Carrier CAECOMZR001B00 Packaged Air-Handling Units Instruction Manual

June 6, 2024
Carrier

Carrier CAECOMZR001B00 Packaged Air-Handling Units Instruction Manual

SAFETY CONSIDERATIONS

Installation of this accessory can be hazardous due to system pressures, electrical components, and equipment location (such as a roof or elevated structure). Only trained, qualified installers and service technicians should install, start-up, and service this equipment. When installing this accessory, observe precautions in the literature, labels attached to the equipment, and any other safety precautions that apply:

  • Follow all safety codes
  • Wear safety glasses and work gloves
  • Use care in handling and installing this accessory

It is important to recognize safety information. This is the safety alert symbol: . When you see this symbol  on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.

INTRODUCTION

The economizer accessory (see Fig. 1) allows outside air to be mixed with return air for “free” cooling if the outdoor-air temperature and humidity are suitable. Economizer cooling can be used alone or in conjunction with mechanical cooling. The economizer can also be used to provide ventilation air to improve indoor air quality. An enthalpy control is provided with the economizer accessory. Refer to Table 1 to determine unit capacity by size and see Table 2 for accessory weight and kit contents.

A separate CO2 sensor accessory is available for use with the economizer. The sensor signals the economizer to admit outdoor air to the occupied space to dilute the carbon dioxide level when it exceeds the set point. The sensor has an adjustable range of 0 to 2000 ppm.
Economizer Accessory

PRE-INSTALLATION

Complete Pre-installation Checks
Remove accessory packaging and inspect shipment for damage.
File claim with shipping company if accessory is damaged or incomplete.

Check Unit Clearance
Provide sufficient space for airflow clearance, wiring, and servicing accessory after it is mounted on unit. See Fig. 2 for accessory dimensions. Base unit service clearances of 2.5 ft from front and sides of unit and 3 in. from rear of unit also apply to the economizer.

Table 1 — Unit Model Size to Nominal Tons

UNIT MODEL SIZE NOMINAL TONS
40RU 524J
07 07
08 08
10 10
12 12
14 14
16 16
25 25
28 28
30 30

Table 2 — Accessory Usage and Weight


UNIT

| ECONOMIZER ACCESSORY KIT NO.| WEIGHT —

lb (kg)

| ****

KIT CONTENTS

---|---|---|---
Direct-Expansion Units,

6 to 10 Tons

Chilled Water Units,

7-1/2 to 10 Tons

| CAECOMZR001B00

(Unpainted)

| 185

(84.1)

| ****

1 — Economizer Assembly
1 — Transformer
1 — Enthalpy Sensor (with mounting screws)
1 — Supply-Air Temperature Sensor
1 — Relay (Pilot Duty)
4 — No. 10 x 1/2 in. Self-Tapping Screws
4 — No. 8 x 1/2 in. Sheet Metal Screws
4 — P-Clamps

Direct-Expansion Units and Chilled Water Units,

12-1/2 to 20 Tons

| CAECOMZR002B00

(Unpainted)

| 340

(154.5)

Direct-Expansion and Chilled Water Units, 25 and 30 Tons| CAECOMZR003B00

(Unpainted)

| 450

(204.5)

Fig. 2 — Economizer Mounted on Unit (Vertical Installation Shown)
Economizer Mounted on Unit
Economizer Mounted on Unit
Economizer Mounted on Unit
NOTE: Dimensions in [ ] are millimeters.

INSTALLATION

Mount Economizer on Unit
Refer to Fig. 3 and 4 and perform the following steps:

  1. Orient the unit so that the desired return-air opening is acces- sible. For vertical installations, reposition the panel from the rear to the bottom of the unit using the same screws.
  2. Remove the bag containing loose parts and fasteners from inside the economizer. These parts will be used later.
  3. Install field-supplied gasket material over economizer flanges.
  4. Place the economizer and gasket over the return-air opening so that the flanges and screw holes on the top and bottom of the economizer box are aligned with those surrounding the return-air opening.
  5. Using field-supplied 1/4 in. x 3/4 in. (maximum length) sheet metal screws, fasten the long economizer flanges to the matching return-air opening flanges and tighten all screws.
  6. Using the four 10 x 1/2 in. self-tapping screws supplied, fasten the short economizer flanges to the matching return air opening flanges and tighten all screws.
    INSTALLATION
    INSTALLATION

Install Transformer, Relay, and Supply-Air Temperature Sensor

The transformer, relay, and supply-air temperature (SAT) sensor are shipped with the economizer accessory for field installation as follows:

WARNING
ELECTRIC SHOCK HAZARD

Failure to follow this warning could result in personal injury, property damage, or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
If any wiring changes are required, first be sure to remove power from the economizer module before starting work. Pay particular attention to verifying the power connection (24 vac).

