universal douglays WIR-3110 DIALOG IR Setting Unit User Manual
- October 27, 2023
- universal douglays
Table of Contents
WIR-3110
Description & Function
Liquid Crystal Display Panel (LCD)
-
Device Name
The device that you are programming. Available devices are: 1-4 Button Switch, 8 Button Switch, Dimmer Switch, 8-Contact Input, Key Switch, PIR Occupancy Sensor and Photo Sensor. -
Delay ON Time
Number of seconds an ON command is delayed after being activated. Minimum 0 Seconds – Maximum 40 minutes.
When ‘Occupancy PIR’ is the device selected, this field will indicate the level of sensitivity to apply (from 0-10). -
Delay OFF Time
Number of seconds an OFF command is delayed after being activated. Minimum 0 Seconds – Maximum 40 minutes. -
Occupancy
Indicates whether occupancy sensor connected will use default manufacturer settings for time delay (NO) or time delay as set by the IR Setting Unit (YES) for 8-Contact Input Unit only. -
Action
The action to be performed by the IR Setting Unit. READ (Reads current settings from a particular device), WRITE (Writes the current settings on the LCD screen to a particular device), CLEAR (Clears all settings associated with a device), OFF (Turns the IR Setting Unit Off). -
Function of Selected Device
Sets a switch’s function. Options are: ON only, OFF only, Toggle (ON and OFF), Dim Up, Dim Down. Sets the Contact Input Units function to correspond to the Contact-type that is connected to its terminals. -
Channel Number
Output channel to be programmed. -
Address
Sets the Address for the device being programmed. -
Input Type
Input to target: Individual, Group, Local Preset, Global Preset, Indiviual Dim, Group Dim. -
Input Component Number
The input component of a device being programmed (multiple button switch or 8-Contact Input Unit). -
Cursor
Indicates a selected item.
Setting a Switch
Setting a Switch
Step 1 – Switch Configuration
Using the UP/DOWN buttons, move the cursor until it highlights the ‘#-Button
Switch’ field.
Select the switch configuration that matches the switch that you are
programming by rotating the scroll wheel clockwise or counterclockwise.
*Instructions apply for a Key Switch as well Step 2 – Input Type
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Type’
field. Select the switch input type to apply to the switch that you are
programming by rotating the scroll wheel clockwise or counterclockwise. Step
3 – Assigning an Address
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Addr’
field. Select the address you wish to assign the switch by rotating the scroll
wheel clockwise or counterclockwise. Step 4 – Assigning an
Output Channel
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Addr’
field. Select the address you wish to assign the switch by rotating the scroll
wheel clockwise or counterclockwise. Step 5 – Assigning a Function
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Fn’ field.
Select the function you wish to assign the switch by rotating the scroll wheel
clockwise or counterclockwise. Step 6 – Delay ON
Using the UP/DOWN buttons, move the cursor until it highlights the ‘On’ field.
Select the amount of time you wish to delay an ON command after it is
initiated. The time can be adjusted from 0 seconds to 40 minutes by rotating
the scroll wheel clockwise. Step 7 – Delay OFF
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Off’
field. Select the amount of time you wish to delay an OFF command after it is
initiated. The time
can be adjusted from 0 seconds to 40 minutes by rotating the scroll wheel
clockwise or counterclockwise. Step 8 – Writing Programming to a Switch
Using the UP/DOWN buttons, move the cursor until it highlights the bottom
right field.
Rotate the center scroll wheel until ‘Write’ is highlighted. Point the
Infrared transmitter approximately 0.5”away from the IR lens of the switch
being programmed and press the center button of the IR Setting Unit. You will
hear a single solid beep sound indicating that the switch was successfully
programmed.
Setting a Dimmer Switch
Step 1 – Switch Configuration
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Dimmer
Switch’ field.
Step 2 – Dimming Type
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Type’
field. Select the dimming type (Dim an individual output channel or Dim a
group) to apply to the switch that you are programming by rotating the scroll
wheel clockwise or counterclockwise. Step 3 – Assigning an
Address
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Addr’
field. Select the address you wish to assign the switch by rotating the scroll
wheel clockwise or counterclockwise.
Step 4 – Assigning an Output Channel
*Applicable only when programming an individual dimmer Using the UP/DOWN buttons, move the cursor until it highlights the ‘Ch’ field. Select the output channel you wish to assign the switch by rotating the scroll wheel clockwise or counterclockwise. Step 5 – Writing Programming to a Switch
Using the UP/DOWN buttons, move the cursor until it highlights the bottom
right field.
Rotate the center scroll wheel until ‘Write’ is highlighted. Point the
Infrared transmitter approximately 0.5” away from the IR lens of the switch
being programmed and press the center button of the IR Setting Unit. You will
hear a single solid beep sound indicating that the switch was successfully
programmed.
Setting a 8-Contact Input Unit
Step 1 – Selecting a 8-Contact Input Unit
Using the UP/DOWN buttons, move the cursor until it highlights the ‘8-Contact
Input’ field.
Select the 8-Contact Input Unit from the list of options by rotating the
scroll wheel clockwise or counterclockwise.
