This step-by-step design guide provides the tools necessary to design a nVent RAYCHEM Hot Water Temperature Maintenance System (HWAT). For additional information, contact your nVent representative or call (800) 545-6258. Also, visit our website at nVent.com/RAYCHEM.
INTRODUCTION
nVent RAYCHEM Hot Water Temperature Maintenance (HWAT) systems are a smart
alternative to conventional recirculation systems for meeting modern Green
energy and plumbing code that save water, energy and improve water quality.
HWAT systems consist of an electronic controller, self-regulating electric
heating cables, pipe insulation and easy-to-install connection kits. The
heating cables are attached to hot water supply pipes to compensate for heat
loss and maintains water temperature to point of use, thus eliminating the
need for return piping, balancing valves and associated equipment. When used
in concert with conventional designs, it can optimize the overall efficiency
of the hot water delivery system.
While our HWAT 208-277 V solutions have been delivering the benefits of Hot
Water Temperature Maintenance immediate hot water at the tap, reduced water
waste, and space and cost savings in mixed use high-rise buildings, schools
and hotels for quite some time, our new HWAT 120 V system now offers the added
value of a more residential / multi-family building-friendly “behind-the-
meter” application.
When submetering is required by code, a conventional design would typically
require a water heater installation for every unit in the building or a
complex circulation system. A HWAT 120 V system, along with a central water
heating unit, delivers a more economical solution that enables efficient and
inexpensive metering and billing for each individual unit’s hot water usage
without complex system design and installations.
Additionally, our high quality HWAT systems improve water quality by meeting
ASHRAE 188 Legionella control guidelines. HWAT systems are eligible for LEED
points for both Energy Savings and Innovation in Design.
Typical Applications
The HWAT system is designed to be installed and operated in commercial and
residential buildings. Table 1 shows typical HWAT applications, desired
maintain temperatures when nVent RAYCHEM HWAT-P1 heating cable is used in
conjunction with the nVent RAYCHEM HWAT-ECO-GF, or when nVent RAYCHEM HWAT-R2
heating cable is used in conjunction with the nVent RAYCHEM HWAT-ECO-GF or
ACS-30 controllers.
Table 1 Typical HWAT Applications
Application | Desired maintain temperature |
---|---|
Hospitals, nursing homes | 105°F (40°C) |
Schools, prisons, some hospitals | 115°F (45°C) |
Offices, hotels, homes and apartments | 125°F (50°C) |
Kitchens, laundries | 140°F (60°C)* |
-
with HWAT-R2 only.
This design guide covers standard HWAT applications which must meet the following conditions:- Installed on copper or rigid plastic pipes
- Insulated in accordance with the insulation schedule shown in Table 6
- Powered at 120 V using HWAT-ECO-GF or at 208 – 277 V using the ACS-30 or HWAT-ECO-GF controller
- Operated indoors where the ambient temperature is relatively constant and between 60°F (15°C) and 80°F (27°C)
If your application does not meet the above conditions, contact your nVent
representative for custom design assistance.
Approvals and Code Compliance
The HWAT system components are c-UL-us Listed in nonhazardous locations.
HWAT-P1 and HWAT-R2 heating cables, RayClic, HWT and FTC-HST-PLUS connection
kit and the HWAT-ECO-GF controller are c-UL-us Listed and the ACS-CRM and the
ACS-CRMS controllers are c-UL-us certified (ACS-UIT3) to US and Canadian
standards for us in non-hazardous locations. Refer to the specific product
data sheets for details.
The HWAT system is designed in accordance with the following international and
national codes:
- International Plumbing Code
- International Building Code
- International Energy Conservation Code
- National Standard Plumbing Code
- National Electrical Code
- Canadian Electrical Code
- ANSI/ASHRAE Standard 188-2018 – Legionellosis: Risk Management for Building Water Systems
- CIBSE TM13-2013 Minimising the Risk of Legionnaires Disease
Additionally, our HWAT solution has numerous state and local code approvals.
Contact your nVent representative for further information. Due to its
potential to reduce energy usage and greenhouse gas emissions, HWAT solutions
are eligible for LEED points.
Safety Guidelines
The safety and reliability of any heat-tracing system depends on the quality
of the products selected and on proper design, installation, and maintenance.
Incorrect design, handling, installation, or maintenance of any of the system
components can cause underheating or overheating of the pipe or damage to the
heating cable system and may result in system failure, electric shock, or
fire. The guidelines and instructions contained in this guide are important.
Follow them carefully to minimize these risks and to ensure that the HWAT
system performs reliably.
Pay special attention to safety warnings identified as WARNING.
