nVent RAYCHEM E-40 End Seal User Manual
- May 15, 2024
- nVent RAYCHEM
Table of Contents
nVent RAYCHEM E-40 End Seal
Package Content
E-40
ATEX / UKEX | IECEX |
---|---|
XTV(R) | SGS20ATEX0049X / |
BAS21UKEX0499X
II 2 G Ex 60079-30-1 eb IIC T* Gb
II 2 D Ex 60079-30-1 tb IIIC T°C Db
II 2 G Ex 60079-30-1 eb mb IIC T* Gb
II 2 D Ex 60079-30-1 mb tb IIIC T*°C Db Tmin –60°C| IECEx BAS.06.0044X
Ex 60079-30-1 eb IIC T Gb
Ex 60079-30-1 tb IIIC T°C Db
Ex 60079-30-1 eb mb IIC T* Gb
Ex 60079-30-1 mb tb IIIC T°C Db Tmin –60°C
KTV| SGS20ATEX0051X /
BAS21UKEX0500X
II 2 G Ex 60079-30-1 eb IIC T226°C (T2) Gb
II 2 D Ex 60079-30-1 tb IIIC T226°C Db
II 2 G Ex 60079-30-1 eb mb IIC T226°C(T2) Gb
II 2 D Ex 60079-30-1 mb tb IIIC T226°C Db Tmin –60°C| IECEx BAS.06.0046X
Ex 60079-30-1 eb IIC T226°C (T2) Gb
Ex 60079-30-1 tb IIIC T226°C Db
Ex 60079-30-1 eb mb IIC T226°C(T2) Gb
Ex 60079-30-1 mb tb IIIC T226°C Db Tmin –60°C
HTV| PTB 21 ATEX 1003 X /
BAS21UKEX0649X
II 2 G Ex 60079-30-1 eb IIC T Gb
II 2 D Ex 60079-30-1 tb IIIC T°C Db
II 2 G Ex 60079-30-1 eb mb IIC T* Gb
II 2 D Ex 60079-30-1 mb tb IIIC T°C Db Tmin –60°C| IECEx PTB 21.0007X
Ex 60079-30-1 eb IIC T* Gb
Ex 60079-30-1 tb IIIC T*°C Db
Ex 60079-30-1 eb mb IIC T Gb
Ex 60079-30-1 mb tb IIIC T°C Db Tmin –60°C
VPL| SGS20ATEX0045X / BAS21UKEX0503X
I 2 G Ex 60079-30-1 eb IIC T* Gb
II 2 D Ex 60079-30-1 tb IIIC T°C Db
II 2 G Ex 60079-30-1 eb mb IIC T* Gb
II 2 D Ex 60079-30-1 mb tb IIIC T*°C Db
Tmin –60°C () By design with TraceCalc Pro® Engineering Software and as
shown in the approval| IECEx BAS 06.0048X
Ex 60079-30-1 eb IIC T* Gb
Ex 60079-30-1 tb IIIC T°C Db
Ex 60079-30-1 eb mb IIC T* Gb
Ex 60079-30-1 mb tb IIIC T°C Db Tmin –60°C
| ООО Центр «ПрофЭкс» ЕАЭС RU C BE.AЖ58.B.01728/21
1 Ex e IIC T Gb X Ex tb IIIC T Db X
TЕМП ОКР СРЕДЫ –60 to +56°C
XTV(R),
KTV,
HTV,
VPL| | cCSAus Certificate 1333271X
Class I Division 2 Group A, B, C, D; Class II /
III Division 2 Group E, F, G
Ex 60079-30-1 IIC T Gb
Ex 60079-30-1 IIIC T Db
Class I Zone 1 AEx eb IIC T Gb Zone 21 AEx tb IIIC T Db Only for nVent
RAYCHEM XTV(R), KTV, HTV and VPL1 Um= 277 V (XTV(R), KTV, HTV) and 480 V max
(VPL)
ATEX / UKEX| IECEX*
---|---
HTV| | CL I DIV 2 GRP ABCD T CLI ZN 2 GRP IIC CLII/III DIV2
GRP FG T ZN 22 IIIB T
CL I DIV 2 (ZN 2) GRP ABCD T* CLII/III DIV 2 (ZN22*)
GRP EFG T -WS for CANADA
(** PER CE CODE TABLE 18)
FM20US0147X
FM20CA0073X
Um= 277 V max
Specific conditions of use
Maximum voltage: 480 V
Maximum exposure temperature: 260°C (500°F)
Minimum installation temperature: –60°C (–76°F)
Installation instructions for nVent RAYCHEM E-40 end seal kit. For use with
all nVent RAYCHEM XTV(R), KTV, HTV and VPL heating cables.
WARNING: To prevent electrical shock, short circuit or arcing, this
product must be installed correctly and water ingress must be avoided before
and during the installation.
Before installing this product, read the installation instructions completely.
- Earth fault equipment protection is required for each circuit.
- De-energise circuits before installation or servicing.
- Keep ends of heating cables and kit components dry before and during installation.
- The electrically conductive covering of this heating cable shall be connected to a suitable earthing terminal.
- The presence of the heating cables shall be made evident by the posting of caution signs or markings at appropriate locations and/or at frequent intervals along the circuit.
- The insulation resistance of the heating cable shall be measured and recorded after installation and shall not less than 20 Mohm.
- Persons involved in the installation and testing of electric trace heating systems shall be suitably trained in all special techniques required.
- Installation shall be carried out under the supervision of a qualified person.
- Refer to installation manual. A ground fault circuit interrupter shall be used with this device.
Important note: Heat shrink technique for E-40 kits – Step 9
Heat gun power for optimal shrinking time – 3000 W or greater is recommended.
Lower power heat guns may work, but may require more time.
Recommended heat gun temperature: 600-650°C
-
Set heat gun at maximum temperature and maximum air flow.
-
Starting on cable end of heat shrink, hold heat gun in one position over the translucent heat shrink tubing until it turns clear (+/– 1 min).
Then slowly move the heat gun around all sides until the heat shrink turns clear in this segment. -
Slowly move to an adjacent unshrunk translucent position and repeat for this next segment.
-
Slowly continue along the length of heat shrink, rotating the heat gun at each segment until complete. Installation typically takes several minutes.
-
Keep heat gun as close as possible to heat shrink (5 mm) but do not allow it to touch cable or heat shrink (to avoid burning and damaging materials).
Connectivity
DE, FR, NL, NO, SV, DA, FI, IT, ES, PL, RU, CZ, HU, CRO: page 18-23.
Customer Support
©2023 nVent. All nVent marks and logos are owned or licensed by nVent Services
GmbH or its affiliates.
All other trademarks are the property of their respective owners. nVent
reserves the right to change specifications without notice.
United Kingdom
Tel. 0800 969 013
salesthermalUK@nVent.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>