Step 2 – Input Type
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Type’
field. Select the input type to apply to the Contact Input Unit that you are
programming by rotating the scroll wheel clockwise or
counterclockwise. Step 3 – Assigning an Address
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Addr’
field. Select the address you wish to assign the Contact Input Unit by
rotating the scroll wheel clockwise or counterclockwise. Step 4 – Assigning an Output Channel
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Ch’ field.
Select the output channel you wish to assign the Contact Input Unit by
rotating the scroll wheel clockwise or counterclockwise. Step 5 – Assigning a Function
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Fn’ field.
Select the function you wish to assign the Contact Input Unit by rotating the
scroll wheel clockwise or counterclockwise.
Available functions are:
Step 6 – Delay ON
*If you are connecting an Occupancy Sensor By Others and wish to use the built in delay time, adjust the time directly on the sensor according to the manufacturers specifications and set the delay ON and OFF fields of the WIR-3110 to 0 Using the UP/DOWN buttons, move the cursor until it highlights the ‘On’ field. Select the amount of time you wish to delay an ON command after it is initiated. The time can be adjusted from 0 seconds to 40 minutes by rotating the scroll wheel clockwise or counterclockwise.
Step 7 – Input Type
*If you are connecting an Occupancy Sensor By Others and wish to use the built in delay time, adjust the time directly on the sensor according to the manufacturers specifications and set the delay ON and OFF fields of the WIR-3110 to 0 Using the UP/DOWN buttons, move the cursor until it highlights the ‘Off’ field.
Select the amount of time you wish to delay an OFF command after it is
initiated. The time can be adjusted from 0 seconds to 40 minutes by rotating
the scroll wheel clockwise or counterclockwise. Step 8 –
Assigning an Address
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Occ’
field. Select either ON or OFF.
- select ON if you wish to use the delay settings on the IR Setting Unit. Ensure that the adjustable delay time directly on the sensor is set to the lowest setting possible.
- select OFF if you wish to use the delay settings provided by the manufacturer directly on the sensor. Using the UP/DOWN buttons, move the cursor until it highlights the ‘Occ’ field. Select either ON or OFF.
Step 9 – Assigning an Output
Channel
Using the UP/DOWN buttons, move the cursor until it highlights the bottom
right field.
Rotate the center scroll wheel until ‘Write’ is highlighted. Point the
Infrared transmitter approximately 0.5” away from the IR lens of the switch
being programmed and press the center button of the IR Setting Unit. You will
hear a single solid beep sound indicating that the switch was successfully
programmed.
Setting a Occupancy Sensor
Step 1 – Delay ON
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Occupancy
PIR’ field.
Step 2 – Input Type
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Type’
field. Select the input type (Individual, Group, Preset Local, Preset Global)
to apply to the sensor that you are programming by rotating the scroll wheel
clockwise or counterclockwise.
Step 3 – Assigning an Address
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Addr’
field. Select the address you wish to assign the sensor by rotating the scroll
wheel clockwise or counterclockwise. Step 4 – Assigning an
Output Channel
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Ch’ field.
Select the output channel you wish to assign the Occupancy Sensor by rotating
the scroll wheel clockwise or counterclockwise. Step 5 – Input
Type
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Sens’
field. Select the level of sensitivity (1 – 10) you wish to apply to the
Occupancy Sensor being programmed. A level of ‘1’ being the least amount of
sensitivity and a level of ‘10’ being the greatest. Step 6 – Assigning an Address
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Off’
field. Select the amount of time you wish to delay an OFF command after it is
initiated. The time
can be adjusted from 0 seconds to 40 minutes by rotating the scroll wheel
clockwise or counterclockwise.
Step 7 – Assigning an Output
Channel
Using the UP/DOWN buttons, move the cursor until it highlights the bottom
right field.
Rotate the center scroll wheel until ‘Write’ is highlighted. Point the
Infrared transmitter approximately 0.5” away from the IR lens of the sensor
being programmed and press the center button of the IR Setting Unit. You will
hear a single solid beep sound indicating that the sensor was successfully
programmed.
Setting a Photo Sensor
Step 1 – Photo Sensor Selection
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Photo
Sensor’ field.
Step 2 – Photo Type
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Type’
field. Select the input type (Local Photo and Global Photo) to apply to the
sensor that you are programming by rotating the scroll wheel clockwise or
counterclockwise. Step 3 – Assigning an Address
Using the UP/DOWN buttons, move the cursor until it highlights the ‘Addr’
field. Select the address you wish to assign the sensor by rotating the scroll
wheel clockwise or counterclockwise. Step 4 – Writing
Programming to a Photo Sensor
Using the UP/DOWN buttons, move the cursor until it highlights the bottom
right field.
Rotate the center scroll wheel until ‘Write’ is highlighted. Point the
Infrared transmitter approximately 0.5” away from the IR lens of the sensor
being programmed and press the center button of the IR Setting Unit. You will
hear a single solid beep sound indicating that the switch was successfully
programmed.
Notes
Learn More at www.universaldouglas.com
It’s EASY to REACH US…..
universaldouglas.com
UniversalDouglasSupport
Douglas Lighting Controls
(877) 873-2797
techsupport@universaldouglas.com
Universal Lighting Technologies
(800) 225-5278
tes@universaldouglas.com
universaldouglas.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>