VERTIV Liebert ITA2 UPS Installation Guide

October 30, 2023
VERTIV

VERTIV Liebert ITA2 UPS

VERTIV-Liebert-ITA2-UPS-product

Product Information

ITA2 UPS
The ITA2 UPS provides flexible power protection for rack or tower installation, with a wide input voltage range and the ability to deliver both three-phase and single-phase output. With a robust structure, cutting-edge channelized airflow design, and compliance with seismic conduction and vehicle-carrying tests, this UPS is designed for reliability in a compact footprint.

Available in 5-40 kVA, the ITA2 UPS is tailored for global deployment in a low-carbon, compact footprint. It is suitable for use in edge networks, data centers, automation industries, server farms, workstations, and telecom applications.

Key Features:

  • Robust structure with cutting-edge channelized airflow design
  • Wide input voltage range, making it immune to grid interference
  • Rack-tower design for installation flexibility
  • Able to deliver both three-phase and single-phase output
  • 0.99 input power factor for better grid or generator compatibility
  • Powerful charging capability for minimum battery recharging time
  • Programmable output outlets/terminals with cascade protection to protect key devices during heavy load
  • Integrated communication port for remote monitoring
  • Easy to install, repair, and maintain
  • Compliance with seismic conduction and vehicle-carrying test
  • Gravity sense LCD display

The Most Efficient UPS:
The ITA2 UPS is highly efficient with an efficiency rating of up to 98%. It offers ECO mode and double conversion mode options for greater flexibility in managing power usage.

The Most Flexible UPS:
The ITA2 UPS is designed for flexibility with optimized modules that minimize the amount of used space in the rack, a support base for stable floor placement, and adjustable display panel for readability and ease of use. It also offers fast, flexible, and easy-to-deploy power output distribution options. The flexible battery configurations such as VRLA and Lithium-ion external battery cabinets are designed to meet individual installation availability and backup time requirements.

Dust-resistant Design:
The ITA2 UPS is designed with a dust-resistant design that provides reliability in a compact footprint. It offers fully-digital control with high output voltage precision, manages all nine power problems including sagging, spikes, and fluctuations, and provides a built-in intelligent communication card for remote monitoring and management. It also offers built-in power charger for fast charging, reduces the battery charging time, prolonged backup time through cascaded connection, and is quality-tested for 1000 hours for extreme durability and tolerance even in stringent conditions.

High Availability:
The ITA2 UPS offers early warning of UPS system status through multiple audible and visual alarms that instantly alert for critical issues. It also provides periodic battery testing that offers automatic and manual self- diagnostic battery testing for peace of mind. Power-factor correction prevents noise, harmonics, and distortion from being transferred to connected loads or fed back to the utility.

Product Usage Instruction

To use the ITA2 UPS, follow these steps:

  1. Choose the appropriate model based on your power requirements and installation needs. The ITA2 UPS is available in 5-40 kVA and can be installed as a rack or tower.
  2. Prepare the installation site by ensuring that it is dust-free and meets the seismic conduction and vehicle-carrying test requirements.
  3. Install the UPS according to the instructions provided in the user manual. The rack-tower design offers installation flexibility, and the easy-to-install design ensures a quick and hassle-free installation.
  4. Connect the input power to the UPS, ensuring that the input voltage range is within the specified limits.
  5. Connect the output power to your critical systems, such as edge networks, data centers, automation industries, server farms, workstations, or telecom applications. The programmable output outlets/terminals with cascade protection will protect key devices during heavy load.
  6. Monitor the UPS using the integrated communication port for remote monitoring. The gravity sense LCD display provides easy-to-read information about the UPS status.
  7. Maintain the UPS regularly by performing periodic battery testing and following the instructions provided in the user manual for repair and maintenance. The UPS is designed for easy repair and maintenance to ensure maximum uptime and reliability.

In today’s dynamic world, having basic power protection is not enough for enterprises. Business continuity is even more vital with digital trends constantly emerging and transforming the way you do business. In your critical system, you simply cannot afford downtime or waste time recovering these systems after a disruption. What you need is a robust, highly-efficient, reliable UPS system that offers perennial, round-the-clock protection for diverse applications.

