NELSEN 400 Non-Electric Dry Chlorine Pellet Feeder Instruction Manual
- October 27, 2023
- NELSEN
Table of Contents
- NELSEN 400 Non-Electric Dry Chlorine Pellet Feeder
- Installation & Operation Information
- Theory of Operation
- Calculating Chlorine Concentration Per Pump Cycle
- Refilling Information & Part Identification
- Model 400 Feeder – Trouble Shooting
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
NELSEN 400 Non-Electric Dry Chlorine Pellet Feeder
THE MANUFACTURER EXPRESSLY DISCLAIMS AND SHALL HAVE NO LIABILITY WHATSOEVER IN EXCESS OF THE PURCHASE PRICE OF THE MODEL 400 FEEDER FOR ANY LOSS, DAMAGE OR INJURY TO PERSON OR PROPERTY, INCLUDING ANY SUCH LOSS, DAMAGE OR INJURY ATTRIBUTABLE TO MANUFACTURER’S NEGLIGENCE OR FAULT AND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, from (a) the design, manufacture, sale, delivery, installation, repair, operation or use of the Model 400 feeder or any part thereof, (b) any actual or alleged failure or defect in the Model 400 feeder or any part thereof, or (c) any actual or alleged breach or non- performance by the manufacturer. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
Installation & Operation Information
The Model 400 feeder will operate on a varying pressure such as a home well
system or on a constant pressure such as a sprinkler or pool system.
When used as a varying pressure system the non-functioning valve (No. 11) must
be in place as received. A charcoal filter must follow the Model 400 feeder on
a varying pressure system for proper operation. Tests have shown that one cube
of coconut shell activated carbon is the best carbon to use (grade 9/50, mesh·
8/30).
There are seven positions for varying the amount of chemical feed. Rotate the
top cap (No. 7) so there is a hole showing through the level desired. There
are two hole selections for each hole in the cap (No. 7).
The smaller hole will dispense the greatest amount and selecting a lower hole
on the cap will increase the output.
Approximate chlorine readings using a 42 gallon pressure tank out of the Model
400 feeder ·per pump cycle in PPM, for each hole are; 1=2, A=3.5, 2=:=8, B=l3,
3=30,C=40 and with no holes showing, the off position is 60 plus.
These readings are obtained with no iron or hydrogen sulfide using the chlorine. Variables that will change the dilution are: pressure tank size, large volumes of water flow while the pump is building pressure to shut off, horse power of the pump, and a water logged pressure tank or air pressure is low or high in the air bag. The Model 400 feeder will dispense the same amount of chemical for each cycle of the pump from maximum to minimum pressure.
When used on a constant-pressure and flow it is necessary to replace the valve (No.11). Replace it with the optional adjustable valve (No. 20). It may be necessary to install the optional screen filters (No. 19) in the top inside hole of (No. 8) and screen (No. 18) in the adjustable inlet hole when using chemicals other than chlorine, When using the unit for constant pressure and flow such as a sprinkler system or pool; install the unit on the output to the sprinkler heads or on the return line to the pool. The adjustments for the constant pressure system should have no holes shown through in the off position. The amount of chemical dispensed is controlled with the adjustable rate of feed valve on the outside of the unit. It may be necessary to adjust the unit if flow is increased or decreased.
(Actual size of the Model 400 Feeder – 10.5” high X 11.5” long) (Empty weight
– 6.5 lbs.)
MAXIMUM TESTED PRESSURE IS 80 LBS.
U.S. PATENT NOS. 5,053,206; 4,908,190;
4,548,228; 4,407,322
WARNING: Use Only Calcium Hypochlorite Chlorine Tablets For Potable Water.
NOTE : Install a Check Valve After the Pressure Tank For Heavy Use of an Irrigation Valve.
DANGER: Do Not Mix Different Types or Brands of Chlorine, an Explosion Can Occur.
Theory of Operation
After filling the unit with chemical to no higher than the bottom of the
adjustable cap or less and returning water flow, fluid will flow into the
chemical container mixing with the chemical until the air trapped in the top
of the unit is compressed to the same pressure as the line pressure.
When the line pressure is reduced, compressed air in the air chamber will
force fluid from the container down and up through the outside center tube and
down the inside tube to the water line until pressure is equal or until the
fluid level reaches the hole that is open in the outside tube. At that time
the compressed air will flow through the hole into the outside tube, down the
inside tube and no more fluid will flow. This procedure will occur on each
pump cycle. The outside tube has six (6) holes with three of them smaller. The
cap can be rotated to select either a large hole or a small hole in six
different locations. During fluid flow a small amount of fluid will flow
through the hole selected thereby diluting the fluid flowing up through the
outside tube. Most chemical solutions are heavier than water and the top of
the fluid is not as heavily saturated as the bottom of the container.
Selecting a small hole will increase the chemical concentration and selecting
a lower hole increases the solution output.
The unit can be used as a venturi operation for operations other than varying pressure. In this mode the cap maybe rotated so there is no hole through the outside tube or left with the hole through the outside tube to help dilute the fluid if needed. The chemical solution out is controlled with the optional rate of feed valve in a constant pressure system.
Approximate Chlorine Concentration Per Pump Cycle
To oxidize one PPM of Hydrogen Sulfide (H2S), it takes 2.2
PPM of Chlorine (Cl2). To oxidize 1 PPM of Iron (Fe) it takes .64 PPM of Cl2
Example: If you have 4 PPM of Fe and 1 PPM of H2S, look on the vertical
portion of the graph labeled PPM and start at 4 and move horizontal to the
line marked Iron – Fe X . 64 Cl2 and then down to the bottom of the graph
marked Chlorine – Cl2 PPM.
It should intercept the bottom about 2. 6. This is the amount of Cl2 needed to
oxidize 4 PPM of Fe. Now look on the vertical portion of the graph labeled PPM
and start at 1 and move horizontal to the line marked Hydrogen Sulfide – H2S X
2.2 Cl2 and then down to the bottom of the graph.
It should intercept the bottom about 2.2. This is the amount of Cl2 needed to
oxidize 1 PPM of H2S.
Example in dotted lines:
4 PPM Fe requires 2.6 PPM of Cl2
1 PPM H2S requires 2.2 PPM of Cl2
Total Cl2 required is 2.6 plus 2.2 = 4.8 PPM Cl2
If using a 42 gallon pressure tank, the No. 2 hole on the Model 400 feeder should be used. This will dispense about 8 PPM of Cl2 and a filter with one cube of activated carbon after the unit will eliminate the excess Cl2. If using the Model 400 feeder for iron removal or extremely high H2S, it is necessary to use a back washing valve on the carbon filter.
Higher PPM than the graph can be calculated.
Example:
20 PPM H2S X 2.2 Cl2 = 44 PPM of Cl2
20 PPM Fe X .64 C~ = 12.8 PPM of Cl2
The Model 400 feeder will hold about 4 pounds of Cl2 (10 gram tablets). If it
is adjusted to the No. 1 hole, and using a 42 gallon pressure tank with one
cube of activated carbon the system should process approximately 20,000
gallons of water before the unit would need refilling.
Calculating Chlorine Concentration Per Pump Cycle
Approximate Model 400 Feeder Cl2 Concentration Per Pump Cycle for a 42 Gallon Pressure Tank.
If Using an 82 Gallon Pressure Tank Divide the PPM By 2
If Using a 20 Gallon Pressure Tank Multiply the PPM By 2
- = 2 PPM A = 3.5 PPM
- = 8 PPM B = 13 PPM
- = 30 PPM C = 40 PPM
OFF = 60+ PPM
Chlorine Setting in PPM for Center Tube & Cap
Hole Settings in Parts Per Million
HOLE # 1 = 2 PPM
HOLE # A = 3 .5 PPM
HOLE # 2 = 8 PPM
HOLE # B = 13 PPM
HOLE # 3 = 30 PPM
HOLE # C = 40 PPM
All Holes Closed Will Deliver
60 PPM Per Pump Cycle.
This chart is for a 42 gallon or equivalent pressure tank.
When using an 80 gallon pressure tank, the PPM amount will be 50% less per
pump cycle. A 20 gallon pressure tank will yield 2 times the amount.
Each number or letter will show a different hole in the cap.
Line up the 3 holes in the cap with the proper number or letter directly under
it (as per figure 1). The hole in the tube should show in the center of the
hole in the cap.
CAUTION: UNIT MUST BE INSTALLED AFTER THE PRESSURE TANK
U.S. PATENT NOS.
5,053,206; 4,908,190;
4,548,228; 4,407,322
Center Tube Must be Removed and Cleaned Each Time Before Refilling. (See
filling information #3)
When removing center tube for cleaning, check hole setting in cap.
After cleaning, be sure the setting is the same before replacing cap.
Install PVC Check Valve Before Feeder if Untreated
Water is Used Before Feeder.
Refilling Information & Part Identification
-
Shut off water ahead of unit.
-
Open drain valve after FEEDER and relieve line pressure
-
Unscrew top (No. 4) and remove adjustment tube (No. 8) to DRAIN UNIT and replace with a clean tube and cap (No. 7). To clean the removed tube & cap. Soak in a mixture of Muriatic Acid. One part Muriatic Acid to five parts water. Always pour the acid into the water.
ADHERE TO THE WARNINGS FOR HANDLING AND USE OF MURIATIC ACID. Tube & Cap can also be cleaned by soaking in white vinegar over night or longer. -
If unit needs cleaning, loosen nuts (No. 14), turn unit upside down and flush with water.
-
Fill with chlorine tablets to the bottom of cap (No. 7).
Do not till above bottom of cap (No. 7) and do not add water to the unit or operation will be inhibited. It may take a few pump cycles before chlorine is dispensed. -
Replace top (No. 4) and close drain valve.
-
Tum on water.
NOTES: If unit is opened after pressurization, it is necessary to drain fluid to the bottom of cap (No. 7) before repressurizing, or operation will be inhibited. If unit is used for odor removal, do not refill until odor returns to minimize chemical use.
DANGER: DO NOT MIX DIFFERENT TYPES OR BRANDS OF CHLORINE AN EXPLOSION CAN
OCCUR CHLORINE is highly corrosive. Causes skin and eye damage.
May be fatal if swallowed and irritating to nose and throat. Wear goggles or
face shield and rubber gloves when handling or opening the Model 400 feeder.
Avoid breathing dust. Remove and wash contaminated clothing and shoes before
reuse.
CAUTION: USE ONLY CALCIUM HYPOCHLORlTE CHLORINE TABLETS FOR POTABLE WATER
Model 400 Feeder – Trouble Shooting
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>