nvent RAYCHEM E-40 Heat Shrink End Seal Instructions

June 6, 2024
nVent RAYCHEM

nvent RAYCHEM E-40 Heat Shrink End Seal

Tools Required

How to install

Specific conditions of use

  • Maximum voltage: 480 V
  • Maximum exposure temperature: 260°C (500°F)
  • Minimum installation temperature: –60°C (–76°F)

Installation instructions for nVent RAYCHEM E-40 end seal kit. For use with all nVent RAYCHEM XTV, KTV, HTV, and VPL heating cables.
WARNING: To prevent elec tri cal shock, short circuit or arcing, this product must be installed correctly and water ingress must be avoided ed before and during the installation.
Before installing this product, read the installation instructions completely.

  • Earth fault equipment protection is required for each circuit.
  • De-energise circuits before installation or servicing.
  • Keep ends of Trace heaters and kit components dry before and during installation.
  • The electrically conductive covering of this trace heater shall be connected to a suitable earthing terminal.
  • The presence of the trace heaters shall be made evident by the posting of caution signs or markings at appropriate locations and/or at frequent intervals along the circuit.
  • The insulation resistance of the trace heater shall be measured and recorded after installation and shall not less than 20 Mohm.
  • Persons involved in the installation and testing of electric trace heating systems shall be suitably trained in all special techniques required.
  • Installation shall be carried out under the supervision of a qualified person.
  • Refer to installation manual. A ground fault circuit interrupter shall be used with this device.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

nVent RAYCHEM User Manuals

Related Manuals