  1. Remove the service panel from the control box end of the unit.
  2. Mount the supply-air temperature sensor inside the air handler on the sensor mounting angle. Use the holes in the sensor base as guides to fasten the sensor to the mounting angle with field-supplied self-tapping screws, or drill holes into the mounting angle and fasten sensor in place with field-supplied sheet metal screws (3/4 in. maximum length). Locate the sensor in the middle of the mounting angle. (See Fig. 5.)
  3. For air handlers without a circuit breaker in the control box (units with fan motor sizes less than 5 hp [3.73 kW]) mount the transformer and relay inside the control box. Use the holes in the transformer base and relay base as guides to drill holes into the box and fasten components in place with supplied no. 8 x 1/2 in. sheet metal screws. (See Fig. 6.)
  4. For air handlers with a circuit breaker in the control box (units with fan motor sizes of 5 hp [3.73 kW] or greater), mount the supplied transformer and relay in a field-supplied and installed electrical box as shown in Fig. 6. Use the holes in the transformer base and relay base as guides to drill holes into the box and fasten components in place with supplied no. 8 x 1/2 in. sheet metal screws.
    INSTALLATION
    INSTALLATION

Install Economizer, SAT Sensor, Relay, and Transformer Wiring

WARNING
ELECTRIC SHOCK HAZARD
Failure to follow this warning could result in personal injury, property damage, or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
If any wiring changes are required, first be sure to remove power from the economizer module before starting work. Pay particular attention to verifying the power connection (24 vac).

  1. Remove the economizer control access panel and locate the actuator wiring harness (on 25 and 30 ton units, the master actuator wiring harness). (See Fig. 7 and 8.)

  2. Separate the orange and green wires from the wiring harness.
    Run the remaining wires in the wiring harness through the unit’s return air opening.

  3. Connect the gray wires to the supply-air temperature sensor leads as shown in Fig. 9 and 10.

  4. Remove the air handler control box cover and connect the yellow and blue wires to TB1 terminals Y1 and Y2.

  5. Connect Y1 and Y2 from condensing unit or chiller to Y1 and Y2 on air handler terminal block TB1. Connections can be made using 1/4 in. female quick connects (inside box) or with screw terminals (outside box). (See Fig. 9 and 10.)
    NOTE: If the unit has single-stage cooling, terminate the blue wire with a wire nut and secure.

  6. Route brown and red wires through control wiring access hole in unit corner post and connect to Y1 and Y2 from thermostat.
    NOTE: If the unit has single-stage thermostat, terminate the brown wire with a wire nut and secure.

  7. Connect black wire to transformer as shown in Fig. 9 and 10.

  8. Using field-supplied wires, connect economizer relay (ER) coil to air handler terminals C and G. Connect white wire from transformer secondary to relay common contact. Connect white wire from harness to relay normally open contact.

  9. Using field-supplied wire, connect line voltage power to transformer primary. There are taps for 200, 230, and 460-v power. (For 400-3-50 power, use the 460-v tap.) Connect power wire to correct tap and terminate any unused wires.

  10. See Fig. 9 and 10 for enthalpy sensor wiring diagrams.

INSTALLATION

Fig. 9 — Economizer Wiring, 6 to 20 Ton Units
Economizer Wiring
LEGEND

  • SAT — Supply-Air Temperature
  • Terminals
  • Wire Nut or Equivalent Connection
  • Economizer Relay
  • Field Wiring
  • Factory Wiring

NOTES:

  1. If system has single-stage cooling, terminate the blue wire with a wire nut and secure. If thermostat is single-stage cooling, terminate the brown wire with a wire nut and secure.

  2. Factory installed 620 ohm, 1 watt, 5% resistor should be removed only if a C7400
    enthalpy sensor is added to SR and + for differential enthalpy.

  3. Economizer relay closes outside air damper when fan coil blower is not powered.

  4. Enthalpy sensor can be located up to 200 ft away from economizer. Use field-supplied 2-conductor 18 AWG (American Wire Gage) wire.

WIRING DIAGRAM FOR CAECOMZR003B00

Fig. 10 — Economizer Wiring, 25 and 30 Ton Units
WIRING DIAGRAM

LEGEND

  • ER — Economizer Relay
  • SAT — Supply-Air Temperature
  • Terminals
  • Wire Nut or Equivalent Connection
  • Field Wiring
  • Factory Wiring

NOTES:

  1. Factory installed 620 Ohm, 1 Watt, 5% resistor should be removed only if a C7400 enthalpy sensor is added to SR and + for differential enthalpy.
  2. Economizer relay closes outside air damper when fan coil blower is not powered.
  3. Enthalpy sensor can be located up to 200 ft away from economizer. Use field-supplied 2-conductor 18 AWG (American Wire Gage) wire.

Applications Using a Single Enthalpy Sensor: Installing Enthalpy Sensor and Connecting Ductwork
NOTE: An optional differential enthalpy sensor (part no.
HH57AC078) mounts in the return air duct and can be used for differential enthalpy control. If using differential enthalpy sensors to control unit, see following section for installation instructions.
Refer to Fig. 11 and perform the following steps:

  1. Size the outdoor air ductwork according to the sizes for the damper flanges shown in Fig. 2.

  2. Attach return-air duct to economizer return-air damper, caulk and secure in place. Ensure damper blades are unobstructed.

  3. Mount the supplied enthalpy sensor (see Fig. 12) inside the outdoor-air duct no more than 200 feet from the unit, as shown in Fig. 11. Use the holes in the sensor base as guides to fasten it to the duct with supplied self-tapping screws, or drill holes into the duct and fasten the sensor in place with field-supplied sheet metal screws.
    IMPORTANT: Mount enthalpy sensor where it is exposed to fresh outdoor air, but NOT exposed to rain, snow, or direct sunlight.

  4. Run the orange and green wires from the economizer wiring harness to the enthalpy sensor, remove knockout in top of economizer cabinet and drill or punch holes in side of duct to route wiring according to the application. Connect the orange wire to terminal So and green to terminal (+). (See Fig. 9 and 10.)
    CAUTION
    EQUIPMENT DAMAGE
    Failure to follow this caution may result in unit damage.
    Route wiring harness carefully to avoid blocking filters or contacting moving parts.

  5. Attach outdoor-air duct to economizer outdoor-air damper.
    Caulk and secure in place. Ensure damper blades are unobstructed.

  6. Using supplied P-clamps, secure the wiring harness to the unit.

  7. Replace air handler service panel.
    INSTALLATION

Applications Using Differential Enthalpy
Sensors: Installing Enthalpy Sensors and Connecting Ductwork

Refer to Fig. 11 and perform the following steps:

  1. Size the supply air ductwork according to the sizes for the damper flanges shown in Fig. 2.

  2. The economizer accessory includes one enthalpy sensor. If economizer operation based on enthalpy differential between outdoor and return air is desired, differential enthalpy sensor part no. HH57AC078 (Honeywell part no. C7400A1004) must be ordered. (See Fig. 12.)

  3. Mount the differential enthalpy sensor inside return air duct as shown in Fig. 11. Use the holes in the sensor base as guides to fasten it to the duct with self-tapping screws, or drill holes into the duct and fasten the sensor in place with field-supplied sheet metal screws.

  4. Remove the factory-installed 620-ohm resistor from between economizer actuator terminals SR and (+). (See Fig. 9 and 10.)

  5. Using field-supplied wires, connect the differential enthalpy sensor terminal S to actuator terminal SR and sensor terminal (+) to actuator terminal (+). Remove knockout in top of economizer cabinet and drill or punch holes in side of duct to route wiring according to the application.

  6. Attach return-air duct to economizer return-air damper. Caulk and secure in place. Ensure damper blades are unobstructed.

  7. Mount the enthalpy sensor inside outdoor-air duct as shown in Fig. 11. Use the holes in the sensor base as guides to fasten it to the duct with self-tapping screws, or drill holes into the duct and fasten the sensor in place with field-supplied sheet metal screws.
    IMPORTANT: Mount enthalpy sensor where it is exposed to fresh outdoor air, but NOT exposed to rain, snow, or direct sunlight.

  8. Run the orange and green wires from the economizer wiring harness to the enthalpy sensor; remove knockout in top of economizer cabinet and drill or punch holes in side of duct to route wiring according to the application. Connect the orange wire to terminal So and green to terminal (+). (See Fig. 9 and 10.)
    CAUTION
    EQUIPMENT DAMAGE
    Failure to follow this caution may result in unit damage.
    Route wiring harness carefully to avoid blocking filters or contacting moving parts.

  9. Attach outdoor-air duct to economizer outdoor-air damper.
    Caulk and secure in place. Ensure damper blades are unobstructed.

  10. Using supplied P-clamps, secure the wiring harness to the unit.

  11. Replace air handler service panel.

Adjust Enthalpy Setting and Minimum Damper Position

The economizer actuator has a control module (see Fig. 13) with 2 adjustable settings; one for enthalpy and another to control the minimum position for the outdoor air damper. The enthalpy setting is determined by a 4-position selector switch. Settings A-D refer to the psychometric chart in Fig. 14. Choose an enthalpy setting according to the desired operation displayed in the chart.

The economizer opens when enthalpy is below the selected setting.

The outdoor air damper minimum position can be set with the potentiometer on the control module. (See Fig. 13.) After choosing the setting, check the damper’s minimum position operation by using the thermostat to cycle the air- handling unit in and out of cooling mode.

When adjustments are complete, replace the economizer control access panel.
Economizer Control Module
Fig. 14 — Psychrometric Chart for Enthalpy Control Using a CO2 Sensor with the Economizer
Economizer Control Module
LEGEND
RH — Relative Humidity

CONTROL CURVE| CONTROL POINT
— APPROX. °F [C] AT 50% RH
---|---
A| 73 [23]
B| 70 [21]
C| 67 [19]
D| 63 [17]

A separately ordered carbon dioxide sensor (see Fig. 15) can be used to signal the economizer to open the outdoor-air dampers to admit fresh air and dilute the indoor CO2 level. Sensor descriptions and part numbers are shown in Table 3. To mount the sensor, refer to the installation instructions shipped with the sensor.

Table 3 — CO2 Sensor Accessories

CO 2 SENSOR ACCESSORY

PART NUMBERS

| DESCRIPTION
---|---
33ZCSENCO2| Wall Mount Sensor
33ZCASPCO2| Duct Mount Aspirator Box

The CO2 sensors listed in Table 3 are factory set for a range of 0 to 2000 ppm and a linear voltage output of 2 to 10 vdc. The relay normally open dry contacts (TB-3 and TB-4) are factory set to close at 1000 ppm. Refer to the instructions supplied with the CO2 sensor for electrical ratings of contacts and information on connecting to power supply. Switch contacts can be used to set off an alarm or light to indicate CO2 levels higher than the switch set point.

Any changes to the factory configuration require the purchase of the User Interface Program (UIP) or Sensor Calibration Service Kit, which also contains the UIP. For correct modulation of the economizer actuator motor, a separately ordered adapter  (Honeywell part no. Q769C1007) is required.
CO2 Sensor

CO2 SENSOR INSTALLATION WITH ECONOMIZER AND STANDARD THERMOSTAT

The economizer and enthalpy sensor(s) must be installed before installing and testing the CO2 sensor. When the CO2 sensor is installed with the economizer and a standard thermostat, the economizer modulates open when the leaving-air temperature demand requires greater airflow than the airflow demand generated by the CO2 sensor to reduce carbon dioxide levels. When the CO2 sensor is installed, there is no minimum leaving air temperature control at the economizer.

Use field-supplied 14 AWG (American Wire Gage) power wiring to connect the CO2 sensor as follows.

WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
To prevent electrical shock, disconnect all power before installing or wiring sensors.

  1. On the actuator logic module, remove the black jumper wire connecting P and P1.
  2. Using a small screwdriver, adjust the minimum position potentiometer fully clockwise (open).
  3. Using field-supplied wire and terminals, connect J8-8 from the CO2 sensor to the (+) terminal on the front of adapter part no. Q769C1007. Connect J8-7 to the (–) terminal. (See Fig. 16 and 17.)
  4. On the back of the adapter, there are two slots that accept 1/4 in. male quick-connect terminals. (See Fig. 17.) Using field-supplied wire, connect the (+) terminal on the back of the adapter to P1 on the logic module. Connect the (–) terminal on the back of the adapter to terminal P on the logic module.

