VERTIV LP6000 Liebert Liqui-Tect Leak Detection Panel User Guide
- June 6, 2024
- VERTIV
Table of Contents
Vertiv™ Liebert® Liqui-Tect™ LP6000 Leak Detection Panel
GUIDE SPECIFICATIONS
1.0 GENERAL
Summary
The leak detection panel shall detect leaks, provide an audible/visual event
annunciation and provide a direct readout of the location of the leak. The
system shall also have the ability to communicate alarm and status information
to the Vertiv™ Liebert® Trellis™, Vertiv™ Liebert® SiteScan™ Web enterprise
monitoring system, Vertiv™ Liebert® Nform and to building management systems.
1.2 Standards
The leak detection panel shall be designed in accordance with applicable
sections of the current revision of the following listings and approvals.
- CE; EMC – EN61326 1997 Class A
- ETL Listed; UL STD 61010A-1; EN STD 61010-1; CAN/CSA C22.2 STD NO. 61010-1
- CL2P/CMP per UL STD (for Vertiv™ Liebert® LT500Y Leak Detection Cable); ANSI/NFPA 262EN62040-2
- RoHS (2011/65/EU)
- REACH (Regulation (EC) No 1907/2006)
- WEEE (2012/19/EU)
1.3 System Description
The leak detection panel shall include an integrated display with an
indication of normal and alarm conditions, as well as leak location. Display
and measurement modules are contained in a single compact package. The panel
can monitor the Liebert® LT500Y leak detection cable for conductive fluids.
The system determines the location of the water on the detection cable and
reports the distance from the leak detection module in feet or meters. To
ensure proper protection, the system continuously monitors operation,
signaling system normal, leak detected and cable fault. The leak detection
panel shall have the following functions:
-
Audible and visual alarms
-
Local touch screen display
-
Adjustable sensitivity set points for leaks and contamination
-
Historical log of leaks and faults
-
Connection to a building management system
-
Automatic detection of broken cables and contaminated cables
-
Password protection
-
The system shall be provided with retention of configuration after a power failure
-
Web-based (HTML) interface
-
Vertiv™ Liebert® SiteScan™ Web integration
-
Vertiv™ Liebert® Nform integration
The system shall consist of a leak detection panel, leak detection cable with cable hold-down clips and accessories.
1.4 User Documentation
The leak detection panel shall be supplied with a quick start guide for ease of installation, configuration and start-up. A full user manual shall be located on the manufacturer’s website for review and download. The user manual shall include installation instructions, a functional description of the equipment, safety precautions, illustrations, step-by-step operating procedures, and general maintenance guidelines.
1.5 Warranty
The leak detection panel manufacturer shall warrant the module against defects in materials and workmanship for one (1) year.
1.6 Quality Assurance
1.6.1 Factory Testing
The manufacturer shall fully and completely test the system to ensure compliance with the specification.
2.0 PRODUCT
2.1 Fabrication
All materials and components making up the leak detection panel shall be new,
of current manufacture and shall not have been in prior service except as
required during factory testing.
2.1.1 Panel
The leak detection panel shall be constructed as a standalone unit suitable
for vertical surface wall mounting and shall be housed in a metal Type 1
enclosure. The module shall be cleaned, primed and painted black.
1. Dimensions
The overall unit dimensions shall be 12.5”W x 10.0”H x 3.25”D (318mmW x 254mmH
x 83mmD) 2. Weight
The overall unit weights shall be less than or equal to 8.2 lb (3.7kg)
2.1.2 Cooling
The leak detection panel shall be convection cooled.
2.2 Power Requirements
1. Input Voltage
The leak detection panel shall be suitable for universal voltage input and
shall operate on 100/120/230240VAC @500mA max, 50/60 Hz, single-phase power
supply.
Power Supply
A universal power supply is integrated in the panel with screw terminal
connections for a hard wired connection.
2.3 Environmental Conditions
-
Operating Temperature
Ambient temperatures between 32°F and 122°F (0°C and 50°C) -
Storage Temperature
Storage at temperatures between -4°F and 158°F (-20°C and 85°C) -
Relative Humidity
Relative humidity between 5% and 95%, non-condensing -
Altitude
Maximum altitude of 15,000 feet (4572m)
2.4 Displays and controls
1. Display
One 480 pixels W x 272 pixels H color LCD, LED-backlit, resistive touch panel
display, is mounted on the front of the leak detection panel. The touch panel
display shall announce alarm conditions, display the status of the leak
detection system, and provide menus and softkeys for use in controlling and
configuring the leak detection panel. Certain menus shall be password
protected to prevent inadvertent changes to the leak detection panel’s
operation.
Audible Alarm
One audible alarm with an 85 db sound output at 2 feet (0.61m) which shall
sound for cable fault and leak detected conditions and shall be silenced by
pressing a softkey on the front panel display, or via the Web interface. The
audible alarm shall be programmable to re-sound after a time period of 0 to
999 minutes.
2.5 Interface Options
2.5.1 Ports
The leak detection panel shall be configured either via a web-based (HTML)
configuration and setup menu accessible from an Ethernet connection, via the
touch panel display or via a terminal-based menu accessible via EIA-232. All
configuration menus shall be password protected.
2.5.2 Relays
1. Leak
The leak detection panel shall include two (2) Form C Leak Relays with
contacts rated at 1A at 24VDC, 0.5A resistive at 120VAC. The relays shall be
configurable as latched or non-latched and supervised or non-supervised.
2. Cable Break
The leak detection panel shall include two (2) Form C Cable Break Relays with
contacts rated at 1A at 24VDC, 0.5A resistive at 120VAC. The relays shall be
configurable as latched or non-latched and supervised or non-supervised.
Maintenance
The leak detection panel shall include one (1) Form C Maintenance Relay, which
may be used to send a signal to a remote Building Management System (BMS) when
periodic maintenance is due. The maintenance interval shall be programmable
via the touch panel display or the Web interface
2.5.3 Analog Output
The leak detection panel shall provide a 4-20mA loop powered analog output,
which shall provide a signal proportional to the distance to the detected leak
2.5.4 Ethernet Communications
The leak detection panel shall be capable of Ethernet communications over a
10/100BASE–T network via the RJ45 network port. Communications protocols
supported over the Ethernet connection shall include SNMP, SMTP (email),
Modbus TCP/IP, BACnet IP, and web-based (HTML) access. 2.5.5 Serial
Communications 1. 232 The leak detection panel shall include an EIA-232 serial
port to interface with a PC allowing access to all functions and diagnostics
within the system. The EIA-232 serial port shall be 9600 baud, no parity, 8
data bits, 1 stop bit.
2. 485
The leak detection panel shall provide three independent EIA-485 serial ports
and shall be capable of Modbus/RTU Master and Slave communications, BACnet
MS/TP Slave communications, and N2 Slave communications via the EIA-485 serial
ports. Baud rates shall be user selectable between 9600, 19,200, and 38,400
baud.
2.5.6 Alarms
The leak detection module shall be capable of sending alarms via SNMP traps,
SMTP (email; up to four designated recipients), and BACnet. SL-
31013_REV1_09-21
4 Guide Specifications
2.6 Features and Functionality
2.6.1 Leak Cable Monitoring
The leak detection panel shall be capable of monitoring up to 10,000 feet
(3,048m) of LT500Y Leak Detection Cable and shall have a leak response time of
less than 30 seconds, a typical sensing repeatability of ±2 feet (.61m) +/-
0.25% of total cable length, and detection accuracy of +/- 2 feet (0.61m) +/-
0.5% of the cable length
2.6.2 System Monitoring
The leak detection panel shall continuously supervise the electrical and
mechanical integrity of the Leak Detection Cable.
2.6.3 Interactive Maps
The leak detection panel shall be capable of holding up to 10 images of floor
plans and overlaying maps of cable layouts on the images. In the event of a
leak or cable fault alarm, the leak detection panel shall be capable of
displaying the location of the leak on the floor plan image on the Web
interface.
2.6.4 Calibration
The leak detection panel shall allow leak detection sensitivity and cable
contamination setting adjustments. It shall be possible to manually and
automatically calibrate the module without the manufacturer’s intervention. An
optional password shall safeguard any unauthorized system calibration.
2.6.5 Virtual Zones
The leak detection panel shall monitor up to 32 user-configurable virtual
zones defined by the cable length at the beginning of the virtual zone. A
unique description of each virtual zone will be user-configurable.
2.6.6 Physical Zones
The leak detection module shall be capable to simultaneously monitoring up to
127 slave devices (leak detection modules and panels) that are integrated via
Modbus RTU (EIA-485) and Modbus TCP/IP (RJ45).