Our Solution

The Vertiv™ Liebert® ITA2 is a fully-digital, highly reliable, double- conversion UPS solution that provides clean and consistent power. This highly efficient solution is ideal for various deployments, including IT racks, network closets, automation control systems, and precision instruments to small-sized control rooms among other edge applications.

  • Cutting–edge design enables seamless integration into various ecosystems
  • Tailored for global deployment in a low-carbon, compact footprint

The ultimate level of engineering and dynamics that have gone beyond the development of this innovative, next-generation product facilitate top-notch availability and excellent performance at low ownership costs, giving you ultimate peace of mind.

Liebert® ITA2 5-40 kVA

Application Areas

  • Edge Networks
  • Data Centers
  • Automation industries
  • Server Farms
  • Workstations
  • Telecom

Liebert® ITA2
Robust power protection solution in a compact package

VERTIV-Liebert-ITA2-UPS-fig- \(2\)

Key Features

  • Robust structure with cutting edge channelized airflow design
  • Wide input voltage range, making it immune to grid interference
  • Rack-tower design for installation flexibility
  • Able to deliver both three-phase and single-phase output2
  • 0.99 input power factor for better grid or generator compatibility
  • Powerful charging capability for minimum battery recharging time
  • Programmable output outlets/terminals with cascade protection to protect key devices during heavy load2
  • Integrated communication port for remote monitoring
  • Easy to install, repair, and maintain
  • Compliance with seismic conduction and vehicle carrying test
  • Gravity sense LCD display
  • Turnkey dust-resistant design with ability to operate under high ambient temperature of up to 50 ºC

The Most Efficient UPS

Vertiv™ Liebert® ITA2 offers best-in-class efficiency of up to 96.5% in double conversion mode over a wide range of load conditions, resulting in significant OPEX cost savings. Liebert ITA2’s integrated ECO mode of operation further enhances efficiency of up to 99%.

VERTIV-Liebert-ITA2-UPS-fig- \(3\)

The Most Flexible UPS

VERTIV-Liebert-ITA2-UPS-fig- \(4\)

  • Optimized modules minimize the amount of used space in the rack
  • The support base makes it convenient and stable to place on a floor
  • Adjustable display panel ensures readability and ease of use
  • Fast, flexible and easy-to-deploy power output distribution options
  • The flexible battery configurations such as VRLA and Lithium-ion external battery cabinets are designed to meet individual installation availability and back up time requirements.VERTIV-Liebert-ITA2-UPS-fig- \(5\)

Available in different wattage variations, Vertiv™ Liebert® ITA2 is ideal in the edge of networks, light industrial applications and data centers, easily blending into any virtualized environment and providing comprehensive power protection at reduced operating costs.

Reliability in a compact footprint

  • Fully-digital control with high output voltage precision
  • Manages all the nine power problems including sagging, spikes, and fluctuations
  • Built-in intelligent communication card for remote monitoring and management
  • Built-in-power charger for fast charging reduces the battery charging time
  • Prolonged backup time through cascaded connection
  • Quality-tested for 1000 hours for extreme durability and tolerance even in stringent conditions

High Availability

Early Warning of UPS System Status
Multiple audible and visual alarms instantly alert for critical issues.

Periodic Battery Testing
Provides automatic and manual self-diagnostic battery testing for peace of mind.

Power-Factor Correction
Prevents noise, harmonics, and distortion from being transferred to connected loads or fed back to the utility.

Lightning and Surge Protection
The transient voltage surge suppression circuitry inside the Liebert® ITA2 provides additional protection for the connected equipment.

Wide Input Voltage Window
Prolongs battery life by allowing the UPS to maximize the use of utility power before being transferred to the battery when the input voltage exceeds the specified limits.

More of What You Need: High Power Density
The Vertiv™ Liebert® ITA2 is designed with a high power factor in a small footprint. This increased power density maximizes the usable power to meet the needs of advanced IT operations.