ADJUSTING ADAPTER NO. Q769C1007

The adapter is factory-set to begin modulating the actuator open from the fully closed position at 2.4 vdc and closed from the fully open position at 9.8 vdc, with the calibration potentiometer (Fig. 17) set at the midrange position. The potentiometer can be used to adjust the minimum damper position. Turning the potentiometer counterclockwise increases the damper’s minimum position setting; turning the potentiometer clockwise decreases the minimum position setting.
ADJUSTING ADAPTER
ADJUSTING ADAPTER

SEQUENCE OF OPERATION — AIR HANDLER WITH ECONOMIZER

This sequence is based on an installation where the economizer has been correctly installed on the air-handling unit, and the entire HVAC system (including the air handler, economizer actuators, condensing unit or chiller, and thermostat) have been powered on.

When the thermostat turns the indoor fan on, the economizer relay is energized and the actuator(s) are powered on. The actuator(s) move the dampers to the minimum positions as determined by the adjustment potentiometer on the actuator or master actuator. If the system uses a CO2 sensor, the minimum position is determined by the potentiometer on the required field-supplied adapter.

On a call for heating from the thermostat (W1 and/or W2 energized), the economizer remains at the minimum position.

NOTE: If a CO2 sensor is used, the economizer can modulate based on the carbon dioxide level in the space. There is no low leaving-air temperature limit control. Controls to accomplish this must be field-supplied and installed.

On a call for cooling from the thermostat (Y1 energized), the actuator logic module determines if the outdoor air enthalpy is acceptable according to the set point on the actuator. If the outdoor air enthalpy is acceptable, the economizer begins to modulate open and is controlled to maintain a 56°F leaving air temperature.

If outdoor air enthalpy is unacceptable, the logic module bypasses the use of outdoor air and energizes Y1 at the condensing unit or chiller.

On a call for a second stage of cooling (Y2 energized), the actuator energizes Y1 at the condensing unit or chiller if the outdoor air enthalpy is acceptable. If the outdoor air is unacceptable, the actuator logic module energizes Y2 at the condensing unit or chiller.

If the system is equipped with a CO2 sensor in a modulating configuration, the following applies: if the system is operating in the Cooling mode and the demand for fresh air to reduce the carbon dioxide level in the space is greater than the cooling load demand, the actuator modulates to reduce the carbon dioxide level and does not modulate towards closed if the leaving-air temperature is below 56°F. If, however, the cooling demand is greater than the demand to reduce the carbon dioxide level, the actuator modulates open and controls to a 56°F leaving-air temperature.

START-UP

After installing and wiring the economizer and sensors, perform the following start-up steps:

  1. Set the thermostat to OFF. Set the cooling and heating set points to minimum.

  2. Start the air handler and the condensing unit according to the base unit installation instructions.

  3. At the thermostat, turn the fan to ON. The air handler starts and the outdoor air dampers move to the minimum position.
    If a different minimum vent position is required, adjust the minimum position potentiometer on the economizer control module.

  4. Set the thermostat to HEAT or AUTO mode. Raise the heating mode set point until the first stage of heat comes on at the air handler and check for correct heating cycle operation according to the instructions shipped with the heating device.
    Through the access panel on the side of the economizer, check to see that the economizer outdoor air damper stays in the minimum vent position. If heat does not operate correctly or damper does not stay in minimum vent position, recheck and correct wiring.

  5. Repeat the procedure from the previous step to engage the second stage of heating (if present), and again check to make sure that the economizer outdoor air damper stays in the minimum vent position.

  6. Set the thermostat to COOL or AUTO mode. Reduce the set point to activate the first stage of cooling.

  7. If the outdoor air enthalpy is above the set point on the enthalpy sensor, the first stage of mechanical cooling is turned on. If the cooling set point is reduced further, the second stage of cooling is activated.

  8. If the outdoor air enthalpy is below the set point on the economizer control module, the first stage call for cooling opens the economizer outdoor-air dampers. (It may be necessary to temporarily set the enthalpy switch to the “A” setting to check for correct damper operation.) If the cooling set point is reduced further, the first stage of mechanical cooling is turned on.
    NOTE: The economizer controls the dampers to maintain a supply-air temperature of 56°F when the enthalpy is suitable.

  9. As the cooling stages are engaged, verify correct operation of the cooling stages and the economizer dampers.

  10. Verify linked damper/CO2 sensor operation by blowing on sensor and observing damper operation. Monitor the dc voltage on actuator logic module terminals P and P1 when testing damper operation. The sensor must register 1000 ppm or higher (approximately 6 vdc) to activate relay contacts.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals