Invertek Drives OPT-2-ENCOD-IN OPTIDRIVE Encoder Interface User Guide
- June 12, 2024
- Invertek Drives
Table of Contents
- Invertek Drives OPT-2-ENCOD-IN OPTIDRIVE Encoder Interface
- Product Information: OPTIDRIVE Encoder Interface
- LED Status Indication
- Error Code Definitions
- Compatibility
- Specifications
- Error Code Definitions
- Product Usage Instructions
- Compliance
- Option Module Connections
- Operation
- Commissioning
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Invertek Drives OPT-2-ENCOD-IN OPTIDRIVE Encoder Interface
Product Information: OPTIDRIVE Encoder Interface
The OPTIDRIVE Encoder Interface is an option module designed for use with Optidrive P2 and Optidrive Elevator drives. It provides LED status indication for easy monitoring and is compatible with various encoder types.
LED Status Indication
The encoder module has 2 LEDs – LED A (Green) and LED B (Red).
- LED A (Green): Indicates the status of the encoder operation.
- LED B (Red): Indicates fault codes related to the encoder operation.
The fault code is indicated on the drive display. Please see Error Code Defi nitions. For transient faults, the LED will remain illuminated for 50ms to notify a fault on the module.
Error Code Definitions
The following error codes are related to the encoder operation:
Compatibility
The OPTIDRIVE Encoder Interface is compatible with the following product ranges:
- Optidrive P2 (ODP-2-…. Drives)
- Optidrive Elevator (ODL-2-…. Drives)
Model Code
OPT-2-ENCOD-IN (5 Volt TTL Version)
OPT-2-ENCHT (8 – 30 Volt HTL Version)
Compatible Encoder Types
TTL Version : 5V TTL – A & B Channel with Compliment
HTL Version 24V HTL – A & B Channel with Compliment
Note: +24V HTL encoder requires external supply voltage
Specifications
- Power Supply Output: 5V DC @ 200mA Max
- Maximum Input Frequency: 500kHz
- Environmental: 0°C – +50°C
- Terminal Torque: 0.5Nm (4.5 Ib-in)
Error Code Definitions
The OPTIDRIVE Encoder Interface may display error codes related to the encoder operation. The fault code is indicated on the drive display. Please refer to the Error Code Definitions section in the user manual for more information.
Product Usage Instructions
Mechanical Installation
Follow these steps for mechanical installation:
- Insert the Option Module into the Optidrive Option Module Port. Refer to the diagram in the user manual for guidance.
- Ensure that no undue force is used while inserting the option module into the port.
- Make sure the option module is fitted securely before powering on the Optidrive.
- Before tightening connections, remove the terminal block header from the option module. Replace it after wiring is completed.
- Tighten the connections to the torque setting provided in the Specifications section.
Electrical Installation
Follow these steps for electrical installation:
- Use an overall shielded twisted paired cable.
- Connect the shield to Ground (PE) at both ends.
- Do not connect the encoder cable shield to 0V of the drive or encoder module.
- Maintain a minimum distance of 500mm.
- Overall Shielded twisted paired cable to be used
- Shield should be connected to Ground (PE) both Ends
Connection Examples
5V TTL Encoder – OPT-2-ENCOD-IN
24V HTL Encoder – OPT-2-ENCHT
Alternatively (to External supply) the drives on-board 24V supply can be used
(T1 (24V) and T7 (0V)) – Ensure total current consumption from T1 does not
exceed 100mA.
NOTE 0V of encoder must also be connected to drive 0V (T7).
NOTE Do not connect the encoder cable shield to 0V of the drive or
encoder module.
Refer to the user manual for connection examples and follow these notes:
- Ensure that the encoder cable shield is not connected to 0V of the drive or encoder module.
- The 0V of the encoder must be connected to drive 0V (T7).
Operation and Commissioning
When commissioning, follow these steps:
- Commission the Optidrive in Encoderless Vector Speed Control (P6-05 = 0) initially.
- Perform a speed and polarity check to ensure that the feedback signal matches the speed reference in the drive.
Compliance
Hereby, Invertek Drives Ltd declares that the Optidrive Encoder Interface. Model Code: OPT-2-ENCOD-IN and OPT-2-ENCHT is in compliance with Directive 2014/30/EU, 2014/35/EU, 2011/65/EU The EU declaration of conformity is available on request from your Invertek Drives Sales Partner.
Option Module Connections
Operation
Parameter Settings
When operating with an encoder, the following parameter settings are required as a minimum:
- P1-09: Motor rated frequency (found on the motor nameplate).
- P1-10: Motor rated speed (found on the motor nameplate).
- P6-06: Encoder PPR value (enter value for the connected encoder).
Closed Loop Vector speed provides full torque holding capability at zero speed and enhanced operation at frequencies below 1Hz. The drive, encoder module and encoder should be connected according to the voltage rating of the encoder as shown in the wiring diagrams. The encoder cable should be an overall shielded type, with the shield bonded to earth at both ends.
Commissioning
When commissioning, the Optidrive should firstly be commissioned in Encoder less Vector Speed Control (P6-05 = 0), and a speed / polarity check should then be made to ensure that the sign of the feedback signal matches that of the speed reference in the drive. The steps below show the suggested commissioning sequence, assuming the encoder is correctly connected to the Optidrive.
- Enter the following parameters from the motor nameplate:
- P1-07 – Motor Rated Voltage
- P1-08 – Motor Rated Current
- P1-09 – Motor Rated Frequency
- P1-10 – Motor Rated Speed
- To enable access to the advanced parameters required, set P1-14 = 201
- Select Vector Speed Control Mode by setting P4-01 = 0
- Carry out an Auto-tune by setting P4-02 = 1
- Once the Auto-tune is completed, the Optidrive should be run in the forward direction with a low speed reference (e.g. 2 – 5Hz). Ensure the motor operates correctly and smoothly.
- Check the Encoder Feedback value in P0-58. With the Optidrive running in the forward direction, the value should be positive, and stable with variation of + / – 5% maximum. If the value in this parameter is positive, the encoder wiring is correct. If the value is negative, the speed feedback is inverted. To correct this, reverse the A and B signal channels from the encoder.
- Varying the drive output speed should then result in the value of P0-58 changing to reflect the change of the actual motor speed. If this is not the case, check the wiring of the whole system.
- If the above check is passed, the feedback control function can be enabled by setting P6-05 to 1.
Warranty
Complete Warranty Terms and Conditions are available upon request from your IDL Authorised Distributor.
Invertek Drives Ltd
Offa’s Dyke Business Park
Welshpool
Powys, UK
SY21 8JF
www.invertekdrives.com
Optidrive Encoder Interface Module User Guide
Version 2.00