VERTIV-Liebert-ITA2-UPS-fig- \(6\)

POD- Optional Accessories
The Liebert POD maintenance bypass and output distribution unit ensures continuous uptime when your critical system cannot afford any power loss without power, even for scheduled UPS maintenance. It allows you to manually transfer connected equipment to utility power via a maintenance bypass switch, permitting scheduled service or UPS replacement without shutting down connected equipment.

Lithium-ion Battery Compatibility

The Liebert® ITA2 is powered with most powerful & intelligent battery charger that enables to integrate seamlessly with Safest Lithium Iron Phosphate (LFP) chemistry batteries. Considering the benefits lithium-ion batteries providesover traditional battery deployments. Not only do users enjoy the longer life, more cycles and fewer replacements, they also benefit from the compact, smaller size and lower weight. Plus, the higher operating temperature and lower maintenance add to the savings.

All these advantages directly impact IT facilities to drive an impressive total cost of ownership experience. Vertiv leverages its DNA in critical systems to deliver a lithium-ion battery system that is integrated seamlessly into the power chain.
Our capabilities and processes come together to ensure the UPS, batteries, monitoring, management service and support offerings are orchestrated for delivering on our customer expectations.

Benefits of Lithium-ion Batteries

VERTIV-Liebert-ITA2-UPS-fig- \(9\)

Intelligent Communications

The Vertiv™ Liebert® ITA2 offers an intuitive control panel, network connectivity communications card, and optional software monitoring, all designed to ensure visibility, control and peace of mind for manned or unmanned locations. You can even monitor key environmental and room conditions.

Vertiv™ Power Insight
Vertiv™ Power Insight is a web-based solution for managing and monitoring up to 100 Vertiv™ UPSs and rPDUs that provides a quick way to safely shutdown IT devices based on user-configured parameters. It helps improve availability and simplifies the monitoring and management of mission-critical IT equipment. Additionally, if VMware™ is your virtualization platform of choice, you can benefit from the seamless integration offered by the Vertiv Power Insight vCenter Plugin. The vCenter Plugin provides single-pane-of-glass monitoring and management of UPS and rPDU infrastructure directly within the vCenter Management Platform.

It can also be configured to trigger automatic Virtual Machine (VM) shutdown or migration (using vMotion) based on alarms or events communicated by Vertiv Power Insight.

Remote Diagnostic Services for Rapid Response

Data-Driven Insight
With Life Services you don’t just have someone periodically checking equipment status. You have Vertiv experts continuously monitoring and analysing all relevant control and operating parameters from your equipment to maintain optimum performance.

Real-time Response
Real-time data enables realtime response to potential anomalies. Rather than wait for a problem to be detected by on-site personnel, Vertiv Life Services “sees” operating issues as soon as they occur. It triggers immediate service action to prevent problems or cut hours or days off the time-to-repair, preventing or reducing downtime.

Connected Service
Vertiv service engineers can resolve many anomalies remotely and are connected to the Vertiv field service organisation for on-site resolution. They can dispatch a field service engineer as soon as a critical condition is identified, often arming the engineer with a diagnosis so they arrive knowing the issue and with any required replacement parts.

Battery Backup

Battery Backup Table (With VRLA)

UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
5kVA| 4.5kVA| 4kVA| 3.5kVA| 3kVA| 2.5kVA| 2kVA| 1.5kVA| 1kVA| 0.5kVA
 | 1| 6.8| 7.8| 9.2| 11.2| 13.9| 17.9| 24.3| 35.6| 58| 122.4
 | 2| 18| 20.9| 24.6| 29.7| 36.5| 46| 59.7| 81.7| 126.4| 278.8
 | 3| 31.9| 36.6| 42.6| 50.2| 60.2| 74.1| 94.5| 128.3| 207| 435.7
5kVA|  |  |  |  |  |  |  |  |  |  |
 | 4| 46.3| 52.6| 60.3| 70.2| 83.5| 102.2| 130.3| 182.7| 287.6| 592.5
 | 5| 60.4| 68.1| 77.8| 90.3| 107| 131.4| 171.6| 237.1| 368.2| 749.3
 | 6| 74.4| 83.7| 95.4| 110.4| 131.5| 164.6| 212.9| 291.5| 448.8| 906.1
UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
6kVA| 5.4kVA| 4.8kVA| 4.2kVA| 3.6kVA| 3kVA| 2.4kVA| 1.8kVA| 1.2kVA| 0.6kVA
 | 1| 5.1| 6.1| 7.1| 8.6| 10.8| 13.9| 19| 28| 46.9| 101
 | 2| 14| 16.1| 19.1| 23| 28.6| 36.5| 48.4| 67| 103.9| 228.2
 | 3| 24.7| 28.7| 33.6| 40| 48.5| 60.2| 77.6| 105.6| 167.6| 359.7
6kVA|  |  |  |  |  |  |  |  |  |  |
 | 4| 36.7| 42| 48.7| 57| 68| 83.5| 106.9| 147.8| 235.1| 491.2
 | 5| 48.8| 55.3| 63.3| 73.6| 87.5| 107| 138.3| 193.5| 302.6| 622.8
 | 6| 60.5| 68.2| 77.9| 90.4| 107.1| 131.5| 172.9| 239.1| 370.1| 754.3
UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
10kVA| 9kVA| 8kVA| 7kVA| 6kVA| 5kVA| 4kVA| 3kVA| 2kVA| 1kVA
 | 2| 4.8| 5.5| 7.4| 10.2| 14| 18| 24.6| 36.5| 59.7| 126.4
 | 3| 8.8| 10.2| 13.6| 18.5| 24.7| 31.9| 42.6| 60.2| 94.5| 207
10kVA| 4| 13.7| 15.9| 21.1| 28.4| 36.7| 46.3| 60.3| 83.5| 130.3| 287.6
 | 5| 19.4| 22.4| 29.7| 39.3| 48.8| 60.4| 77.8| 107| 171.6| 368.2
 | 6| 25.8| 29.6| 38.6| 50.6| 60.5| 74.4| 95.4| 131.5| 212.9| 448.8
UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
16kVA| 14.4kVA| 12.8kVA| 11.2kVA| 9.6kVA| 8kVA| 6.4kVA| 4.8kVA| 3.2kVA| 1.6kVA
 | 4| 9.5| 11| 13| 15.6| 19.4| 24.8| 33.8| 48.7| 77.7| 169.6
 | 6| 16.8| 19.6| 23.1| 27.8| 34| 42.9| 56.2| 77.9| 121.7| 271.9
16kVA| 8| 25.3| 29.3| 34.4| 40.8| 49.2| 60.7| 78.1| 107.3| 173.2| 374.1
 | 10| 34.4| 39.5| 45.9| 53.8| 63.9| 78.4| 100.3| 138.9| 225.2| 476.3
 | 12| 43.6| 49.7| 57.2| 66.5| 78.7| 96.1| 122.4| 173.7| 277.2| 578.6
UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
20kVA| 18kVA| 16kVA| 14kVA| 12kVA| 10kVA| 8kVA| 6kVA| 4kVA| 2kVA
 | 4| 6.9| 8| 9.5| 11.5| 14.3| 18.3| 24.8| 36.7| 60.3| 130.3
 | 6| 12.3| 14.3| 16.8| 20.4| 25.3| 32.3| 42.9| 60.5| 95.4| 212.9
20kVA| 8| 18.5| 21.5| 25.3| 30.5| 37.5| 46.8| 60.7| 84| 131.8| 295.5
 | 10| 25.3| 29.3| 34.4| 41| 49.7| 61.1| 78.4| 107.6| 173.4| 378.1
 | 12| 32.6| 37.5| 43.6| 51.4| 61.6| 75.2| 96.1| 132.3| 215.1| 460.7
Note: Battery autonomy times and 5 year design life are based on operation at 2 5 ° C . Approximate autonomy times are based on fully charged batteries and can vary +/-5% due to battery manufacturing variances.

Battery Backup Table (With 192 V, 12 Ah Lithium-ion)

UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
5kVA| 4.5kVA| 4kVA| 3.5kVA| 3kVA| 2.5kVA| 2kVA| 1.5kVA| 1kVA| 0.5kVA
 | 1| 20| 22| 28| 32| 36| 46| 56| 76| 118| 222


5 kVA

(Single phase UPS

Models)

| 2| 44| 50| 56| 64| 78| 92| 116| 156| 242| 448
3| 68| 76| 88| 100| 118| 144| 178| 240| 364| 674
4| 94| 104| 116| 134| 158| 194| 240| 322| 484| 894
5| 118| 132| 144| 168| 198| 244| 302| 404| 604| 1114
 | 6| 142| 160| 172| 202| 238| 294| 364| 486| 724| 1334
UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
6kVA| 5.4kVA| 4.8kVA| 4.2kVA| 3.6kVA| 3kVA| 2.4kVA| 1.8kVA| 1.2kVA| 0.6kVA
 | 1| 16.0| 18.0| 20.6| 26.0| 30.0| 36.0| 47.9| 63.0| 98.3| 185.0


6 kVA

(Single phase UPS

Models)

| 2| 36.0| 41.0| 46.9| 53.0| 60.0| 78.0| 95.8| 129.0| 201.7| 373.3
3| 56.0| 63.0| 71.3| 83.0| 96.0| 118.0| 147.8| 199.0| 303.3| 561.7
4| 78.0| 86.0| 97.5| 111.0| 130.0| 158.0| 197.8| 267.0| 403.3| 745.0
5| 97.0| 109.0| 123.8| 139.0| 164.0| 198.0| 247.8| 335.0| 503.3| 928.3
 | 6| 117.0| 132.0| 150.0| 167.0| 198.0| 238.0| 297.8| 403.0| 603.3| 1111.7
UPS

Model

| Battery Modules|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
10kVA| 9kVA| 8kVA| 7kVA| 6kVA| 5kVA| 4kVA| 3kVA| 2kVA| 1kVA
 | 1| 10| 11| 14| 16| 18| 23| 28| 38| 59| 111


10 kVA

(Single phase UPS

Models)

| 2| 22| 25| 28| 32| 39| 46| 58| 78| 121| 224
3| 34| 38| 44| 50| 59| 72| 89| 120| 182| 337
4| 47| 52| 58| 67| 79| 97| 120| 161| 242| 447
5| 59| 66| 72| 84| 99| 122| 151| 202| 302| 557
 | 6| 71| 80| 86| 101| 119| 147| 182| 243| 362| 667
UPS

Model

| Battery **Modules*|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
20kVA| 18kVA| 16kVA| 14kVA| 12kVA| 10kVA| 8kVA| 6kVA| 4kVA| 2kVA**
 | 1 string| 10| 11| 14| 16| 18| 23| 28| 38| 59| 111


20 kVA

(Three phase UPS

Models)

| 2 string| 22| 25| 28| 32| 39| 46| 58| 78| 121| 224
3 string| 34| 38| 44| 50| 59| 72| 89| 120| 182| 337
4 string| 47| 52| 58| 67| 79| 97| 120| 161| 242| 447
5 string| 59| 66| 72| 84| 99| 122| 151| 202| 302| 557
 | 6 string| 71| 80| 86| 101| 119| 147| 182| 243| 362| 667
UPS

Model

| Battery **Modules*|  |  |  | Backup Time in Minutes|  |  |
---|---|---|---|---|---|---|---|---
30kVA| 27kVA| 24kVA| 21kVA| 18kVA| 15kVA| 12kVA| 9kVA| 6kVA| 3kVA**
 | 2 string| 15| 16| 18| 21| 25| 30| 39| 52| 78| 173


