niko 41750 Presence Detector Instruction Manual

June 6, 2024
niko

niko 41750 Presence Detector

Safety notes

Ensure that the electrical lines are de-energized before installation. Installation is only permitted by electricians in compliance with local legislation.

Installation Placement

niko 41750 Presence Detector
1

niko 41750 Presence Detector 3

The detector responds to movements and heat in its environment. Avoid an installation in close proximity to stoves, electrical heaters, fans or other moveable objects as they may trigger an unintended activation (2). The presence detector is designed for ceiling mounting.

Range

To reduce the detection area the enclosed half-shells can be clamped between lens and cover. The detector’s recommended mounting height is 2 to 3,5 m (1). The range of the presence detector may be increased with up to 10 secondary presence detectors edition UP Art. No 41752 or edition AP Art. No 41753. Ensure an approximate 30% overlap of the detection areas for disruption-free detection when using several detectors.

Wiring

Wire the presence detector according to the wiring diagram (5). All DALI devices are wired in parallel. The Master device automatically recognises connected DALI devices. Do not connect additional DALI power supplies nor multiple Master devices as it would damage the DALI coils as well as the presence detectors.

The presence detector contains an in-built DALI power supply. Do not connect an external DALI power supply.

Setup mode Out of the box

Connect the presence detector to mains voltage only after the installation is completely wired. Respect an approx. 40 s warm-up delay after mains connection for the detector be operational. The DALI ballasts willl be automatically recognised by the presence detector. As soon as the detector is connected to mains voltage, all connected lights switch on and the presence detector works in On/Off mode. The delay time is set to 15 min. All zones may be switched on and off via the connected 230 V push-buttons or via the P-IR remote control. All 230 V push-buttons will have the same functionality.
Note: All LEDs (red, blue, yellow, green) flash alternately, showing that the presence detector is in «Out-of-the-box» mode.
Commissioning and programming are described in the operating instructions.

Technical Data

Supply voltage 230 V / 50 Hz
Standby power 0,45 W
Switching power 2300 W / 10 A resistive (cos j 1,0)

1200 VA / 5,2 A inductive (cos j 0,5)

350 VA / 1,5 A LED

DALI devices| 1–64
DALI power supply| max. 200 mA
DALI cable length| Ø 2.5 mm2 < 300 m

Ø 1.5 mm2 < 150 m

Ø 1.0 mm2 < 100 m

Max. no. of secondary detectors| 10
Detection area| 360°
Detection range| max. Ø 6 m presence, approx. Ø 24 m at a height of 3 m
Installation height| 2–3,5 m
Lux level control| 100–2000 lx
Timer control| 5 min to ¥
Standby lighting| Off, 5 min to ∞, level 0.1 to 51%.
Protection class| IP54
Temperature range| -5 bis +50 °C
Dimensions| Edition UP: Ø 100×46.4 mm (visible dimensions) Edition AP: Ø 117.3×45.9 mm (visible dimensions)
Flush-mount drilling| Ø 90 mm
Colour| RAL9010

Support & contact

Niko sa Industriepark West 40 9100 Sint-Niklaas, Belgium
www.niko.eu

Niko prepares its manuals with the greatest care and strives to make them as complete, correct, and up-to-date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals