VERTIV Liebert GXE3-6000IRT4UXL Uninterruptible Power Supply User Manual

June 9, 2024
VERTIV

VERTIV Liebert GXE3-6000IRT4UXL Uninterruptible Power Supply

Overview

VERTIV Liebert GXE3-6000IRT4UXL Uninterruptible Power Supply
1

Vertiv™ Liebert® GXE Features
  • Hight output power factor (1.0)

  • Full-color graphic LCD

  • High efficiency in online mode (up to 94%)

  • ECO mode (up to 98% efficiency)

  • Flexible rack/tower design

  • Rack mounting kit included

  • Extended runtime with up to
    4 External Battery
    Cabinets (EBC)

  • User replaceable internal
    UPS batteries

  • Remote management capability with optional network management cards

  • Automatic internal bypass

  • Fast recharge time
    (3 hours @90%)

  • Wide input frequency operation (40-70Hz) without any power derating

  • Free UPS management software Vertiv Power Insight and Vertiv Power Assist

The Vertiv™ Liebert® GXE UPS in an online double conversion solution which offers power protection in an affordable, efficient system with deployment and operation flexibility.

The unity output power factor (1.0) of the Liebert® GXE UPS enables continuous and reliable power to more connected devices, protecting them against many disturbances in the AC mains with the online double conversion technology.

The high efficiency in both line and ECO modes of operation for this already affordable UPS also drives energy and operational costs savings.
It provides flexibility for mounting in either tower position or inside a rack cabinet, together with the IT equipment critical for any application. Moreover, the capability to add external battery cabinets provides scalable runtime for those applications requiring even a longer period of backup in case of AC mains failures.

In addition to the extended runtime, having multiple monitoring options make this compact UPS ideal for delivering best-in-class power protection to equipment at
the edge of networks or in remote sites.

VERTIV Liebert GXE3-6000IRT4UXL Uninterruptible Power Supply
2

What’s In The Box

  • Vertiv™ Liebert® GXE Unit
  • Quick Installation Guide
  • Safety Instructions
  • Adjustable 4-post rack mounting kit
  • Rack mounting ears/hardware
  • Stabilizing feet for tower configuration
  • USB type A to B cable (1.2 m)
  • Free download Vertiv™ Power Assist software for local UPS status and shutdown, or Vertiv™ Power Insight for remote network management with the optional IS-UNITY network management card

Technical Specifications

Technical Specifications|
---|---
 | GXE3-6000IRT4UXL| GXE3-10KIRT5UXL
Power Rating (VA/W)| 6000VA / 6000W| 10000VA / 10000W
Form Factor| Rack / Tower (4U)| Rack / Tower (5U)
Dimensions, mm|  |
Unit (W x D x H)| 430 x 750 x 173| 430 x 700 x 217
Shipping (W x D x H)| 600 x 850 x 480| 600 x 800 x 530
Weight, kg|  |
Unit| 70| 80
Shipping| 92| 102
Input AC Parameters|  |
Voltage Range Without Battery Operation

(230V default, derating applies)*

| 100 – 288| 100 – 288
Voltage Range Without Battery Operation

(230V default, 100% load)

| 176 – 288| 178 – 288
Frequency Range (Hz, autosensing)| 40 – 70| 40 – 70
Input Wiring| Hardwired (terminals L-N-G)| Hardwired (terminals L-N-G)
Surge Protetion (J)| 600| 600
Output AC Parameters|  |
Output Voltage| 220/230 (default) /240| 220/230 (default) /240
Waveform| Pure Sine Wave| Pure Sine Wave
Output Overload (AC Mode)| 105% – 125% @ 5 min – 126% – 150% @ 1 min

150% @ 200 ms

| 105% – 125% @ 5 min – 125% – 150% @ 1 min

150% @ 200 ms

Output wiring| Hardwired (terminals L-N-G)| Hardwired (terminals L-N-G)
Efficiency (online mode, max.)| 94%| 94%
Efficiency (ECO mode, max.)| 98%| 98%
Battery|  |
Type| Valve-regulated, non-spillable, lead-acid| Valve-regulated, non- spillable, lead-acid
Recharge Time (internal batteries, typical)| 3 hr @ 90%| 3 hr @ 90%
Backup Time (100% load, minutes)| 5| 3.5
Backup Time (50% load, minutes)| 14| 9
Comaptible External Battery Cabinet| GXE3-EBC192VRT2U| GXE3-EBC240VRT3U
Environmental|  |
Operating Temperature (ºC)| 0 to 40ºC| 0 to 40ºC
Storage Temperature (ºC, without battery inside)| -20ºC to +70ºC| -20ºC to +70ºC
Relative Humidity (operation, non-condensing)| 5% to 95%| 5% to 95%
Operating Altitude (m), without derating ()| 2000| 2000
Audible Noise (line mode)| <55dBA| <58dBA
Agency|  |
Compliance| CE, CB Report, EAC, UKCA, Morocco, RCM| CE, CB Report, EAC, UKCA, Morocco, RCM
Safety| IEC/EN 62040-1| IEC/EN 62040-1
Transportation| ISTA 3E| ISTA 3E
Environmental| RoHS, REACH, WEEE| RoHS, REACH, WEEE
Communications and Management|  |
Slot for optional cards| Yes| Yes
Communication port| USB| USB
Emergency Power Off (EPO)| Yes| Yes
Warranty**|  |
Warranty (electronics and batteries)| 2 years| 2 years

Note: Specific conditions or power derating applies. (**) Note: Up to 3000 m with power derating.

External Battery Cabinets

Dimensions, mm GXE3-EBC192VRT2U GXE3-EBC240VRT3U
Unit (W x D x H) 430 x 765 x 85 430 x 645 x 130
Shipping (W x D x H) 600 x 850 x 405 600 x 800 x 450
Weight, kg  
Unit 58.4 66.9

Shipping

Agency

| 78| 85
Compliance| CE, CB Report, EAC, UKCA, Morocco| CE, CB Report, EAC, UKCA, Morocco

Vertiv.com 

Vertiv Headquarters, 505 N. Cleveland Ave., Westerville, Ohio, 43082, USA
© 2023 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at Vertiv’s sole discretion upon notice.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals