GENASUN GVB-8-Pb-12V-WP Waterproof Voltage Boosting Solar Charge Controllers User Manual

June 8, 2024
GENASUN

GVB-8-WP (Boost) Manual

Waterproof Voltage Boosting Solar Charge Controllers with Maximum Power Point Tracking

For models:

GVB-8-Pb-12V-WP: 12 V Lead-Acid/AGM/Gel/Sealed/Flooded
GVB-8-Pb-24V-WP: 24 V Lead-Acid/AGM/Gel/Sealed/Flooded
GVB-8-Pb-36V-WP: 36 V Lead-Acid/AGM/Gel/Sealed/Flooded
GVB-8-Pb-48V-WP: 48 V Lead-Acid/AGM/Gel/Sealed/Flooded
GVB-8-Li-14.2V-WP: 12 V (4s) Lithium Iron Phosphate
GVB-8-Li-28.4V-WP: 24 V (8s) Lithium Iron Phosphate
GVB-8-Li-41.7V-WP: 36 V (10s) Lithium Cobalt/Manganese/Nickel
GVB-8-Li-42.6V-WP: 36 V (12S) Lithium Iron Phosphate
GVB-8-Li-50.0V-WP: 36 V (12s) Lithium Cobalt/Manganese/Nickel
GVB-8-Li-54.2V-WP: 48 V (13s) Lithium Cobalt/Manganese/Nickel
GVB-8-Li-56.8V-WP: 48 V (16s) Lithium Iron Phosphate
GVB-8-Li-58.4V-WP: 52 V (14s) Lithium Cobalt/Manganese/Nickel

8A Input – 105 W / 210 W / 325 W / 350 W
GENASUN GVB-8-WP BOOST (ALL MODELS STARTING FROM S/N 188100) MANUAL, REVISION 7.0 | 2024

SUNFORGE LLC
2598 FORTUNE WAY • SUITE K
VISTA, CA 92081 • USA
https://sunforgellc.com

IMPORTANT SAFETY INSTRUCTIONS | SAVE THESE INSTRUCTIONS

Safety Instructions:

This manual contains important instructions for the GVB-8-WP Boost (all versions starting from S/N 188100) solar charge controllers that shall be followed during installation and maintenance. Various models of the GVB-8-WP are available to charge different battery types as follows:

  • GVB-8-Pb-12V-WP: 12 V Lead-Acid/AGM/Gel/Sealed/Flooded
  • GVB-8-Pb-24V-WP: 24 V Lead-Acid/AGM/Gel/Sealed/Flooded
  • GVB-8-Pb-36V-WP: 36 V Lead-Acid/AGM/Gel/Sealed/Flooded
  • GVB-8-Pb-48V-WP: 48 V Lead-Acid/AGM/Gel/Sealed/Flooded
  • GVB-8-Li-14.2V-WP: 12 V (4S) Lithium Iron Phosphate
  • GVB-8-Li-24.8V-WP: 24 V (8S) Lithium Iron Phosphate
  • GVB-8-Li-41.7V-WP: 36 V (10S) Lithium Cobalt/Manganese/Nickel
  • GVB-8-Li-42.6V-WP: 36 V (12S) Lithium Iron Phosphate
  • GVB-8-Li-50.0V-WP: 36 V (12S) Lithium Cobalt/ Manganese/Nickel
  • GVB-8-Li-54.2V-WP: 48 V (13S) Lithium Cobalt/ Manganese/Nickel
  • GVB-8-Li-56.8V-WP: 48 V (16S) Lithium Iron Phosphate
  • GVB-8-Li-58.4V-WP: 52 V (14S) Lithium Cobalt/ Manganese/Nicke

Consult your battery charging specifications to ensure that the GVB-8-WP is compatible with your chosen batteries.
The GVB-8-WP includes an external 10 A In-Line fuse rated for the maximum battery voltage.

WARNING: EXPLOSION HAZARD. DO NOT CONNECT OR DISCONNECT WHEN ENERGIZED. DO NOT REMOVE OR REPLACE FUSES UNLESS POWER HAS BEEN DISCONNECTED OR THE AREA IS FREE OF IGNITIBLE CONCENTRATIONS. ATTENTION: RISQUE D’EXPLOSION. NE PAS CONNECTER NI DÉCONNECTER PAS LORSQU’IL EST SOUS TENSION. NE PAS CONNECTER LE CIRCUIT ALORS QUE EST VIVANT OU A MOINS QUE LA ZONE EST LIBRE DE CONCENTRATIONS IGNITAIRES. CAUTION for the GVB-8-Pb-**V-WP (Lead-Acid Versions Only): INTERNAL TEMPERATURE COMPENSATION. RISK OF FIRE, USE WITHIN 0.3 m (1 ft) of BATTERIES. Lead-acid batteries can create explosive gases. Short circuits can draw thousands of amps from a battery. Carefully read and follow all instructions supplied with the battery. DO NOT SHORT CIRCUIT the solar array when plugged into the controller. DO NOT MEASURE SHORT CIRCUIT CURRENT of the array while connected to the controller. This may damage the controller, and such damage will not be covered under warranty. Grounding is not necessary for operation and is at the user’s discretion. If the GVB-8-WP is to be used with a solar array electrically connected to earth ground, please note the following: WARNING: THIS UNIT IS NOT PROVIDED WITH A GFDI DEVICE. Consult Article 690 of the National Electrical Code (or the standards in force at the installation location) to determine whether a GFDI is necessary for your installation.

WARNING: THIS UNIT IS NOT PROVIDED WITH DISCONNECT DEVICES. Consult Article 690 of the National Electrical Code (or the standards in force at the installation location) to determine whether disconnect devices are necessary for your installation.

LITHIUM WARNING: Use caution when working with lithium systems. Genasun Li controllers use the CC/CV charging profile indicated on the controller. CHECK the specifications of the battery pack to ensure that the CV voltage is correct. Further check that the power supplied by the solar array and Genasun controller is within the battery specified design limits.

LITHIUM BMS WARNING: Genasun recommends using a lithium battery with a Battery Management System capable of disconnecting the solar charge controller in the event that any cell in the pack is outside of its rated temperature, current, or voltage range. Failure to do so may result in property damage, injury or death. Genasun highly recommends the use of a BMS with cell balancing. Cell balancing is mandatory for lithium iron phosphate. Use only copper conductors suitable for a minimum of 60 °C. If operation at high power or at high ambient temperatures is expected, wire with a higher temperature rating may be necessary.

Product Certifications

| |
---|---|---
EMC
Conforms to:
EN 61000-6-3:2007+A1:2011
EN 61000-6-2:2005
AS/NZS 61000-6-3:2012| EMC
Conforms to:
FCC (CFR Title 47) Part 15 Radio frequency
Devices, Subpart B – Unintentional
Radiators. Tested for compliance.| Restriction Hazardous Substances
Conforms to:
EN 50581:2012

Inspection & Maintenance

Inspect the controller at least once per year to ensure proper performance.

  • Check for animal or insect damage.
  • Inspect for corrosion / water damage.
  • Inspect the security of all connections.
  • Ensure the solar array does not exceed the maximum input voltage.
  • Repair and clean as necessary
Installation & System Connections:
  • Connections should be made according to Article 690 of the National Electrical Code (NFPA 70) or the standards in force at the installation location.
  • Electrical connections may be made in any order; however the sequence below is recommended.

(1) MOUNTING

Mount the controller near your battery securely using the holes provided on the enclosure’s flanges or with a means appropriate to the application.

  • Mount near the battery (for lead-acid versions only, use within 0.3 m (1 ft) of batteries. See Caution, p.2).
  • The GVB-8-WP can be mounted in any orientation on the floor or wall. We recommend a position in which all labels are clearly visible.
  • Do not mount in direct sunlight or near a source of heat.
  • Allow adequate airflow around the controller to achieve maximum output capability

Note: The positive or negative battery cable must be protected by a fast- acting fuse or circuit breaker of 10 A or less, rated for the maximum battery voltage and connected close to the battery terminal or power distribution block. This fuse will protect the wiring in the event of a short circuit or controller damage.

  1. Note: GVB-8-WP is Negative Common , “-Panel” and “-Battery” (both black cables) are interchangeble.
  2. 10 A IN-LINE FUSE (INCLUDED)
  3. Note: Starting from S/N 188100 the GVB-8-WP (all models) comes with 12 AWG flying leads.
    For the previous version, please refer to manual revision 6.0 |2021

(2) CONNECTING THE SOLAR PANEL

Connect the solar panel to the PANEL+ and PANEL- terminals.

  • In most applications, the panel should be connected only to the GVB-8-WP.
  • The LED may blink red until a battery is connected.
  • Do not use blocking diodes for single-panel installations. The GVB-8-WP prevents reverse current flow.
  • If multiple panels are being used in parallel, blocking diodes are recommended in series with each panel, unless the panel manufacturer recommends otherwise.
  • Solar panel voltage rises in cold weather. Check that the solar panel open circuit voltage (Voc) will remain below the maximum input voltage of the GVB-8-WP at the coldest possible expected temperature.
  1. PANEL
  2. BATTERY
  3. *FUSE

Note: In the GVB-8-WP, the negative side of the battery is connected internally to the negative side of the solar panel.

(3) CONNECTING THE BATTERY

Connect the battery to the BATT+ and BATT- terminals.

  • A small spark while connecting the battery is ok.
  • Any loads should be connected directly to the battery. The GVB-8-WP does not provide protection against over-discharge.

GENASUN GVB-8-Pb-12V-WP Waterproof Voltage Boosting Solar Charge Controllers
3

  1. The GVB-WP has a MULTICOLOR LED. Learn about this indicator on the following page.

CAUTION, RISK OF FIRE OR EXPLOSION: Do not make the final battery connection near lead-acid batteries that have recently been charging.

Status Indication:

The GVB has a MULTICOLOR LED

LED RUN/CHARGE INDICATION
Standby: The battery is connected properly and ready to charge when solar panel power is available.
2 SEC. BETWEEN BLINKS

Charging (low current, input current less than ~3.5 A):
FAST & SHORT BLINKS

Charging (high current, input current more than ~3.5 A):
LONGER, SLOWER BLINKS

Charging (current limit): charging at current limit.
The GVB-8-WP is overloaded and limiting input current. Check that the solar panel rating is within the GVB-8-WP’s input specifications.
LONG, THEN SHORT BLINKS

Battery Charged: The battery is in the absorption or float charging stage.
SOLID GREEN

LED ERROR INDICATION

Overheat: The controller’s internal temperature is too high.
SETS OF 2 RED BLINKS

Overload: The GVB-8-WP has been overloaded.
This could be caused by changing the solar panel connections while the controller is operating.
SETS OF 3 RED BLINKS

Battery voltage too high: Check that the correct GVB-8-WP has been selected for the nominal system battery voltage. If the nominal battery voltage is correct, check the functioning of other chargers that may be connected to the system. This error can also be caused by a disconnected battery or blown fuse.
SETS OF 5 RED BLINKS

Internal Error: Contact your dealer for assistance.
2 LONG BLINKS, FOLLOWED BY ANY NUMBER OF SHORT BLINKS

Battery voltage too low: The controller cannot begin charging due to low battery voltage. Charge the battery by some other means before use.
SETS OF 4 RED BLINKS SOLID RED OR OTHER LED INDICATIONS NOT LISTED

Troubleshooting

If the LED Indicator will not light, or displays an indication not listed in this manual:

  • Verify correct battery polarity;
  • Check that there is a solid electrical connection to the battery;
  • Check that battery voltage appears on the GVB-8-WP battery cables.

Note: The most common causes of blown fuses are:

  • Connecting the GVB-8-WP to the battery backwards;
  • Shorting the solar panel input while the GVB-8-WP is charging. In this case, there may be internal damage to the controller.

The GVB-8-WP will not operate without a battery. If the system appears to be overcharging or the GVB-8-WP will not begin charging, ensure that the solar panel is wired only to the GVB-8-WP. If the GVB-8-WP does not appear to be charging, note that the GVB-8-WP waits up to one minute before trying to restart if is has shut down due to lack of power from the solar panel. If the LED indicator will not light with a battery connected, or blinks the over- battery-voltage error, or the controller does not charge, the fuse may be blown. The GVB-8-WP fuse is located in a black waterproof in-line fuse holder in the positive battery line. If the fuse is blown, replace it with a 10 A fast-acting ATO or ATC fuse rated for the maximum battery voltage. Automotive- style fuses are typically rated to 32 V, and are suitable for the GVB-8-Pb- 12V-WP, GVB-8-Pb-24V-WP, GVB-8-Li-14.2V-WP, and GVB-8-Li-28.4V-WP. For versions 36 V and 48 V nominal, a fuse with a higher voltage rating is required. We recommend Optifuse part number APR58-UL-10A, rated 10 A / 58 V. For more in-depth system troubleshooting, please visit the support area of our website: https://sunforgellc.com/learning-center.

Specifications:

| GVB-8-WP, All Models
---|---
Rated Panel (Input) Current:¹| 8 A
Minimum Panel Voltage for Charging: | 5 V
Minimum Battery Voltage for Operation:| 9.5 V
Trickle Charge to Recover Dead (0V) Battery: | Yes
Maximum Input Panel: | 60 V
Recommended Max Panel Voc at STC:| 50 V
Input Voltage Range:| 0-60 V
Maximum Input Short Circuit Current:²| 8 A
Maximum Input Current:³| 15 A
Operating Temperature:| -40 °C – 85 °C
Maximum Full Power Ambient:| 50 °C
MPPT Tracking Speed:| 15 Hz
Environmental Protection:| IP68, Waterproof
Connection:4| Flying Leads, 12 AWG tinned wire, pre-stripped
Weight:| 10.3 oz. , 290 g
Dimensions:| 5.5 x 3.2 x 2.2” (14 x 8.1 x 5.5 cm)
Warranty:| 5 years

(1) Panel ratings have increased since we designed the GVB-8-WP. Although we don’t believe in changing specifications without a corresponding engineering change, based on both our customers’ experiences over the years as well as the headroom we designed into the GVB-8-WP, we feel comfortable recommending the GVB-8-WP for panels with Imp up to 9 A.
(2) Panel Isc. Maximum input power and maximum input voltage requirements must also be respected.
(3) Maximum current that the controller could draw from an unlimited source. This specification is not intended for determining PV input.
(4) Starting from S/N 188100, flying leads are 12 AWG instead of 16 AWG. For the previous version, please refer to manual revision 6.0 | 2021.

| GVB-8-Pb-12V-WP| GVB-8-Pb-24V-WP| GVB-8-Pb-36V-WP| GVB-8-Pb-48V-WP
---|---|---|---|---
Charge Profile:| Multi-Stage with Temperature Compensation
Nominal Battery Voltage:| 12 V| 24 V| 36 V| 48 V
Maximum Recommended Panel Vmp:| 13 V| 26 V| 41 V| 43 V
Maximum Recommended Panel Power (8A Panel w/~155mm cells):| 105 W| 210 W| 325 W| 350 W
Bulk Voltage:| 14.4 V| 28.8 V| 43.2 V| 57.6 V
Absorption Voltage:| 14.2 V| 28.4 V| 42.6 V| 56.8 V
Absorption Time:| 2 Hours
Float Voltage:5| 13.3 V| 26.6 V| 39.9 V| 53.2 V
Re-Absorb (Re-Bulk):6| 12.5 V| 25 V| 37.5 V| 50 V
Battery Temperature Compensation (referred to 25 °C):| -28 mV/°C| -56 mV/°C| -84 mV/°C| -112 mV/°C
Electrical Efficiency:| 95% – 97% typical| 96% – 98% typical| 96% – 98% typical| 96% – 99% typical
Night Consumption:| 7 mA| 6 mA| 6 mA | 5 mA
Battery type: | 4S LiFePO4| 8S LiFePO4| 10S Li-ion| 12S LiFePO4| 12S Li-ion| 13S Li-ion | 16S LiFePO4| 14S Li-ion
---|---|---|---|---|---|---|---|---
Charge Profile: | CC/CV
CV Voltage: | 14.2 V| 28.4 V| 41.7 V| 42.6 V| 50 V| 54.2 V| 56.8 V| 58.4 V
Battery Temperature Compensation:| Disabled
Maximum Recommended Panel Vmp:| 13 V| 26 V| 39 V| 39 V| 41 V| 43 V| 43 V| 43 V
Maximum Recommended Panel Power:| 105 W| 210 W | 325 W| 325 W| 325 W | 350 W| 350 W| 350 W
Electrical Efficiency:| 95% – 97% typical| 96% – 98% typical | 96% – 98% typical| l 96% – 98% typical| 96% – 98% typical| 96% – 99% typical| 96% – 99% typical | 96% – 99% typical
Night Consumption:| 7 mA| 6 mA| 6 mA| 6 mA| 6 mA| 5 mA| 5 mA| 5 mA

(5) Starting from S/N 188100, the Float Voltage was reduced on Pb models. For the previous version, please refer to manual revision 6.0 | 2021.
(6) If the battery voltage drops below this point, the controller will attempt to run an absorption cycle. Otherwise, it will charge to the float voltage.
Copyright © 2024 Sunforge LLC. All rights reserved. Changes are periodically made to the information herein which will be incorporated in revised editions of this publication. Sunforge may make changes or improvements to the product(s) described in this publication at any time and without notice.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GENASUN User Manuals

Related Manuals