30 kVA

(Three phase UPS

Models)

| 3 string| 22| 25| 28| 32| 38| 47| 59| 81| 120| 260
4 string| 30| 34| 38| 43| 52| 63| 79| 109| 161| 345
5 string| 38| 43| 48| 55| 66| 78| 99| 137| 202| 430
6 string| 47| 52| 59| 67| 80| 93| 119| 165| 243| 515
 | 7 string| 56| 62| 70| 79| 94| 109| 139| 193| 284| 600

Note: 1 string equals to 2 battery cabinets
Backup times in above tables have approximate values. They are based on new, fully charged batteries at a temperature of 77°F (25°C) with 100% resistive UPS loading. Different loading will change the actual backup times. Backup times listed may vary by ±5% due to manufacturing variances of the batteries.

Build Your Total Infrastructure Solution with Vertiv

Discover expert-designed IT infrastructure solutions with proven success in diverse environments

VERTIV-Liebert-ITA2-UPS-fig- \(12\)

Vertiv™ Liebert ITA2 UPS Specifications

Nominal Ratings (kVA) 5 6 10 16 20 30 40
Long Backup Model ITA- 05k00AL1102P00 ITA- 06k00AL1102P00 ITA-
10k00ALA102P00 ITA- 16k00AL3A02P00 ITA- 20k00AL3A02P00 ITA- 30k00AL3302P00

ITA- 40k00AL3302P00
Part Number| 01202670| 01202671| 01202672| 01202682| 01202683| 01202660| 01202897

Input Parameters



Nominal Input Voltage (V)

| ****


220/230/240 VAC 1-Phase, 2 Wire

| 220/230/240 VAC

1-Phase, 2 Wire;

380/400/415 VAC

3-Phase, 4 Wire

| ****


380/400/415 VAC 3-Phase, 4 Wire

---|---|---|---
Input Voltage Range (V)| 176-288 VAC at full load; 100-176 VAC at linear derating; 100 VAC at half load
Nominal Input Frequency (Hz)| 50/60
Input Power Factor (kW/kVA)3| 0.99
Current THD at Full Linear Load3| <3

Battery

Battery Blocks Per String| 12, 15, 16, 17, 18, 19, 20| 24, 30, 32, 34, 36, 38, 40| 32-40| 24-40**
---|---|---|---|---
Battery Charger Max. Power (A)| 5| 8| 13|


External Battery Cabinet Option (VRLA)

| P/C : ITA-BCI0020K01 ( built-in battery module of 16 block X 12 V X 9 AH) Battery cabinet Dimensions in rack arrangement – 430 (W) x 750 (D) x 85 (H)| Only external

battery cabinet


External Battery Cabinet Option (Li-ion)4

| P/C: ITA-BLI0020KL2 ( 2U lithium ion battery module assembly – 192V / 12Ah/1 cabinet ) Battery cabinet Dimensions in rack arrangement- 430 (W) x 680 (D) x 86 (H); Weight – 35 kg / cabinet| ****

NA

Output

VERTIV-Liebert-ITA2-UPS-fig- \(13\)

Efficiency

Online Mode Efficiency Up to 95.5% Up to 95.8% Up to 96.2% Up to 96.5%
ECO Mode Efficiency     Up to 99%

Dimensions and Weight

UPS Dimensions (W x D x H) in mm-Rack Mounted Arrangement| ****

430 x 480 x 85

| ****

430 x 590 x 85

| ****

430 x 600 x 130

| ****

430 x 730 x 130

---|---|---|---|---
Weight (kg)| 11| 15| 23| 23.5| 30

General

VERTIV-Liebert-ITA2-UPS-fig- \(14\)

Note:
Departing conditions apply ** 24-26-28-30 with de-rating (1) with ABS certification (2) Not Available in 30 & 40 kVA (3) Conditions apply (4) For 5-10 kVA, requires min 1 battery cabinet; For 16-20 KVA, requires min one group (2 battery cabinets); For 30 kVA, requires min two groups (4 battery cabinets); For 40 kVA, not available.

Vertiv.com | Asia Pacific
© 2022 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Group Corp. assumes no responsibility and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VERTIV User Manuals

Related Manuals