Invertek Drives 3-140022-3F1A Variable Frequency Drive, User Guide

October 27, 2023
Invertek Drives

Invertek Drives logo

Invertek Drives 3-140022-3F1A Variable Frequency Drive

Invertek Drives 3-140022-3F1A Variable Frequency Drive

  1. CHECK: Check the correct drive type, check suitable motor type & info
  2. PREPARE: Correct tools, suitable mounting location, weather protection
  3. MOUNT: Mechanical mounting
  4. CONNECT: Power & Control connections
  5. CHECK: Final check of everything before operation 6 POWER ON
  6. COMMISSION the drive parameters
  7. OPERATE and check everything is as intended

WARNING! The Optidrive should ONLY be installed by a qualified electrician.
WARNING! In a residential environment, this product may cause radio interference in which case supplementary mitigation measures may be required.
NOTE This guide does not provide detailed installation, safety or operational instructions.
See the Optidrive E3 IP66 Outdoor User Manual for complete information.
Unpack and check the drive. Notify the supplier and shipper immediately of any damage.

CHECK

Identifying the Drive by Model Number
Each drive can be identified by its model number, as shown in the table below.

PREPARE

Prepare the Mounting Location

  • The Optidrive must be mounted in a vertical position only.
  • Installation should be on a suitable flat, flame resistant surface. Do not mount flammable material close to the drive.
  • Refer to Technical Data and ensure the chosen mounting location is within the drive specification.
  • The mounting location should be free from vibration.
  • Do not mount the drive in any area with excessive humidity, corrosive airborne chemicals or potentially dangerous dust particles.
  • Avoid mounting close to high heat sources.
  • The drive must not be mounted in direct sunlight. If necessary, install a suitable shade cover.
  • The mounting location must be free from frost.
  • Do not restrict the flow of air through the drive heatsink. The drive generates heat which must be naturally allowed to dissipate. Correct air clearance around the drive must be observed.
  • If the location is subject to wide ambient temperature and air pressure variation, install a suitable pressure compensation valve in the drive gland plate.

NOTE If the drive has been in storage for a period longer than 2 years, the DC link capacitors must be reformed. Refer to online documentation for further information.

MOUNT

Mechanical Dimensions

Invertek Drives 3-140022-3F1A Variable Frequency Drive
2

Dimensions

Drive Size A B C D E Weight
mm in mm in mm in mm
mm in kg Ib
1 232 9.13 161 6.34 162 6.37
2 257 10.12 188 7.4 182 7.16
3 310 12.2 211 8.3 235 9.25
4 360 14.17 240 9.44 271 10.67

Mounting Clearance

Drive Size X Above & Below Y Either Side
mm in mm
All Frame Sizes 200 7.87
NOTE Typical drive heat losses are approximately 3% of operating load

conditions.

Above are guidelines only and the operating ambient temperature of the drive MUST be maintained below the maximum limit at all times.

Mounting Bolts & Tightening Torques

Tightening Torques

Frame Size| Control Terminals| Power Terminals
1, 2, 3| 0.5 Nm (4.4 lb-in)| 0.8 Nm (7 lb-in)
4| 0.5 Nm (4.4 lb-in)| 2 Nm (19 lb-in)

CONNECT

Cable Selection

  • For 1 phase supply (Sizes 1-3 only), the mains power cables should be connected to L1/L, L2/N.
  • For 3 phase supplies, the mains power cables should be connected to L1, L2, and L3. Phase sequence is not important.
  • For compliance with CE and C Tick EMC requirements, refer to online documentation.
  • A fixed installation is required according to IEC61800-5-1 with a suitable disconnecting device installed between the Optidrive and the AC Power Source. The disconnecting device must conform to the local safety code / regulations (e.g. within Europe, EN60204-1, Safety of machinery).
  • The cables should be dimensioned according to any local codes or regulations. Maximum dimensions are given in the Rating Tables section of this Quick Start Guide.

Install the Power Wiring

Invertek Drives 3-140022-3F1A Variable Frequency Drive
3

Drive Size Power & Motor Cables
Hole Size Recommended PG Gland
Size 1 22
Size 2 & 3 27
Size 4 37

Motor Terminal Box Connections
Most general purpose motors are wound for operation on dual voltage supplies. This is indicated on the nameplate of the motor. This operational voltage is normally selected when installing the motor by selecting either STAR or DELTA connection. STAR always gives the higher of the two voltage ratings.

Information for UL Compliance
Optidrive E3 is designed to meet the UL requirements. For an up to date list of UL compliant products, please refer to UL listing NMMS.E226333. In order to ensure full compliance, the following must be fully observed.

Input Power Supply Requirements

Supply Voltage| 200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum.
380 – 480 Volts for 400 Volt rated units, + / – 10% variation allowed, Maximum 500 Volts RMS.
Frequency| 50 – 60Hz + / – 5% Variation
Short Circuit Capacity| All drives are suitable for use on a circuit capable of delivering not more than 100kA maximum short-circuit Amperes symmetrical with the specified maximum supply voltage when protected by Class J fuses.
Mechanical Installation Requirements
All Optidrive E3 units are intended for installation within controlled environments which meet the condition limits shown in the Environment section of this Quick Start Guide.
The drive can be operated within an ambient temperature range as stated in the Environment section of this Quick Start Guide.
Electrical Installation Requirements
Incoming power supply connection must be according to the Install the Wiring section of this Quick Start Guide.
Suitable power and motor cables should be selected according to the data shown in Rating Tables section of this Quick Start Guide and the National Electrical Code or other applicable local codes.
Motor Cable| 75°C Copper must be used.
Power cable connections and tightening torques are shown in the Mechanical Dimensions section of this Quick Start Guide.
Integral Solid Sate short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the national electrical code and any additional local codes. Ratings are shown in the Rating Tables section of this Quick Start Guide.
For Canadian installations transient surge suppression must be installed on the line side of this equipment and shall be rated 480Volt (phase to ground), 480 Volt (phase to phase), suitable for over voltage category iii and shall provide protection for a rated impulse withstand voltage peak of 2.5kV.
UL Listed ring terminals / lugs must be used for all bus bar and grounding connections.
General Requirements
Optidrive E3 provides motor overload protection, set at 150% of full load, in accordance with the National Electrical Code (US). Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-60 = 1.

Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information shown in the Motor Thermistor Connection section of the Quick Start Guide.

UL rated ingress protection (“Type” ) is only met when cables are installed using a UL recognized bushing or fitting for a flexible conduit system which meets the required level of protection (“Type”).
For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC.
Not intended for installation using rigid conduit system.
WARNING: The opening of the branch-circuit protective device may be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, current-carrying parts and other components of the controller should be examined and replaced if damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced.

Default functions of the control switches

Invertek Drives 3-140022-3F1A Variable Frequency Drive
6

Switch Confi guration

Invertek Drives 3-140022-3F1A Variable Frequency Drive
7

Invertek Drives 3-140022-3F1A Variable Frequency Drive
8

Control Connections

Invertek Drives 3-140022-3F1A Variable Frequency Drive
9

A Serial RS485 Port
B Ethernet Ports (Factory fit option)
C Control Terminals

Control Terminal Wiring

  • All analog signal cables should be suitably shielded.
    Twisted pair cables are recommended.

  • Power and Control Signal cables should be routed separately where possible, and must not be routed parallel to each other.

  • Signal levels of different voltages e.g. 24 Volt DC and 110 Volt AC, should not be routed in the same cable.

  • Maximum control terminal tightening torque is 0.5Nm.

  • Control Cable entry conductor size: 0.05 – 2.5mm2 / 30 – 12 AWG.

Control Terminal Connections
Control Switched Units: May use the built in control switch and potentiometer, or external control signals connected to the control terminals.
Non-Switched Units: Require external control signals to be connected to the control terminals.

Using the Control Terminals

Invertek Drives 3-140022-3F1A Variable Frequency Drive
10

Invertek Drives 3-140022-3F1A Variable Frequency Drive
22

Connection Example

Invertek Drives 3-140022-3F1A Variable Frequency Drive
11

Factory Default Functions

No.| Description|
---|---|---
DI1| 0/1| Open : Stop| Closed : Run
DI2| P/Q| Open : Forward Rotation| Closed : Reverse Rotation
DI3| Analog Speed Reference / Preset Speed| Open : Speed Reference set by Analog Speed Reference Closed : Speed Reference set by Preset Speed 1 (P-20)

Sets the Speed Reference

NOTE For Switched units, the internal pot is selected by default in P-16.

For Non-switched units, an external pot or 0 – 10 V reference may be connected. Other signal types may also be used, set P-16 to the correct format.

AI1| Analog Speed Reference Input
NOTE| Additional functions are possible, refer to the online documentation for further information.

Analog and Digital Input Macro Configurations

Overview

Optidrive E3 uses a Macro approach to simplify the configuration of the Analog and Digital Inputs. There are two key parameters which determine the input functions and drive behaviour:
P-12 Selects the main drive control source and determines how the output frequency of the drive is primarily controlled.
P-15 Assigns the Macro function to the analog and digital inputs.
Additional parameters can then be used to further adapt the settings, e.g.
P-16 Used to select the format of the analog signal to be connected to analog input 1, e.g. 0 – 10 Volt, 4 – 20mA.
P-30 Determines whether the drive should automatically start following a power on if the Enable Input is present.
P-31 When Keypad Mode is selected, determines at what output frequency / speed the drive should start following the enable command, and also whether the keypad start key must be pressed or if the Enable input alone should start the drive.
P-47 Used to select the format of the analog signal to be connected to analog input 2, e.g. 0 – 10 Volt, 4 – 20mA.