Ground Fault Protection
To minimize the danger of fire from sustained electrical arcing if the heating
cable is damaged or improperly installed, and to comply with nVent
requirements, agency certifications, and national electrical codes, ground
fault equipment protection must be used on each heating cable branch circuit.
Arcing may not be stopped by conventional circuit breakers. The HWAT-ECO-GF
and ACS-30 controllers meet the electrical code requirements for ground fault
equipment protection.
Scald Protection
WARNING: Water temperature above 130°F (55°C) presents a significant
risk of personal injury and/or death and requires that scald protection
measures be implemented for safe use.
HWAT systems present an increased risk of scalding due to the high water
temperature. Pay special attention to the scald warning to the left.
Design Requirements
To comply with warranty requirements, the design and installation of the HWAT
system must be in accordance with this guide and the additional documents
listed below:
- HWAT-ECO-GF Installation and Operations Manual (H60223)
- HWAT System Installation and Operations Manual (H57548)
- Rayclic Connection Kit Installation Instructions (H55388 and H55092)
Installation documents are shipped with the respective products and are also available on our website at nVent.com/RAYCHEM.
SYSTEM OVERVIEW
A complete HWAT system includes one or more HWAT-ECO-GF or ACS-30 electronic
controllers, HWAT-P1 or HWAT-R2 heating cable and nVent RAYCHEM RayClic
connection kits. Fig. 1 illustrates a typical HWAT system. The key components
of the system will be described in this section. HWAT Electronic Controllers
The HWAT-ECO-GF electronic controller is designed for use with a single
circuit of HWAT-P1 or HWAT-R2 self-regulating heating cable. For large hot
water systems the ACS-30 distributed controller is available, refer to the
ACS-30 data sheet (H58261) for more information. The HWAT-ECO-GF provides a
variety of features and control options, listed below, for your hot water
temperature maintenance system.
- Equipment rated ground fault protection built-in
- Intuitive set-up and programming, includes a 5″ inch color touch screen
- Flexible temperature control of hot water temperature maintenance systems
- Energy savings through an integrated function that lowers the maintain temperature during hours of low water consumption
- Heat-up cycle function that increases the water temperature of the hot water in the pipes
- Alarm relay to signal power, temperature or communication problems
- Hot water storage and pipe temperature monitoring with high and low temperature alarms and automatic system shut down
- Seven pre-defined building timer programs that can be customized by the user
- Program in advance in power-off mode by using external power bank/charger and USB connection
HWAT Heating Cables
HWAT-P1 or HWAT-R2 self-regulating heating cables are installed on hot water
supply pipes underneath standard pipe insulation. The heating cable adjusts
its power output to reduce the effect of ambient temperature swings. The HWAT
system provides continuous hot water temperature maintenance while eliminating
the need for a recirculation system. HWAT heating cables provide the following
features:
- Adjust power output to reduce the variations in water temperature
- Can be cut to length, spliced, teed, and terminated in the field
- Designed for use with the HWAT-ECO-GF or ACS-30 controller
RayClic, FTC and HWT Connection Kits
The RayClic connection system is a simple, fast, and reliable set of
connection kits developed for use with HWAT self-regulating heating cables.
RayClic connection kits reduce installation time, lowering the total installed
cost of the HWAT system. nVent RAYCHEM HWT-P and FTC-HST-PLUS heat shrink kits
may also be used.
DESIGN GUIDELINES
This section describes the seven steps necessary to design an HWAT system:
- Select the heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configurations
- Select thermal insulation
- Complete Bill of Materials
To assist you with the design, we will carry two design examples through this
process. The example details are listed below each step in red.
Example 1
An elementary school where 115°F (46°C) is the desired maintain temperature
and no heat-up cycle is required. Piping layout shows approximately 300 ft of
pipe with two branches at the same location.
Example 2
A medium security prison where 115°F (46°C) is the desired maintain
temperature and a 140°F (60°C) heat-up cycle is required. Piping layout shows
approximately 700 ft of pipe with two branches at different locations.
Before You Begin
Before you begin designing your HWAT system, gather this necessary
information:
- Desired maintain temperature
- Indoor ambient temperature
- Supply voltage
- Piping layout
- Total pipe length
- Pipe diameters
HWAT System Design
- Select heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configuration
- Select insulation
- Complete Bill of Materials
Step 1 Select heating cable
Use Table 2 to select the appropriate system temperature setting. For more
information on heat-up cycles, refer to the HWAT-ECO-GF Installation and
Operations Manual (H60223) or ACS-30 Programming Guide (H58692).
Heating Cable Catalog Number
Before beginning, take a moment to understand the structure underlying heating
cable catalog numbers. You will refer to this numbering convention throughout
the product selection process. Your goal is to determine the catalog number
for the product that best suits your needs.
Catalog Number: HWAT-P1 or R2
Voltage P1 = 120 V
R2 = 208, 240, 277 V
Fig. 5 Heating cable catalog number
Record the following information:
- Desired maintain temperature (°F/°C) _____
- Indoor ambient temperature (°F/°C) _____
- Supply voltage (V) _____
- Heat-up cycle (Yes/No) _____
- Temperature (°F/°C) _____
Example: Heating Cable Selection
Desired maintain temperature
Ambient temperature
Supply voltage
Heat-up cycle required
Heat-up cycle temperature| Example 1
115°F (46°C)
70°F (21°C)
208 Vac
No
n/a| Example 2
115°F (46°C)
70°F (21°C)
208 Vac
Yes
140°F (60°C)
---|---|---
Table 2 HWAT System Temperature Range
| HWAT-ECO-GF| ACS-30
---|---|---
Minimum maintain temperature| 105°F (40°C)| 100°F (38°C)
Maximum maintain temperature (HWAT-R2)| 140°F (60°C)| 150°F (66°C)
Maximum maintain temperature (HWAT-P1)| 130°F (54°C)|
Heat-up cycle*| >140°F (60°C)| >150°F (66°C)
WARNING: Water temperature above 130°F (55°C) presents a significant risk of personal injury and/or death and requires that scald protection measures be implemented for safe use.
- For additional information on heat-up cycles, refer to the “Expanded HWAT-ECO-GF Electronic Controller Capabilities” section of the HWAT-ECO-GF Installation and Operations Manual (H60223).
Heating Cable Selection
Heating cable selected| Example
HWAT-R2
---|---
HWAT System Design
- Select heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configuration
- Select insulation
- Complete Bill of Materials
Step 2 Lay out the heating cable
The piping layout of your building may require more than one HWAT circuit.
To determine the number of circuits, group your piping by maintain temperature
and location, a step that may require you to consult the plumbing and/or
electrical engineer. Calculate the total length of pipe in each group,
allowing one foot of heating cable for each foot of pipe. The length of
heating cable in each group must not exceed the circuit lengths listed in
Table 3.
In Step 4, you will calculate the additional cable required to install the
connection kits. This will increase the total length of heating cable and may
require the need for additional circuits.
Table 3 Maximum Circuit Length
| Circuit Lengths
---|---
Circuit breaker size (Amps)| HWAT-P1 @120 V ft (m)| HWAT-R2
@208-277 V ft (m)
10| 125 (38)|
15| 195 (59)| 250 (75)
20| 276 (84)| 330 (100)
30| 395 (120)| 500 (150)
Note: Assumes a minimum water temperature of 50°F (10°C) at startup
Example: Lay out Circuits
HWAT heating cable selected
Length of pipe
Number of circuits
Circuit breaker size| Example
HWAT-R2
700 ft
2
30 Amp
---|---
HWAT System Design
- Select heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configuration
- Select insulation
- Complete Bill of Materials
Step 3 Select connection kits and accessories
HWAT systems are approved and warranted only as a complete system. The
appropriate RayClic, FTC or HWT connection kits must be used. Use Table 4 to
select the connection kits and accessories necessary for your HWAT system.
Refer to the RayClic Connection System data sheet (H57545) and the FTC Heat
Shrinkable Connection Kits Datasheet (H58159) in the Technical Data section
for more information on the products.
The appropriate numbers of end seals are included with each connection kit.
Table 4 Connection Kits and Accessories
Catalog number| Description| Quantity required| No. of end
seals included
---|---|---|---
RayClic-PC| Power connection kit| One -PC, -PS, -PT required per circuit| 1
RayClic-PS| Powered splice kit| One -PC, -PS, -PT required per circuit| 2
RayClic-PT| Powered tee kit| One -PC, -PS, -PT required per circuit| 3
RayClic-S| Splice kit| As required*| 0
RayClic-X| Cross kit| As required| 2
RayClic-T| Tee kit| As required| 1
RayClic-E| End seal kit| As required for spares| 1
HWT-P| Heat shrink power connection kit| One required per circuit| 1
FTC-HST-PLUS| Heat shrink splice or tee kit| As required| 0
GT-66| Glass tape| 1 roll per 50 ft of pipe| n/a
ETL| Electric traced tape| 1 label per 10 ft of pipe| n/a
- To minimize cable waste, nVent recommends that one RayClic-S be ordered for every 500 feet of cable.
Example: Select Connection Kits and Accessories
Piping layout determined that the following connection kits and accessories
are required.| Example
2 RayClic-PC
2 RayClic-T
14 G T- 66
70 ETL
---|---
HWAT System Design
- Select heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configuration
- Select insulation
- Complete Bill of Materials
Step 4 Finalize circuit length
Additional cable is required for future access at each connection kit. Add the
additional cable, as detailed in Table 5, to the estimated circuit lengths
from Step 2. Confirm that the maximum lengths shown in Table 3 have not been
exceeded. If your circuit lengths are greater than those shown, reconfigure
your heating cable layout to allow for additional circuits.
Table 5 Additional Cable Required for Each Connection Kit
Connection kit name| No. of cable connections/kit| Cable length/
connection ft (m)| Total cable length (service loop) ft (m)
---|---|---|---
RayClic-PC| 1| 2.0 (0.6)| 2.0 (0.6)
RayClic-S| 2| 1.0 (0.3)| 2.0 (0.6)
RayClic-T| 3| 1.0 (0.3)| 3.0 (0.9)
RayClic-X| 4| 1.0 (0.3)| 4.0 (1.2)
RayClic-PS| 2| 1.5 (0.5)| 3.0 (0.9)
RayClic-PT| 3| 1.3 (0.4)| 4.0 (1.2)
RayClic-E| 1| n/a| n/a
HWT-P| 1| 2.0 (0.6)| 2.0 (0.6)
FTC-HST-PLUS| 2 or 3| 1.0 (0.3)| 2.0 (0.6) for a splice
3.0 (0.9) for a tee
Example: Finalize Circuit Length
Length of heating cable per circuit Additional cable required
RayClic-PC
RayClic-T
RayClic-X
Total length of heating cable required| Example Circuit 1
350 ft
2 ft
3 ft
n/a
355 ft| Circuit 2
350 ft
2 ft
3 ft
n/a
355 ft
---|---|---
-
In this example, the circuits were evenly divided. Equal circuit lengths are not required.
HWAT System Design- Select heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configuration
- Select insulation
- Complete Bill of Materials
Step 5 Select control configuration
For single circuit applications, choose the HWAT-ECO-GF controller.
For multi-circuit applications, choose the ACS-30 controller.
Example: Select Control Method
Type
Number of circuits
Controller| Example 1
Individual circuit
1
HWAT-ECO-GF| Example 2
Multi-circuit
up to 260
ACS-30
---|---|---
HWAT System Design
- Select heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configuration
- Select insulation
- Complete Bill of Materials
Step 6 Select insulation
Select the size of thermal insulation from Table 6. You will need to know the
length and diameter of each pipe used in your application.
For pipes 1¼ inches and smaller, use insulation that is oversized by ¼ inch to
allow room for insulating over the heating cables. Table 6 specifies IPS (Iron
Pipe Size) insulation, which has a greater inner diameter than CTS (Copper
Tube Size) insulation.
For pipes 3 inches and larger, the thickness of insulation can either be equal
to the pipe diameter with a single heating cable or 1/3 the pipe diameter with
two heating cables. For example, a 6 inch pipe with 6 inches of insulation and
one run of heating cable is equivalent to a 6 inch pipe with 2 inches of
insulation and two runs of heating cable.
Table 6 Fiberglass Insulation Selection
Copper pipe size (in)| IPS insulation size (in)| Insulation
thickness (in)
---|---|---
½| ¾| ½
¾| 1| 1
1| 1½| 1
1¼| 1½| 1½
1½| 1½| 1½
2| 2| 2
2½| 2½| 2½
3| 3| 3
Example: Sel| ect Insulation| |
---|---|---|---
| Copper pipe size (in)| IPS insulation size (in)| Insulation
thickness (in)
Example 1| ¾| 1| 1
1| 1¼| 1
1½| 1½| 1½
Example 2| 1| 1¼| 1
2| 2| 2
2½| 2½| 2½
HWAT System Design
- Select heating cable
- Lay out the heating cable
- Select connection kits and accessories
- Finalize circuit length
- Select control configuration
- Select insulation
- Complete Bill of Materials
Step 7 Complete bill of materials
You are now ready to compile a Bill of Materials. Using the design results,
detail each item as shown in Table 7 below. Fig. 5 illustrates a complete
typical HWAT system. Table 7
Bill of Materials (Example)
Description | Catalog number | Quantity |
---|---|---|
HWAT heating cable | HWAT-R2 | 706 ft |
Power connection kit | RayClic-PC | 2 |
Tee connection kit | RayClic-T | 2 |
Controller | HWAT-ECO-GF | 2 |
Attachment tape | GT-66 | 12 rolls |
Labels | ETL | 70 |
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com
Our powerful portfolio of brands:
CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACER
©2023 nVent. All nVent marks and logos are owned or licensed by nVent Services
GmbH or its affiliates. All other trademarks are the property of their
respective owners.