HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans User Manual

June 4, 2024
HAVACO

HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans

SAFETY WARNINGS

  • Installation must only be carried out by qualified persons.
  • Make sure that the installation complies with each country is current mechanical and electrical norms.
  • Once ready to use, the apparatus must fulfill the following standard:
  • Standard for LOW Pressure Installments 2014/35 EU
  • Standard for Electromagnetic Compatibility 2014/30 EU
  • Ventilators, or apparatus that include them, have been designed to move the air in the area stipulated on their characteristics plate.
  • This apparatus must not be used in explosive or corrosive atmospheres.
  • If a ventilator is going to be installed to extract air from premises where a boiler or other combustion apparatus are installed, make sure that the building has sufficient air intakes to assure adequate combustion. The extractor outlet must not be connected to a duct used exhaust smoke or fumes from any appliance that uses gas or any other type of fuel.
  • This appliance is not intended for use by young children or infirm per-sons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance

TRANSPORTATION

  • The packaging used for this apparatus has been designed to support normal transporting conditions. The fan should be kept in original pack-age as preventing to deform or damage the product.
  • The product should be stored in a dry place in its original packaging, protected from dust and dirt until it is installed in its final location.
  • Do not accept delivery if the apparatus is not in its original packaging or shows clear signs of having been manipulated in any way.
  • Do not place heavy weights on the packed product and avoid knock-ing or dropping it.

INSTALLATION

  • Make sure there are no loose elements near the ventilator, as they could run the risk of being sucked up by it. If it is going to be installed in a duct, check that it is clean of any element that could be sucked up by the ventilator.
  • When installing an apparatus, make sure that all the fittings are in place and that the structure which supports it is resistant enough to bear its weight at full functioning power.
  • Before manipulating the apparatus, make sure the mains supply is dis-connected, even if the machine is switched off.
  • Check that the mains supply voltage and frequency values coincide with the stipulations on the characteristics plate.
  • The electrical installation must include a double pole switch with a con-tact clearance of at least 3 mm, correctly sized and in accordance with the electrical standards of the country of installation.
  • Please follow the connections diagram for the electrical connections.
  • If an earth connection is necessary, check that it correctly connected and that adequate thermal and overloading protection has been con-nected and adjusted to the corresponding limits.
  • If a ventilator is installed in a duct, the duct must be exclusively for the ventilation system.

Before starting up the machine, make sure that:

  • The apparatus is well secured and the electrical connections have been carried out correctly.
  • No loose material or fitting remains can be sucked up by the ventila-tor, If the ventilator has been mounted in a duct, make sure it is clear of loose material.
  • The earth fittings are adequately connected.
  • The electrical safety devices are correctly connected, adjusted and ready for use.
  • The wire and electrical connections inputs are correctly sealed and water-tight.

When starting up the machine, make sure that:

  • The propeller turns in the correct direction.
  • There are no abnormal vibrations.
  • If any of the electrical safety devices blow, the apparatus must be quickly disconnected from the mains supply. The whole installation should be carefully checked before trying to start up the machine again.
  1. Unlock the clips
  2. Open the clips on both ends. Place the motor unit to the base
  3. Remove the motor unit
  4.  Attach the base unit
  5. Lock up clips connecting the motor unit with connections
  6. Connect the ducts

WIRING DIAGRAM

HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans-
fig3

Wiring diagram with HRX speed cotrol

HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans-
fig4

Wiring diagram with HRS switch control

HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans-
fig5

 TECHNICAL DRAWING

HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans-
fig6

TECHNICAL DATA

HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans-
fig7

CLEANING AND MAINTENANCE

  • Before manipulating the ventilator, make sure it is disconnected from the mains supply even if it has previously been switched off. Prevent the possibility of anyone else connecting it while it is being manipulated.
  • The apparatus must be regularly inspected. These inspections should be carried out bearing in mind the machine is working conditions, in order to avoid dirt or dust accumulating on the propeller, turbine, motor or grids. This could be dangerous and perceptibly shorten the working life of the ventilator unit.
  • While cleaning, great care should be taken not to unstable the propel-ler or turbine.
  • All maintenance and repair work should be carried out in strict compli-ance with each country is current safety regulations.

HAVACO ICMsilent-100-125-290M Diagonal in Line Duct Fans-
fig8 HAVACO ICMsilent-100-125-290M
Diagonal in Line Duct Fans-fig9

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HAVACO User Manuals

Related Manuals