Example Connection Diagrams
The diagrams below provide an overview of the functions of each terminal macro function, and a simplified connection diagram for each.

Invertek Drives 3-140022-3F1A Variable Frequency Drive
13

Macro Functions Guide Key

The table below should be used as a key on the following pages.

Function Explanation
STOP Latched Input, Open the contact to STOP the drive
RUN Latched input, Close the contact to Start, the drive will operate

as long as the input is maintained
FWD P| Latched Input, selects the direction of motor rotation FORWARD
REV Q| Latched Input, selects the direction of motor rotation REVERSE
RUN FWD P| Latched Input, Close to Run in the FORWARD direction, Open to STOP
RUN REV Q| Latched Input, Close to Run in the REVERSE direction, Open to STOP
ENABLE| Hardware Enable Input.

In Keypad Mode, P-31 determines whether the drive immediately starts, or the keypad start key must be pressed.

In other modes, this input must be present before the start command is applied via the fieldbus interface.

START =| Normally Open, Rising Edge, Close momentarily to START the drive (NC STOP Input must be maintained)
^- START -^| Simultaneously applying both inputs momentarily will START the drive (NC STOP Input must be maintained)
STOP?| Normally Closed, Falling Edge, Open momentarily to STOP the drive
START = FWD P| Normally Open, Rising Edge, Close momentarily to START the drive in the forward direction (NC STOP Input must be maintained)
START = REV Q| Normally Open, Rising Edge, Close momentarily to START the drive in the reverse direction (NC STOP Input must be maintained)
^-FAST STOP (P-24)-^| When both inputs are momentarily active simultaneously, the drive stops using Fast Stop Ramp Time P-24
FAST STOP? (P-24)| Normally Closed, Falling Edge, Open momentarily to FAST STOP the drive using Fast Stop Ramp Time P-24
E-TRIP| Normally Closed, External Trip input. When the input opens momentarily, the drive trips showing depending on P-47 setting
Fire Mode| Activates Fire Mode
Analog Input AI1| Analog Input 1, signal format selected using P-16
Analog Input AI2| Analog Input 2, signal format selected using P-47
AI1 REF| Analog Input 1 provides the speed reference
AI2 REF| Analog Input 2 provides the speed reference
P-xx REF| Speed reference from the selected preset speed
PR-REF| Preset speeds P-20 – P-23 are used for the speed reference, selected according to other digital input status
PI-REF| PI Control Speed Reference
PI FB| Analog Input used to provide a Feedback signal to the internal PI controller
KPD REF| Keypad Speed Reference selected
FB REF| Selected speed reference from Fieldbus (Modbus RTU / CAN Open / Master depending on P-12 setting)
(NO)| Input is Normally Open, Close momentarily to activate the function
(NC)| Input is Normally Closed, Open momentarily to activate the function
INC SPD =| Normally Open, Rising Edge, Close momentarily to increase the motor speed by value in P-20
DEC SPD?| Normally Open, Rising Edge, Close momentarily to decrease the motor speed by value in P-20

Macro Functions – Terminal Mode (P-12 = 0)

P-15| DI1| DI2| DI3 / AI2| DI4 / AI1| Diagram
---|---|---|---|---|---
0| 1| 0| 1| 0| 1| 0| 1
0| STOP| RUN| FWD P| REV Q| AI1 REF| P-20 REF| Analog Input AI1| 1
1| STOP| RUN| AI1 REF| PR-REF| P-20| P-21| Analog Input AI1| 1
2| STOP| RUN| DI2| DI3| PR| P-20 – P-23| P-01| 2
0| 0| P-20
1| 0| P-21
0| 1| P-22
1| 1| P-23
3| STOP| RUN| AI1| P-20 REF| E-TRIP| OK| Analog Input AI1| 3
4| STOP| RUN| AI1| AI2| Analog Input AI2| Analog Input AI1| 4
5| STOP| RUN FWD P| STOP| RUN REV Q| AI1| P-20 REF| Analog Input AI1| 1
 | ^——FAST STOP (P-24)—- ^
6| STOP| RUN| FWD P| REV Q| E-TRIP| OK| Analog Input AI1| 3
7| STOP| RUN FWD P| STOP| RUN REV Q| E-TRIP| OK| Analog Input AI1| 3
^——FAST STOP (P-24)—- ^
8| STOP| RUN| FWD P| REV| DI3| DI4| PR| 2
0| 0| P-20
1| 0| P-21
0| 1| P-22
1| 1| P-23
9| STOP| START FWD P| STOP| START REV Q| DI3| DI4| PR| 2
^——FAST STOP (P-24)—- ^| 0| 0| P-20
1| 0| P-21
0| 1| P-22
1| 1| P-23
10| (NO)| START =| STOP| (NC)| AI1 REF| P-20 REF| Analog Input AI1| 5
11| (NO)| START = FWD

Q

| STOP| (NC)| (NO)| START =

REV Q

| Analog Input AI1| 6
^———————FAST STOP (P-24)——————- ^
12| STOP| RUN| FAST STOP (P-24)| OK| AI1 REF| P-20 REF| Analog Input AI1| 7
13| (NO)| START FWD P| STOP| (NC)| (NO)| START REV Q| KPD| REF| P-20 REF| 13
^———————FAST STOP (P-24)——————- ^
14| STOP| RUN| DI2| E-TRIP| OK| DI2| DI4| PR| 11
 | 0| 0| P-20
1| 0| P-21
0| 1| P-22
1| 1| P-23
15| STOP| RUN| P-23 REF| AI1| Fire Mode| Analog Input AI1| 1
16| STOP| RUN| P-23 REF| P-21 REF| Fire Mode| FWD| REV| 2
17| STOP| RUN| DI2| Fire Mode| DI2| DI4| PR| 2
0| 0| P-20
1| 0| P-21
0| 1| P-22
1| 1| P-23
18| STOP| RUN| FWD P| REV Q| Fire Mode| Analog Input AI1| 1

Macro Functions – Keypad Mode (P-12 = 1 or 2)

P-15| DI1| DI2| DI3 / AI2| DI4 / AI1| Diagram
---|---|---|---|---|---
0| 1| 0| 1| 0| 1| 0| 1
0| STOP| ENABLE| –| INC SPD =| –| DEC SPD ?| FWD P| REV Q| 8
^—————-START————— ^
1| STOP| ENABLE| PI Speed Reference| 2
2| STOP| ENABLE| –| INC SPD =| –| DEC SPD ?| KPD REF| P-20 REF| 8
^—————-START————— ^
3| STOP| ENABLE| –| INC SPD =| E-TRIP| OK| –| DEC SPD ?| 9
^——————————-START—————————— ^
4| STOP| ENABLE| –| INC SPD =| KPD REF| AI1 REF| AI1| 10
5| STOP| ENABLE| FWD P| REV Q| KPD REF| AI1 REF| AI1| 1
6| STOP| ENABLE| FWD P| REV Q| E-TRIP| OK| KPD REF| P-20 REF| 11
7| STOP| RUN FWD| STOP| RUN REV Q| E-TRIP| OK| KPD REF| P-20 REF| 11
^———FAST STOP (P-24)——- ^
8| STOP| RUN FWD P| STOP| RUN REV Q| KPD REF| AI1 REF| AI1| 1
14| STOP| ENABLE| –| INC SPD =| E-TRIP| OK| –| DEC SPD ?|
15| STOP| ENABLE| PR REF| KPD REF| Fire Mode| P-23| P-21| 2
16| STOP| ENABLE| P-23 REF| KPD REF| Fire Mode| FWD P| REV Q| 2
17| STOP| ENABLE| KPD REF| P-23 REF| Fire Mode| FWD P| REV Q| 2
18| STOP| ENABLE| AI1 REF| KPD REF| Fire Mode| AI1| 1
9, 10, 11, 12, 13 = Behavior as per setting 0
NOTE| When P15=4 in keypad mode, DI2 &DI4 are edge triggered. Digital pot speed will be increased or decreased once for each rising edge. The step of each speed change is defined by the absolute value of Pre-set Speed 1 (P-20).

Speed change only happens during normal running condition (no stop command etc.). Digital pot will be adjusted between minimum speed (P-02) and maximum speed (P-01).

Macro Functions – Fieldbus Control Mode (P-12 = 3, 4, 7, 8 or 9)

P-15| DI1| DI2| DI3 / AI2| DI4 / AI1| Diagram
---|---|---|---|---|---
0| 1| 0| 1| 0| 1| 0| 1
0| STOP| ENABLE| FB REF (Fieldbus Speed Reference, Modbus RTU / CAN / Master-Slave defined by P-12)| 14
1| STOP| ENABLE| PI Speed Reference| 15
3| STOP| ENABLE| FB REF| P-20 REF| E-TRIP| OK| Analog Input AI1| 3
5| STOP| ENABLE| FB REF| PR REF| P-20| P-21| Analog Input AI1| 1
^—-START (P-12 = 3 or 4 Only)— ^
6| STOP| ENABLE| FB REF| AI1 REF| E-TRIP| OK| Analog Input AI1| 3
^—-START (P-12 = 3 or 4 Only)— ^
7| STOP| ENABLE| FB REF| KPD REF| E-TRIP| OK| Analog Input AI1| 3
^—-START (P-12 = 3 or 4 Only)— ^
14| STOP| ENABLE| –| –| E-TRIP| OK| Analog Input AI1| 16
15| STOP| ENABLE| PR REF| FB REF| Fire Mode| P-23| P-21| 2
16| STOP| ENABLE| P-23 REF| FB REF| Fire Mode| Analog Input AI1| 1
17| STOP| ENABLE| FB REF| P-23 REF| Fire Mode| Analog Input AI1| 1
18| STOP| ENABLE| AI1 REF| FB REF| Fire Mode| Analog Input AI1| 1
2, 4, 8, 9, 10, 11, 12, 13 = Behavior as per setting 0

Macro Functions – User PI Control Mode (P-12 = 5 or 6)

P-15| DI1| DI2| DI3 / AI2| DI4 / AI1| Diagram
---|---|---|---|---|---
0| 1| 0| 1| 0| 1| 0| 1
0| STOP| RUN| PI REF| P-20 REF| AI2| AI1| 4
1| STOP| RUN| PI REF| AI1 REF| AI2 (PI FB)| AI1| 4
3, 7| STOP| RUN| PI REF| P-20| E-TRIP| OK| AI1 (PI FB)| 3
4| (NO)| START| (NC)| STOP| AI2 (PI FB)| AI1| 12
5| (NO)| START| (NC)| STOP| PI REF| P-20 REF| AI1 (PI FB)| 5
6| (NO)| START| (NC)| STOP| E-TRIP| OK| AI1 (PI FB)|
8| STOP| RUN| FWD P| REV Q| AI2 (PI FB)| AI1| 4
14| STOP| RUN| –| –| E-TRIP| OK| AI1 (PI FB)| 16
15| STOP| RUN| P-23 REF| PI REF| Fire Mode| AI1 (PI FB)| 1
16| STOP| RUN| P-23 REF| P-21 REF| Fire Mode| AI1 (PI FB)| 1
17| STOP| RUN| P-21 REF| P-23 REF| Fire Mode| AI1 (PI FB)| 1
18| STOP| RUN| AI1 REF| PI REF| Fire Mode| AI1 (PI FB)| 1
2, 9, 10, 11, 12, 13 = Behavior as per setting 0
NOTE| P1 Setpoint source is selected by P-44 (default is fixed value in P-45, AI 1 may also be selected). P1 Feedback source is selected by P-46 (default is AI 2, other options may be selected).

Motor Thermistor Connection
Where a motor thermistor is to be used, it should be connected as follows:

Control Terminal Strip Additional Information
Compatible Thermistor: PTC Type, 2.5kΩ trip level.

§ Use a setting of P-15 that has Input 3 function as External Trip,

e.g. P-15 = 3. Refer to online documentation for further details.

COMMISSION

Managing the Keypad
The drive is configured and its operation monitored via the keypad and display.

Operating Displays

Invertek Drives 3-140022-3F1A Variable Frequency Drive
16

Changing Parameters

Invertek Drives 3-140022-3F1A Variable Frequency Drive
17

Read Only Parameter Access

Invertek Drives 3-140022-3F1A Variable Frequency Drive
18

Resetting Parameters

Resetting a Fault

Invertek Drives 3-140022-3F1A Variable Frequency Drive
20 OPERATE

Parameters
Standard Parameters

Par. Description Min Max Default Units
P-01 Maximum Frequency/Speed Limit P-02 500.0 **50.0
(60.0)** Hz/RPM
P-02 Minimum Frequency/Speed Limit 0.0 P-01 0.0

Hz/RPM
P-03| Acceleration Ramp Time| 0.00| 600.0| 5.0| s
P-04| Deceleration Ramp Time| 0.00| 600.0| 5.0| s
P-05| Stopping Mode/Mains Loss Response| 0| 4| 0|
 | Setting| On Disable| On Mains Loss
0| Ramp to Stop (P-04)| Ride Through (Recover energy from load to maintain operation)
1| Coast| Coast
2| Ramp to Stop (P-04)| Fast Ramp to Stop (P-24), Coast if P-24 = 0
3| Ramp to Stop (P-04) with AC Flux Braking| Fast Ramp to Stop (P-24), Coast if P-24 = 0
4| Ramp to Stop (P-04)| No action
P-06| Energy Optimiser| 0| 3| 0|
| Setting| Motor Energy Optimisation| Optidrive Energy Optimisation
---|---|---
0| Disabled| Disabled
1| Enabled| Disabled
2| Disabled| Enabled
3| Enabled| Enabled
P-07| Motor Rated Voltage/Back EMF at rated speed (PM/BLDC)| 0| 250/ 500| 230/400| V
P-08| Motor Rated Current| Drive Rating Dependent| A
P-09| Motor Rated Frequency| 10| 500| 50 (60)| Hz
P-10| Motor Rated Speed| 0| 30000| 0| RPM
Optidrive E3 normally uses frequency for all speed related parameters, e.g. Minimum and Maximum Output Frequency. It is also possible to work directly in RPM, by setting P-10 to the rated speed from the motor nameplate.

When set to the default value of zero, all speed related parameters are displayed in Hz.

Entering the value from the motor nameplate enables the slip compensation function, and the Optidrive display will also now show motor speed in RPM. All speed related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in RPM.

NOTE If P-09 value is changed, P-10 value is reset to 0.

P-11| Low Frequency Torque Boost| 0.0| Drive Dependent| %
P-12| Primary Command Source| 0| 9| 0|
0: Terminal Control 5: PI Control

1: Uni-directional Keypad Control 6: PI Analog Summation Control

2: Bi-directional Keypad Control 7: CAN Control

3: Modbus Network Control 8: CAN Control

4: Modbus Network Control 9: Slave Mode

NOTE When P-12 = 1, 2, 3, 4, 7, 8 or 9, an enable signal must still be provided at the control terminals, digital input 1.

P-13| Operating Mode Select| 0| 2| 0|
 | 0: Industrial Mode| Setting| Appli- cation| Current Limit (P-54)| Torque Characteristic| Spin Start (P-33)| Thermal Overload Limit Reaction (P-60 Index 2)
---|---|---|---|---|---
0| General| 150%| Constant| 0: Off| 0: Trip
1| Pump| 110%| Variable| 0: Off| 1: Current Limit Reduction
2| Fan| 110%| Variable| 2: On| 1: Current Limit Reduction
1: Pump Mode| 2: Fan Mode|  |  |  |  |
P-14| Extended Menu Access code| 0| 65535| 0|
Enables access to Extended and Advanced Parameter Groups. This parameter must be set to the value programmed in P-37 (default:

  1. to view and adjust Extended Parameters and value of P-37 + 100 to view and adjust Advanced Parameters. The code may be changed by the user in P-37 if desired.

Extended Parameters

Par. Description Min Max Default Units
P-15 Digital Input Function Select 0 17 0
P-16 Analog Input 1 Signal Format See Below U0-10


U  : Unidirectional, External 0 – 10Volt reference / pot

B  : Bi-directional, External 0 – 10Volt reference / pot

  : External 0 – 20mA signal

 4 : External 4 – 20mA signal, trip on loss

 4 : External 4 – 20mA signal, P-20 on loss

|  4 : External 20 – 4mA signal, trip on loss

 4 : External 20 – 4mA signal

U  : External 10 – 0 Volt signal

n  :   Switched    units only : Internal pot

|
P-18| Output Relay Function Select| 0| 9| 1|
0: Drive Enabled (Running) 1: Drive Healthy

2: At Target Frequency (Speed) 3: Drive Tripped

4: Output Frequency >= Limit

| 5: Output Current >= Limit 6: Output Frequency < Limit 7: Output Current < Limit

8: Analog Input 2 > Limit

9: Drive Ready to Run

|
P-20| Preset Frequency / Speed 1| -P-01| P-01| 5.0| Hz/RPM
P-21| Preset Frequency / Speed 2| -P-01| P-01| 25.0| Hz/RPM
P-22| Preset Frequency / Speed 3| -P-01| P-01| 40.0| Hz/RPM
P-23| Preset Frequency / Speed 4| -P-01| P-01| P-09| Hz/RPM
P-24| 2nd Ramp Time (Fast Stop)| 0.00| 600.0| 0.00| s
P-25| Analog Output Function Select| 0| 11| 8|
Digital Output Mode. Logic 1 = +24V DC

0: Drive Enabled (Running) 1: Drive Healthy

2: At Target Frequency (Speed) 3: Drive Tripped

4: Output Frequency >= Limit 5: Output Current >= Limit

6: Output Frequency < Limit

7: Output Current < Limit

| Analog  Output Mode

8: Output Frequency (Motor Speed) 9: Output (Motor) Current

10: Output Power

11: Load Current

|
P-30| Start/ Restart / Fire Mode Configuration
Index 1: Start Mode / Auto Restart| N/A| Edge-r|
: Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a power on or reset to start the drive.

: Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed.

 To : Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals.

Index 2: Fire Mode Input Logic| 0| 1| 0|
0: Normally Closed (NC) input. Fire Mode active if input is open.

1: Normally Open (NO) input. Fire Mode active if input is closed.

Index 3: Fire Mode Input Latch| 0| 1| 0|
0: Latched input. The drive will remain in Fire Mode, only as long the fire mode input signal remains.

1: Momentary input. Fire Mode is activated by a momentary signal on the input. Normally Open or Normally Closed operation is supported depending on Index 2 setting.

2: Normally Closed (NC) Input, Preset Speed 4 (P-23).

3: Normally Open (NO) Input, Preset Speed 4 (P-23).

P-31| Keypad Start Mode Select| 0 – 3| 7| 1|
0: Minimum Speed, Keypad Start 1: Previous Speed, Keypad Start

2: Minimum Speed, Terminal Enable

3: Previous Speed, Terminal Enable

| 4: Current Speed, Keypad Start 5: Preset Speed 4, Keypad Start 6: Current Speed, Terminal Start 7: Preset Speed 4, Terminal Start|
P-33| Spin Start| 0| 2| 0|
0: Disabled

1: Enabled

| 2: Enabled on Trip, Brown Out or Coast Stop|
P-34| Brake Chopper Enable (Not Size 1)| 0| 4| 0|
0: Disabled

1: Enabled With Software Protection

2: Enabled Without Software Protection

| 3: Enabled With Software Protection

4: Enabled Without Software Protection

|
Par.| Description| Min| Max| Default| Units
---|---|---|---|---|---
P-38| Parameter Access Lock| 0| 1| 0|
0: Unlocked| 1: Locked|
P-39| Analog Input 1 Offset| -500.0| 500.0| 0.0| %
P-40| Index 1: Display Scaling Factor| 0.000| 16.000| 0.000|
Index 2: Display Scaling Source| 0| 3| 0|
P-41| PI Controller Proportional Gain| 0.0| 30.0| 1.0|
P-42| PI Controller Integral Time| 0.0| 30.0| 1.0| s
P-43| PI Controller Operating Mode| 0| 3| 0|
0: Direct Operation

1: Inverse Operation

| 2: Direct Operation, Wake at Full Speed 3: Reverse Operation, Wake at Full Speed|
P-44| PI Reference (Setpoint) Source Select| 0| 1| 0|
0: Digital Preset Setpoint| 1: Analog Input 1 Setpoint|
P-45| PI Digital Setpoint| 0.0| 100.0| 0.0| %
P-46| PI Feedback Source Select| 0| 5| 0|
0: Analog Input 2

1: Analog Input 1

2: Motor Current

| 3: DC Bus Voltage

4: Analog 1 – Analog 2

5: Largest (Analog 1, Analog 2)

|
P-47| Analog Input 2 Signal Format| | | | U0-10
U : Unidirectional, External 0 – 10Volt reference / pot

External 0 – 20mA signal

4 : External 4 – 20mA signal, trip on loss

4 : External 4 – 20mA signal, P-20 on loss

| 4 : External 20 – 4mA signal, trip on loss

4 : External 20 – 4mA signal

: Motor thermistor

|
P-48| Standby Mode Timer| 0.0| 25.0| 0.0| s
P-49| PI Control Wake Up Error Level| 0.0| 100.0| 5.0| %
P-50| User Output Relay Hysteresis| 0.0| 100.0| 0.0| %

Advanced Parameters

Par. Description Min Max Default Units
P-51 Motor Control Mode 0 5 0

0: Vector speed control mode 1: V/f mode

2: PM motor vector speed control

| 3: BLDC motor vector speed control

4: Synchronous Reluctance motor vector speed control 5: LSPM motor vector speed control

P-52| Motor Parameter Autotune| 0| 1| 0|
0: Disabled| 1: Enabled
P-54| Maximum Current Limit| 0| 175| 150| %
Defines the max current limit in vector control modes
P-61| Ethernet Service Option| 0| 1| 0|
0: Disabled| 1: Enabled
P-62| Ethernet Service Timeout| 0| 60| 0| Mins
0: Disabled| >0: Timeout in minutes
P-63| Modbus Mode Selection| 0| 1| 0|
0: Standard1| 1: Advanced2
P-64| IP66 DI1 Source| 0| 4| 0|
Visible only on IP66 Switched Drives

0: Terminal 2 OR Switch Forward OR Switch Reverse 1: Terminal 2 Only

2: Terminal 2 OR Switch Forward

| ****

3: Terminal 2 AND (S-Forward OR Switch Reverse) 4: Terminal 2 AND Switch Forward

P-65| IP66 DI2 Source| 0| 2| 0|
Visible only on IP66 Switched Drive

0: Terminal 3 OR Switch Reverse

1: Terminal 3 Only

2: Terminal 3 AND Switch Reverse

Asynchronous Induction Motors (IM) Vector Control

Optidrive E3 factory default parameters are intended for use with IM motors where the power rating of the motor is approximately the same or slightly less than the indicated power rating of the drive. In this case, it should be possible to operate the motor without any parameter adjustment at all for initial testing.
For optimum performance, the drive parameters should be adjusted to match the motor ratings. This will also ensure correct protection of the motor from damage due to overload.

The basic parameters that should be adjusted are:

  • P-07 : Motor Rated Voltage (V)

  • P-08 : Motor Rated Current (A)

  • P-09 : Motor Rated Frequency (Hz)
    In addition, it is also possible to set:

  • P-10 : Motor Rated Speed (RPM)
    When this parameter is adjusted, slip compensation is activated. Slip compensation attempts to compensate the motor speed relative to the load applied, such that when operating at a constant speed with different loads, the motor shaft speed should remain approximately the same.
    To further improve the performance of the motor, the following additional steps can be followed:

  • Carry out an Autotune.

    • This requires Advanced Parameter Access, P-14 = P-37 + 100 (Default : 201).

    • After the correct nameplate information is entered from the motor, the drive can additionally measure some electrical characteristics of the motor to further optimise the motor control to suit connected motor.

    • This is achieved by setting P-52 = 1.
      The autotune will begin IMMEDIATELY following the setting of this parameter!

    • The drive output will be enabled, and the motor shaft may move. It is important to ensure this is safe before carrying out the autotune.

    • For IM motors, the autotune takes only a few seconds, and measures only the motor stator resistance. Parameter P-55 will be updated with the new value.

  • Adjust the Low Frequency Torque Boost

    • IM motors require some additional voltage at low frequency to improve the low speed operation and torque.
    • By adjusting P-11, it is possible to optimise the low speed operation.
    • If P-11 is increased too far, excessive motor heating or over current trips may result.
  • Speed regulation and response to load changes may be improved by adjusting P-11 Vector Gain to suit the motor and connected load.

    • Higher values will provide a more dynamic behaviour at the risk of instability.

NOTE For other motor types refer to online document.

Technical Data

Environment
Operational ambient temperature range

Enclosed Drives:                          -20 … 40°C (frost and condensation free)
Storage ambient temperature range: -40 … 60°C
Maximum altitude:                        2000m. Derate above 1000m: 1% / 100m
Maximum humidity:                       95%, non-condensing

Rating Tables

Frame Size| kW| HP| Input Current| Fuse/MCB (Type B)| Maximum Cable Size| Output Current| Recommended Brake Resistance
---|---|---|---|---|---|---|---
Non UL| UL| mm| AWG| A| Ω
110 – 115 (+ / – 10%) V 1 Phase Input, 230V 3 Phase Output (Voltage Doubler)
1| 0.37| 0.5| 7.8| 10| 10| 8| 8| 2.3| –
1| 0.75| 1| 15.8| 25| 20| 8| 8| 4.3| –
2| 1.1| 1.5| 21.9| 32| 30| 8| 8| 5.8| 100
200 – 240 (+ / – 10%) V 1 Phase Input, 3 Phase Output
1| 0.37| 0.5| 3.7| 10| 6| 8| 8| 2.3| –
1| 0.75| 1| 7.5| 10| 10| 8| 8| 4.3| –
1| 1.5| 2| 12.9| 16| 17.5| 8| 8| 7| –
2| 1.5| 2| 12.9| 16| 17.5| 8| 8| 7| 100
2| 2.2| 3| 19.2| 25| 25| 8| 8| 10.5| 50
3| 4| 5| 29.2| 40| 40| 8| 8| 15.3| 25
200 – 240 (+ / – 10%) V 3 Phase Input, 3 Phase Output
1| 0.37| 0.5| 3.4| 6| 6| 8| 8| 2.3| –
1| 0.75| 1| 5.6| 10| 10| 8| 8| 4.3| –
1| 1.5| 2| 8.9| 16| 15| 8| 8| 7| –
2| 1.5| 2| 8.9| 16| 15| 8| 8| 7| 100
2| 2.2| 3| 12.1| 16| 17.5| 8| 8| 10.5| 50
3| 4| 5| 20.9| 32| 30| 8| 8| 18| 25
3| 5.5| 7.5| 26.4| 40| 35| 8| 8| 24| 20
4| 7.5| 10| 33.3| 40| 45| 16| 5| 30| 15
4| 11| 15| 50.1| 63| 70| 16| 5| 46| 10
380 – 480 (+ / – 10%)V 3 Phase Input, 3 Phase Output
1| 0.75| 1| 3.5| 6| 6| 8| 8| 2.2| –
1| 1.5| 2| 5.6| 10| 10| 8| 8| 4.1| –
2| 1.5| 2| 5.6| 10| 10| 8| 8| 4.1| 250
2| 2.2| 3| 7.5| 16| 10| 8| 8| 5.8| 200
2| 4| 5| 11.5| 16| 15| 8| 8| 9.5| 120
3| 5.5| 7.5| 17.2| 25| 25| 8| 8| 14| 100
3| 7.5| 10| 21.2| 32| 30| 8| 8| 18| 80
3| 11| 15| 27.5| 40| 35| 8| 8| 24| 50
4| 15| 20| 34.2| 40| 45| 16| 5| 30| 30
4| 18.5| 25| 44.1| 50| 60| 16| 5| 39| 22
4| 22| 30| 51.9| 63| 70| 16| 5| 46| 22

NOTE Cable sizes shown are the maximum possible that may be connected to the drive. Cables should be selected according to local wiring codes or regulations at the point of installation.

Troubleshooting

Fault Code Messages

Invertek Drives 3-140022-3F1A Variable Frequency Drive
23

Invertek Drives 3-140022-3F1A Variable Frequency Drive
25

NOTE Following an over current or overload trip (1, 3, 4, 15), the drive may not be reset until the reset time delay has elapsed to prevent damage to the drive.

Invertek Drives Ltd. Offa’s Dyke Business Park, Welshpool, Powys SY21 8JF United Kingdom
Tel: +44 (0)1938 556868 Fax: +44 (0)1938 556869
www.invertekdrives.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals