LED T5 Tube and Driver Retrofit
Instruction Manual
SAFETY WARNINGS
IMPORTANT SAFETY INFORMATION
DANGER
Risk of shock. Disconnect power before installation.
DANGER- RISQUE DE CHOC- COUPER L’ALIMENTATION AVANT L’INSTALLATION
WARNING
Risk of fire or electric shock. LED Retrofit Kit installation requires
knowledge of luminaires electrical systems. If not qualified, do not attempt
installation. Product must be installed in accordance with NEC or your local
electrical code. If you are not familiar with these codes and requirements,
contact a qualified electrician.
WARNING
Risk of fire or electric shock. To prevent wiring damage or abrasion, do
not expose wires to the edge of sheet metal or any other sharp objects.
WARNING
Risk of fire or electric shock. Check the existing wiring for damage before
Installing upgrade kit. Do not install if existing wires are damaged.
WARNING
Risk of fire or electric shock. Luminaire wiring and electrical parts may be
damaged when drilling for installation of the LED upgrade kit. Check for
enclosed wiring and components.
SUITABLE FOR DRY LOCATIONS.
NOT FOR USE WITH PHASE CUT DIMMERS.
CONVIENT AUX EMPLACEMENTS HUMIDES.
WARNING
Risk of fire or electric shock. Install this kit only in luminaires that
have the construction features and dimensions shown in the photographs and/or
drawings.
Only the holes indicated in the photographs or drawings may be made or altered
as a result of the kit installation. Do not leave any other holes open in a
wiring enclosure or electrical component.
NOTE
THE RETROFIT KIT IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE
SUITABILITY OF THE COMBINATION SHALL BE DETERMINED AUTHORITIES HAVING
JURISDICTION.
LED Driver Compatibility Requirements
Qty of
Lamps| Kit Part Number
1800 Lumens/Lamp| Driver Rating| Input
Voltage| Drivers Catalog#
---|---|---|---|---
Current| Voltage
1| LR14T5-18L8xx-DU| 260mA| 46V| 120-277V| D70C2OUNVPW-C
LR141.5-18L8xx-DU-XCT| D70C2OUNVPWX12-C
2| LR241-5-36L8xx-DU| 520mA| D1OCC3OUNVPW-C
LR241.5-36L8xx-DU-XCT| D1OCC3OUNVPWX12-C
3| LR341-5-54L8xx-DU| 780mA| D15CCS5UNVPW-C
LR34T5-54L835-DU-XCT| D15CC55UNVPWX12-C
4| LR44.15-72L8xx-DU| 1040mA| D15CCS5UNVPW-C
LR44T5-72L835-DU-XCT| D15CC5SUNVPWX12-C
Bluetooth Control:
Included with models having the XCT suffix
Catalog #: BT-LRT-B
Qty of
Lamps| Kit Part Number
3400 Lumens/Lamp| Driver Rating| Input
Voltage| Drivers Catalog#
---|---|---|---|---
Current| Voltage
1| LR14TSH-34L8xx-DU| 480mA| 46V| 120-277V| D1OCC3OUNVPW-C
LR14TSH-34L8xx-DU-XCT| D1OCC3OUNVPWX12-C
2| LR24T5H-68L8xx-DU| 960mA| D15CCSSUNVPW-C
LR24T5H-68L8xx-DU-XCT| D15CC55UNVPWX12-C
3| LR34T5H-10K8xx-DU| 1440mA| D21CC8OUNVPW-C
LR34T5H-10K8xx-DU-XCT| D21CC8OUNVPWX12-D
xx: 35/3500K, 40/4000K, 50/5000K
Module (Lamp) p/n: LR4FT5M32L/8xxA
LED Retrofit Kit Model Number | Retrofitted Fluorescent Luminaire Type(s) |
---|---|
LR14T5H-32Lxyy-DDU | • 3 lamp linear fluorescent, lensed, recessed strip |
channel luminaires, Type IC, 31°C max ambient, overall external dimensions of
47.5 by 5.875 by 3.75 inches and internal wiring compartment dimensions
overall 5.5 by 1.0 by 46.5 inches
LR24T5H-64Lxyy-DDU
LR14T5-18Lxyy-DU| • Single lamp non-lensed strip light with minimum wiring
compartment dimensions of 2-1/8 by 1-1/2 by 48 inches, suitable for damp
locations, maximum 40°C ambient rating.
LR14T5-18Lxyy-DU-XCT
LR14T5H-34Lxyy-DU
LR14T5H-34Lxyy-DU-XCT
LR24T5-36Lxyy-DU LR24T5-36Lxyy-DU-XCT LR24T5H-68Lxyy-DU LR24T5H-68Lxyy-DU-XCT
All combinations of two one-lamp kits| • Dual lamp non-lensed strip light with
minimum wiring compartment dimensions of 2-1/8 by 1-1/2 by 48 inches, suitable
for damp locations, maximum 40°C ambient rating.
• Dual lamp lensed vaportight fixture with minimum dimensions of 4-1/2 by
6-1/2 by 49-5/8 inches, suitable for damp locations, maximum 40°C ambient
rating.
LR34T5-54Lxyy-DU LR34T5-54Lxyy-DU-XCT LR34T5H-10Kxyy-DU LR34T5H-10Kxyy-DU-XCT
__| • 3 lamp linear fluorescent, lensed, recessed strip channel luminaires,
Type IC, 35°C max ambient, overall external dimensions of 47.5 by 5.875 by
3.75 inches and internal wiring compartment dimensions overall 5.5 by 1.0 by
46.5 inches
• 3 lamp louvred or non-louvred linear fluorescent high bay fixture with
minimum wiring compartment dimensions of 46-1/8 by 23/8 by 1-7/8 inches,
suitable for damp locations, maximum 40°C ambient rating.
LR44T5-72Lxyy-DU LR44T5-72Lxyy-DU-XCT| • 4 lamp non-lensed linear fluorescent
high bay fixture with minimum wiring compartment dimensions of 47-3/4 by
2-3/16 by 1- 5/8 inches, suitable for damp locations, maximum 40°C ambient
rating.
One and two lamp kit combinations| • 3 lamp linear fluorescent, lensed,
recessed strip channel luminaires, Type IC, 35°C max ambient, overall external
dimensions of 47.5 by 5.875 by 3.75 inches and internal wiring compartment
dimensions overall 5.5 by 1.0 by 46.5 inches
• 3 lamp louvred or non-louvred linear fluorescent high bay fixture with
minimum wiring compartment dimensions of 46-1/8 by 23/8 by 1-7/8 inches,
suitable for damp locations, maximum 40°C ambient rating.
Dual 3 lamp kits
All 2 and 4 lamp kit combinations| • 6 lamp non-lensed and non-louvred linear
fluorescent high bay fixture with minimum wiring compartment dimensions of
46-1/8 by 2-3/8 by 1-7/8 inches, suitable for damp locations, maximum 40°C
ambient rating.
| • 6 lamp lensed linear fluorescent vaportight fixture with overall
dimensions of 52 by 6 by 14-5/8 inches, suitable for wet locations, maximum
40°C ambient rating.
INSTALLATION
STEP 1: Disconnect Power to the fixture
STEP 2: Remove existing lamps, ballast cover plate, and ballast. Leave
existing wire in place and as long as possible .Replace lamp holders if
necessary.
STEP 3: Verify that the luminaire is connected to the ground wire from the AC
supply.
STEP 4: Secure the driver into the fixture. Use a self-tapping screw (not
provided) if necessary.
STEP 5: Connect existing leads to the driver as shown. The lamps are connected
and operated in parallel for both ends of the lamps. Wires should be 18AWG
solid conductor with ¼” strip length.
STEP 6: Connect the BT-LRT-B controller and mount it adjacent to the LED
tubes, outside of the ballast wiring channel in recessed troffers (where
applicable).
STEP 7: Insert the line and neutral wires into their connectors.
STEP 8: Replace the ballast cover plate, take care not to pinch wires.
STEP 9: Insert the lamps with the label side facing the back of the fixture.
STEP 10: Place relamp label at a visible location in the fixture. Close or
replace lens and secure latches or other fastening means.
STEP 11: Restore power and confirm lamps are operating properly.
BT-LRT-B INSTALLATION (where applicable)
The sensor has a magnet which allows for it to be mounted to the metal tray or panel of the luminaire. The BTLRT-B should not be mounted within the ballast channel where it is completely enclosed in metal. The leads of the BT-LRT-B are to be connected to the driver as shown in the wiring diagram.
For installation outside of the wiring channel of the fixture the leads should be routed away from the input power leads and not come in contact with the power leads. Leads should exit the end of the channel and the sensor be placed between lamps.
CONNECTION DIAGRAMS
Models without Controls have Violet and Gray leads for 0-10V dimming and do not have aux power.