MOXA MGate EIP3170 Series 1 and 2-Port EtherNet IP-to-DF1 Gateways
Installation Guide
Technical Support Contact Information
www.moxa.com/support
Overview
The MGate EIP3170 and EIP3270 are 1- and 2-port DF1-to-EtherNet/IP gateways that provide protocol conversions for users who need to connect Rockwell Automation PLCs to an EtherNet/IP network. The MGate EIP3000 Series products support up to 8 EtherNet/IP clients and 8 EtherNet/IP servers simultaneously. Each client can send up to 16 requests at one time.
Package Checklist
Before installing the MGate EIP3170 or EIP3270, verify that the package contains the following items:
- MGate EIP3170 or EIP3270 DF1 to EtherNet/IP gateway
- Quick installation guide (printed)
- Warranty card
Optional Accessories:
- DK-35A: DIN-rail mounting kit (35 mm)
- Mini DB9F-to-TB Adaptor: DB9 female to terminal block adapter
- DR-4524: 45W/2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
- DR-75-24: 75W/3.2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
- DR-120-24: 120W/5A DIN-rail 24 VDC power supply with 88 to 132 VAC/176 to 264 VAC input by switch
Please notify your sales representative if any of the above items is missing or damaged.
Hardware Introduction
LED Indicators
Reset Button
The reset button is used to load factory defaults. Use a pointed object such as a straightened paper clip to hold the reset button down for five seconds. Release the reset button when the Ready LED stops blinking.
Panel Layouts
The MGate EIP3170 has a male DB9 port and a terminal block for connecting to serial devices. The MGate EIP3270 has two DB9 connectors for connecting to serial devices.
Hardware Installation Procedure
STEP 1: Use a standard straight-through Ethernet cable to connect the unit to
a network hub or switch.
STEP 2: Connect your device to the unit’s serial port.
STEP 3: Mount the unit on a DIN-rail.
STEP 4: Connect the power source to power input.
Wall or Cabinet Mounting
Mounting the MGate EIP3170/3270 on to a wall requires two screws. The heads of
the screws should be 5 to 7 mm in diameter, the shafts should be 3 to 4 mm in
diameter, and the length of the screws should be more than 10.5 mm.
NOTE: Wall mounting is certified for use in maritime applications.
Software Installation Information
You can download the MGate Manager, User’s Manual, and Device Search Utility (DSU) from Moxa’s website: www.moxa.com. Please refer to the User’s Manual for additional details on using the MGate Manager and DSU. Default IP address: 192.168.127.254
Pin Assignments
Ethernet Port (RJ45)
Environmental Specifications
This device complies with Part 15 of the FCC rules.
Operation is subject to the following conditions:
- This device may not cause harmful interference.
- This device must accept any interference received, including interference that may cause undesired operation.
ATEX and IECEx Information
EIP3170/ EIP3270 Serial
-
Certificate number: DEMKO 18 ATEX 2168X
-
IECEx number: IECEx UL 18.0149X
-
Certification string: Ex nA IIC T4 Gc
Ambient Range : 0°C ≤ Tamb ≤ 60°C (For suffix without -T)
Ambient Range : -40°C ≤ Tamb ≤ 75°C (For suffix with -T) -
Standards covered:
ATEX: EN 60079-0:2012+A11:2013, EN 60079-15:2010
IECEx: IEC 60079-0 Ed.6; IEC 60079-15 Ed.4 -
The conditions of safe usage:
• The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC/EN 60664-1.
• The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP4 in accordance with IEC/EN 60079-0.
• Conductors suitable for Rated Cable Temperature ≥ 100°C
• Input conductor with 28-12 AWG (max. 3.3 mm2) to be used with the devices
EIP3170I/ EIP3270I Serial
-
ATEX Certificate number: DEMKO 19 ATEX 2232X
-
IECEx number: IECEx UL 19.0058X
-
Certification string: Ex nA IIC T4 Gc
Ambient Range : 0°C ≤ Tamb ≤ 60°C (For suffix without -T)
Ambient Range : -40°C ≤ Tamb ≤ 75°C (For suffix with -T) -
Standards covered:
ATEX: EN 60079-0:2012+A11:2013, EN 60079-15:2010
IECEx: IEC 60079-0 Ed.6; IEC 60079-15 Ed.4 -
The conditions of safe usage:
• The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC/EN 60664-1.
• The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP 54 in accordance with IEC/EN 60079-0.
• Conductors suitable for Rated Cable Temperature ≥ 100°C
• Input conductor with 28-12 AWG (max. 3.3 mm2) to be used with the devices
Address of manufacturer: No. 1111, Heping Rd., Bade Dist.,
Taoyuan City 334004, Taiwan