2.6.7 Logging
1. Trend”lL:l;;l;The leak detection panel shall maintain a trend log listing
the cable current level every day recorded at configurable intervals (1 minute
to 1440 minutes (1 day)), for the last 365 intervals.
2. Event
An event log shall also provide a record of the last 1024 events. Logged
events shall include, but not be limited to, Alarms, Cable Faults, and System
Restarts.
3. Time and Date
The leak detection panel shall use a real-time clock for time and date
stamping of trend and event log entries. The date and time shall be set
through the front panel display or the Web interface.
2.6.8 Logging Retention
The leak detection panel shall maintain the trend log and event log in
nonvolatile memory, the logs shall survive events such as power failures and
hard resets. The module shall keep the logs in a first-in-first-out (FIFO)
order.
2.6.9 NTP
The leak detection panel shall utilize Network Time Protocol (NTP) to
synchronize its internal clock to an external time source.
2.6.10 File transfer
The leak detection panel shall be capable of downloading and uploading
configuration files, uploading log files, and downloading images and firmware
upgrades, via the Web interface.
2.7 Vertiv™ Liebert® LT500Y Leak Detection Cable
2.7.1 Summary
The leak detection cable shall detect the presence of water and other
conductive liquids and shall be constructed of two sensing wires and two
insulated wires with an abrasion resistant, non-conductive polymer core. Each
individual sensing wire shall be covered with a non-conductive polymer mesh to
help prevent false alarms from contaminants. The leak detection cable shall be
fast drying and highly flexible allowing for small bend radii.
2.7.2 Standards
The leak detection cable shall be plenum rated to CL2P per UL (ANSI/NFPA262).
2.7.3 Fabrication
1. Physical
The leak detection cable shall be available in 10 feet (3.05m), 35 feet
(10.67m) and 50 feet (15.24m) lengths with mating connectors (male/female)
pre-installed. The cable shall be yellow in color with the sense cables being
black in color. The diameter of the cable shall not exceed 1/4″. The end of
the cable shall be terminated in matching male and female connectors for easy
connection of cables from end to end.
2. Characteristics
The leak detection cable shall have a Sheer Strength of > 180 lbs. (81.65kg)
and a Cut-Through Resistance of > 40 lbs. (18.14kg) with a .005in (0.127mm)
blade.
2.7.4 Environmental Conditions
-
Operating Temperature
Ambient temperatures between 32°F and 167°F (0°C and 75°C) -
Storage Temperature
Storage at temperatures between -22°F and 185°F (-30°C and 85°C) -
Relative Humidity
Relative humidity between 5% and 95%, non-condensing -
Altitude
Maximum altitude of 15,000 feet (4572m)
2.8 Accessories
2.8.1 Jumper Cables
A non-Sensing jumper cable shall be used to bridge between sections of leak
detection cable where water leak detection is not needed. The jumper cable
shall be plenum rated to CL3P per UL. NSC shall be available in 3 feet
(0.91m), 10 feet (3.05m), 25 feet (7.62m), 50 feet (15.24m) and 100 feet
(30.48m) lengths
with mating connectors (male/female) pre-installed.
2.8.2 Branching Connector
A branching connector shall be used to branch the Leak Detection Cable in
multiple directions. The branching connector shall be constructed with a
single cable input, a single cable output and two additional branch lines.
Multiple branching connectors can be used within a single system and the
accuracy of the system shall not be affected. The cable output and both branch
lines will add the equivalent of 35 feet (10.67m) to the system to add a
distinct separation of the outputs. The overall size of the branching
connector shall be 2.0”W x 0.9”H x 3.0”D (50.8mm x 22.86mm x 76.2mm).
2.8.3 Weighted Length
A Connector A-weighted length connector shall be used to simulate 35 feet
(10.67m) of Leak Detection Cable and provide distinct separation between areas
of coverage. The overall size of the weighted length connector shall be 2.5” x
1.0” (63.5mm x 25.4mm).
SL- 31013_REV1_09-21
Guide Specifications
Proprietary and Confidential © 2021 Vertiv Group Corp.
Documents / Resources
|
VERTIV LP6000 Liebert Liqui-Tect Leak Detection
Panel
[pdf] User Guide
LP6000, Liebert Liqui-Tect Leak Detection Panel
---|---