nVent RAYCHEM E-100-L-E End Seal with Indicator Light Instructions

October 30, 2023
nVent RAYCHEM

nVent RAYCHEM E-100-L-E End Seal with Indicator Light

Product Information

The E-100-L-E is an end seal kit designed for use with all nVent RAYCHEM BTV, QTVR, XTV(R), KTV, HTV, and VPL heating cables. It has a rating of II 2 G Ex eb mb IIC T* Gb and is certified by Sira 14ATEX3015X, CSAE 21UKEX3716X, and IECEx SIR14.0007X. The end seal has a rated voltage of 277 V and an IP66 rating. It is suitable for use in hazardous locations classified as Class I, Div. 2, Groups A,B,C,D; Class II, Div. 1 and 2, Groups E,F,G; and Class III. The maximum surface temperature is directly related to the associated process temperature and heat tracing cable with which it is assembled.

Product Usage Instructions

  1. Read the installation instructions completely before installing the product.
  2. To prevent electrical shock, short circuit or arcing, the product must be installed correctly and water ingress must be avoided before and during the installation.
  3. Avoid skin and eye contact with sealing grease. Consult Material safety data sheet VEN 0033 (INSTALL027).
  4. Do not disconnect while the circuit is live or unless the area is free of ignitible concentrations.
  5. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charges on non-conducting surfaces.
  6. Cleaning of the equipment should be done with a damp cloth that is being used.
  7. The supply circuit shall be protected by a fuse capable of withstanding a prospective short current of 1500A.
  8. The Lighted End Seals must be pipe mounted in a single orientation, with the gland entry adjacent to the process pipe, as per the manufacturer’s installation instructions.
  9. Refer to the heating system certificate IECEx PTB 21.0007X; PTB 21 ATEX 1003X (a) for HTV heating cable with E-100-L-E.
  10. For the system Temperature Code, see the heating cable or design documentation.

WHAT INBOX

nVent-RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(2\)

TOOLS REQUIREDnVent-RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(3\)

WIRING

nVent-RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(4\)

E-100-L-E

  • Sira 14ATEX3015X
    • II 2 D Ex tb IIIC T***°C Db
    • II 2 G Ex eb mb IIC T* Gb
  • CSAE 21UKEX3716X
    • IP66
    • Ta = –40°C to +40°C
  • IECEx SIR14.0007X
  • Rated Voltage: 277 V
    • Ex eb mb IIC T* Gb
    • Ex tb IIIC T***°C Db

For HTV heating cable with E-100-L-E; refer to heating system certificate IECEx PTB 21.0007X; PTB 21 ATEX 1003X (a)

  • RU C-BE.МЮ62.B.00054/18
  • Ex e mb IIC Gb U Ex tb mb IIIC Db U
  • Ta –55°C…+40°C IP66
  1. Ex eb mb IIC T* Gb
  2. Ex mb tb IIIC T*°C Db
  • Ex eb mb IIC T* Gb
  • Ex tb IIIC T*°C Db IP66
  • IEx 15.0089X

Hazardous Locations

  • Class I, Div. 2, Groups A,B,C,D
  • Class II, Div. 1 and 2, Groups E,F,G
  • Class III
  • Type 4X Temp Code T*
  1. Ex eb mb IIC T Gb CL I ZN 1 AEx eb mb IIC T Gb
  2. Class I, Div. 2, Groups A,B,C,D
  3. Class II, Div. 1 and 2, Groups E,F,G
  4. Class III
  5. Type 4X Temp Code T*

(a) IECEx PTB 21.0007X, PTB 21 ATEX 1003X : Für HTV-Heizkabel mit E-100-L-E / Pour le câble chauffant HTV avec E-100-L-E / Voor HTV-verwarmingskabel
met E-100-L-E / For HTV varmekabel med E-100-L-E / För HTV värmekabel med E-100-L-E / For HTV-varmekabel med E-100-L-E / HTV lämpökaapeli yhdessä
E-100‑L-E loppupäätteen kanssa / Per il cavo scaldante HTV con E-100-L-E / Para el cable calefactor HTV con E-100‑L-E / Dla przewodów grzejnych HTV i zestawów zakończeniowych E-100-L-E / Данные о греющем кабеле HTV с E-100-L-E см. / Pro topný kabel HTV s E-100-L-E / Az E-100-L-E-vel ellátott
HTV fűtőkábel / Za HTV grijaći kabel s E-100-L-E.

ASSEMBLING

nVent-RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(11\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(12\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(13\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(14\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(15\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(16\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(17\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(18\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(19\) nVent-
RAYCHEM-E-100-L-E End-Seal-with-Indicator-Light-FIG-
\(20\)

Hazardous locations

The temperature class/maximum surface temperature is directly related to the associated process temperature and heat tracing cable with which it is assembled, refer to Conditions of Manufacture for the appropriate equipment marking. For system Temperature Code, see heating cable or design documentation.

Behalve

  1. HTV
  2. KTV

Warning:

  • To prevent electrical shock, short circuit or arcing, this product must be installed correctly and water ingress must be avoided before and during the installation.

  • Avoid skin and eye contact with sealing grease. Consult Material safety data sheet VEN 0033 (INSTALL027).

  • Before installing this product, read the installation instructions completely.
    Warning : Explosion and shock hazard.

  • Do not disconnect while the circuit is live or unless the area is free of ignitible concentrations

Specific Conditions of Use

  1. Some external parts of the system are non-conducting and may generate an ignition-capable level of electrostatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charges on non-conducting surfaces. Additionally, cleaning of the equipment should be done with a damp cloth
  2. The maximum process temperature of the Lighted End Seals is limited to 150°C; this may be further limited by the type of heating cable that is being used. When fitting the Lighted End Seals, the user/installer shall take into account any restrictions that are applicable to the cable
  3. The supply circuit shall be protected by a fuse capable of withstanding a prospective short current of 1500A
  4. The Lighted End Seals must be pipe mounted in a single orientation, with the gland entry adjacent to the process pipe, as per the manufacturer’s installation instructions

Maximum pipe temperature:


Heater type

| ****

Tmax continuous

| Tmax intermittent

1000h cumulative *****

| ****

Tmax power off

---|---|---|---
BTV| 65°C| 85°C| –
QTVR| 110°C| 110°C| –
XTV| 121°C| 250°C| –
XTVR| 150°C| 250°C| –
KTV| 150°C| 250°C| –
HTV| 205°C| 260°C| –
VPL| See tables below| –| 250°C
Cable| 110 V| Cable| 230 V| 254 V
---|---|---|---|---
5VPL1-CT| 235°C| 5VPL2-CT| 230°C| 225°C
10VPL1-CT| 215°C| 10VPL2-CT| 210°C| 200°C
15VPL1-CT| 190°C| 15VPL2-CT| 180°C| 145°C
20VPL1-CT| 150°C| 20VPL2-CT| 150°C| Not allowed

Ambient Temperature: ATEX/IECEx –40°C to +40°C; EAC: –55°C to +40°C
Installation instructions for nVent RAYCHEM E-100-L-E end seal kit. For use with all nVent RAYCHEM BTV, QTVR, XTV(R), KTV, HTV and VPL heating cables. 2000h XTVR and HTV

Apply end seal label to insulation. Apply insulation and cladding. Weather seal the stand entry.
Leave these instructions with the end user for future reference

Serbia and Montenegro
Tel +381 230 401 770
Fax +381 230 401 770
salesee@nVent.com
Schweiz/Suisse
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoBaar@nVent.com
Suomi
Puh 0800 11 67 99
salesfi@nVent.com
Sverige
Tel +46 31 335 58 00
salesse@nVent.com
Türkiye
Tel +90 560 977 6467
Fax +32 16 21 36 04
salesee@nVent.com
United Kingdom
Tel 0800 969 013
salesthermalUK@nVent.com
België/Belgique
Tel +32 16 21 35 02
Fax +32 16 21 36 04
salesbelux@nVent.com
Bulgaria
Tel +359 5686 6886
Fax +359 5686 6886
salesee@nVent.com
Česká Republika
Tel +420 602 232 069
czechinfo@nVent.com
Denmark
Tel +45 70 11 04 00
salesdk@nVent.com
Deutschland
Tel 0800 1818205
salesde@nVent.com
España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
ntm-sales-es@nVent.com
France
Tél 0800 906045
salesfr@nVent.com
Hrvatska
Tel +385 1 605 01 88
Fax +385 1 605 01 88
salesee@nVent.com
Italia
Tel +39 02 577 61 51
Fax +39 02 577 61 55 28
salesit@nVent.com