPEED
RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Contact an IASD.
STEPPER OVERCURRENT
RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Contact an IASD.
MISWIRE
RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Contact an IASD.
Installation Guidelines For 60 Hz EcoGenTM Generators
45
Quick Reference Guide
Active Alarm LED
Problem
Things to Check
Solution
OVERVOLTAGE
RED
Unit will not start in AUTO with utility loss.
Check LED’s / Screen for alarms.
Contact an IASD.
AUXILIARY SHUTDOWN
RED
Unit will not start.
Check auxiliary Set auxiliary shutdown switch(es) to shutdown switch(es). CLOSED (I).
LOW BATTERY
YELLOW
Yellow LED illuminated in any state.
Clear alarm. Using control panel, check battery by navigating to BATTERY MENU Check screen for option from MAIN MENU. If battery additional information. condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace battery.
BATTERY PROBLEM
YELLOW
Yellow LED illuminated in any state.
Check screen for additional information.
Contact an IASD.
CHARGER WARNING
YELLOW
Yellow LED illuminated in any state.
Check screen for additional information.
Contact an IASD.
CHARGER MISSING AC
YELLOW
Yellow LED illuminated in any state.
Check screen for additional information.
Contact an IASD.
SERVICE A
YELLOW
Yellow LED illuminated in any state.
Check screen for Perform SERVICE A maintenance. Press additional information. ENTER to clear.
SERVICE B
YELLOW
Yellow LED illuminated in any state.
Check screen for Perform SERVICE B maintenance. Press additional information. ENTER to clear.
INSPECT BATTERY
YELLOW
Yellow LED illuminated in any state.
Check screen for additional information.
Inspect battery. Press ENTER to clear.
46
Installation Guidelines For 60 Hz EcoGenTM Generators
Section 10: Accessories
Accessories
Performance enhancing accessories are available for air-cooled generators.
Accessory Cold Weather Accessories–
· Battery Pad Warmer · Oil Warmer · Breather Warmer each sold separately
Scheduled Maintenance Kit
Fascia Base Wrap
Touch-Up Paint Kit
Wi-Fi LP Fuel Level Monitor
Description
· Recommended in areas where temperatures fall below 0 °F (-18 °C). (Not
necessary for use with AGM-style batteries)
· Recommended in areas where temperatures fall below 0 °F (-18 °C). ·
Recommended in areas where heavy icing occurs.
Includes all pieces necessary to perform maintenance on the generator along
with oil recommendations.
The fascia base wrap snaps together around the bottom of the new air-cooled
generators. This offers a sleek, contoured appearance as well as offering
protection from rodents and insects by covering the lifting holes located in
the base. Requires use of the mounting pad shipped with the generator.
Very important to maintain the look and integrity of the generator enclosure.
This kit includes touch-up paint and instructions.
The Wi-Fi enabled LP fuel level monitor provides constant monitoring of the
connected LP fuel tank. Monitoring the LP tank’s level is an important step in
making sure your generator is ready to run during an unexpected power failure.
Status alerts are available through the Mobile Link application informing you
when your LP tank needs a refill.
NOTE: Contact an IASD or visit www.generac.com for additional information on accessories and extended warranties.
Installation Guidelines For 60 Hz EcoGenTM Generators
47
Accessories
This page intentionally left blank.
48
Installation Guidelines For 60 Hz EcoGenTM Generators
Section 11: Diagrams
Installation Drawing (10000037315 rev A–1 of 2)
Diagrams
MOUNTING TO CONCRETE PAD
HOLE LOCATIONS FOR OPTIONAL MOUNTING TO
A CONCRETE PAD
16 [5/8] DIA. CLEARANCE HOLE (3) PLACES,
10 [3/8] DIA. MASONRY ANCHOR BOLTS RECOMMENDED
FRONT OF UNIT
19.7 [7.7] 457 [18.0]
393 [15.5]
521 [20.5] 68 [2.7]
( ) MAIN AC/CONTROL WIRING HOLE FOR 1 1/4″ CONDUIT MAIN AC/CONTROL WIRING HOLE FOR 3/4″ CONDUIT
-REMOVE FACTORY PLUGS AND DISCARD -CLOSE ANY UNUSED HOLE WITH A NEMA 3R RATED PLUG (FIELD SUPPLIED)
AUXILIARY SHUTDOWN SWITCH
WIRELESS MODULE
FUEL INLET : 1/2″ NPT REQUIRED FUEL PRESSURE : NATURAL GAS : 3.5-7″ WATER
COLUMN
LIQUID PROPANE (VAPOR) : 10-12″ WATER COLUMN
635 [25.0]
345 [13.6] 218 [8.6]
REAR VIEW
Installation Guidelines For 60 Hz EcoGenTM Generators
733 [28.8] 648 [25.5] LEFT SIDE VIEW
49
Diagrams Installation Drawing (10000037315 rev B–2 of 2)
914 [36.0] MINIMUM OPEN AREA
AIR INTAKE
457 [18.0] MINIMUM OPEN AREA
AIR OUTLET
“DO NOT LIFT BY ROOF”
TOP VIEW
914 [36.0] MINIMUM OPEN AREA
AIR INTAKE
914 [36.0] MINIMUM OPEN AREA
LIFTING HOLES 4 CORNERS: 30 [ 1.2] – MUST BE LIFTED WITH STEEL RODS – RECOMMENDED LIFTING ROD SIZE: 25 [ 1.0] 1218 [48.0]
RIGHT VIEW INTAKE PANEL REMOVED
127 [5.0] GRAVEL PAD/ COMPACTED SOIL
50
1232 [48.5] FRONT VIEW
RIGHT SIDE VIEW
TITLE
INSTALL HSB GENERATOR ECOGEN WM
Installation Guidelines For 60 Hz EcoGenTM Generators
51
Installation Guidelines For 60 Hz EcoGenTM Generators
120V/240V CHARGER
SUPPLY
ECOGEN – TYPICAL OFF-GRID APPLICATION SYSTEM DIAGRAM
TWO-WIRE START
ENGINE CONTROLLER
GENERATOR
12 VOLT ENGINE START BATTERY
ENGINE START BATTERY CHARGER
TWO-WIRE START
120/240V OUTPUT
ALTERNATOR
HOUSE LOADS*
AC DISTRIBUTION
PANEL 120/240V
INVERTER
TWO-WIRE START
BATTERY VOLTAGE SENSING
BATTERY CHARGER
INVERTER/CHARGER
HOUSE LOADS*
DC DISTRIBUTION
PANEL 12V/24V/48V
BATTERY 12V/24V/48V
*House Loads must be less than 10 kW or 2 hp
HOUSE
PHOTO VOLTAIC PANEL
24/48V DC
12/24/36/48V DC
WIND TURBINE
008705
Off-Grid Mode Application Schematic
Diagrams
Installation Guidelines For 60 Hz EcoGenTM Generators
52
VENT HOSE
OIL MAKE UP SYSTEM SCHEMATIC
(NOT TO SCALE)
OIL DIPSTICK AND FILL
ENGINE-IN HOSE (TO OIL PUMP)
ENGINE-OUT HOSE
008706
Diagrams
Oil Make Up System Schematic
Diagrams
This page intentionally left blank.
Installation Guidelines For 60 Hz EcoGenTM Generators
53
Diagrams
This page intentionally left blank.
54
Installation Guidelines For 60 Hz EcoGenTM Generators
Part No. 10000032205 Rev. B 12/17/2018 ©2018 Generac Power Systems, Inc. All rights reserved Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc.
Generac Power Systems, Inc. S45 W29290 Hwy. 59 Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
www.generac.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>