SPER SCIENTIFIC 420001 Electrical Insulation Tester User Manual
- June 3, 2024
- SPER SCIENTIFIC
Table of Contents
- SPER SCIENTIFIC 420001 Electrical Insulation Tester
- SAFETY INFORMATION
- SPECIFICATIONS
- PARTS & CONTROLS
- INSULATION RESISTANCE MEASUREMENTS
- LOW RESISTANCE (CONTINUITY) MEASUREMENTS
- AC/DC VOLTAGE MEASUREMENTS
- BATTERY SAVER (SLEEP MODE)
- POWER TOOLS AND AMALL APPLIANCES
- WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SPER SCIENTIFIC 420001 Electrical Insulation Tester
SAFETY INFORMATION
- Read the following safety information carefully before attempting to operate or service the meter.
- To avoid damages to the instrument do not apply the signals which exceed the maximum limits shown in the technical specifications tables.
- Do not use the meter or test leads if they look damaged. Use extreme caution when working around bare conductors or bus bars.
- Accidental contact with the conductor could result in electric shock.
- Use the meter only as specified in this manual; otherwise, the protection provided by the meter may be impaired.
- Read the operating instructions before use and follow all safety Information.
- Caution when working with voltages above 60V DC or 30V AC RMS. Such voltages pose a shock hazard.
- Before taking resistance measurements or testing acoustic continuity, disconnect circuit from main power supply and all loads from the circuit.
Safety symbols:
Caution refer to this manual before using the meter.
Dangerous voltages.
Meter is protected throughout by double insulation or reinforced insulation.
When servicing, use only specified replacement parts. CE Comply with EN-61010-1
SPECIFICATIONS
General Information Environment conditions:
- Installation CategoriesⅢ
- Pollution Degree 2
- Altitude up to 2000 meters
- Indoor use only
- Relatively humidity 80% max.
- Operation Ambient 0~40ºC
Maintenance & Clearing:
- Repairs or servicing not covered in this manual should only be performed by qualified personnel.
- Periodically wipe the case with a dry cloth. Do not use abrasives or solvents on this instruments.
- Display: Large LCD with dual display
- Measurement Range: 4000MΩ/125V, 4000MΩ/250V, 4000MΩ/500V, 4000MΩ/1000V, 400Ω/BZ, 1000V/DCV. ,750V/ACV
- Sampling Rate: 2.5 times per second.
- Zero Adjustment: Automatic adjustment.
- Over Range Indicator: “OL” of highest digit is displayed.
- Low Battery Indication : The is displayed when the battery Voltage drop below the operating voltage.
- Operating Temperature: 0ºC to 40ºC (32ºF to 104ºF) and Humidity below 80% RH
- Storage Temperature: -10ºC to 60ºC (14ºF to 140ºF) and Humidity below 70% RH
- Power source: DC9V (6×1.5V Size “AA” battery or Equivalent) Dimensions: 200(L) x 92(W) x 50(H) mm
- Weight: Approx 700g include battery
- Accessories: Test leads, 6pcs battery, Carrying case, manual.
Electrical Specifications
Accuracies are specified in the way: ±(…% of reading +…digits) at
23ºC±5ºC,below 80% RH.
OHMS
Range| Resolution| Accuracy| Max. open Circuit Voltage| Overload
Protection
---|---|---|---|---
40.00Ω| 0.01Ω| ****
+ (1.2%+3)
| 5.8V| ****
250Vrms
400.0Ω| 0.1Ω| 5.8V
Continuity Beeper
Range| Resolution| Operation Resistance| Max.open Circuit Voltage| Overload
Protection
---|---|---|---|---
•)))| 0.01Ω| Resistance≤35Ω| 5.8V| 250Vrms
---|---|---|---|---
Short circuit current| ≧200mA
DC Voltage
Range | Resolution | Accuracy | Input Impedance | Overload Protection |
---|---|---|---|---|
1000V | 1V | + (0.8%+3) | 10MΩ | 1000Vrms |
AC Voltage (40Hz~400Hz)
Range| Resolution| Accuracy| Input
Impedance
| Overload Protection
---|---|---|---|---
750V| 1V| + (1.2%+10)| 10MΩ| 750Vrms
Meg OHMS
Terminal Voltage| Range| Resoluti on| Accuracy| Test Current| Short circuit
current
---|---|---|---|---|---
125V(0| 0.125~4.000 MΩ| 0.001MΩ| +(2%+10)| 1mA| ≤1mA
%~+10| 4.001~40.00 MΩ| 0.01MΩ| +(2%+10)| @load|
%)| 40.01~400.0 MΩ| 0.1MΩ| +(4%+5)| 125kΩ|
| 400.1~4000 MΩ| 1MΩ| +(5%+5)| |
250V| 0.250~4.000 MΩ| 0.001MΩ| +(2%+10)| 1mA| ≤1mA
(0%~+1| 4.001~40.00 MΩ| 0.01MΩ| +(2%+10)| @load|
0%)| 40.01~400.0 MΩ| 0.1MΩ| +(3%+5)| 250kΩ|
| 400.1~4000 MΩ| 1MΩ| +(4%+5)| |
500V(0| 0.500~4.000 MΩ| 0.001MΩ| +(2%+10)| 1mA| ≤1mA
%~+10| 4.001~40.00 MΩ| 0.01MΩ| +(2%+10)| @load|
%)| 40.01~400.0 MΩ| 0.1MΩ| +(2%+5)| 500kΩ|
| 400.1~4000 MΩ| 1MΩ| +(4%+5)| |
---|---|---|---|---|---
1000V| 1.000~4.000 MΩ| 0.001MΩ| +(3%+10)| 1mA| ≤1mA
(0%~+1| 4.001~40.00 MΩ| 0.01MΩ| +(2%+10)| @load|
0%)| 40.01~400.0 MΩ| 0.1MΩ| +(2%+5)| 1MΩ|
| 400.1~4000 MΩ| 1MΩ| +(4%+5)| |
PARTS & CONTROLS
- Digital Display
- Data Hold Button; MAX/MIN
- Lock Button
- Backlight Button; ZERO
- Test Button
- Rotary Function switch
- VΩ Jack
- COM input jack
- Pothook
- Battery Cover
How to connect test leads.
On MΩ Range , and 400Ω/BZ ,ACV,.DCV, Connect the red test lead into the “VΩ”
terminal and the black lead into the “COM” terminal.
Battery Check-UP & Replacement
- a) As battery power is not sufficient. LCD will display . Replacement of 6 pcs new batteries, type 1.5V size “AA” is Required.
- b). Place back the battery cover and four the screws.
Test leads check
Set the range select switch to the 400Ω range. With the tip and alligator clip
of the test leads connected. The indicator should read 00.0Ω. When the leads
are not connected the display will read infinity indicated by “OL”. This will
ensure that test lead are under working condition.
Rotary Switch positions
Turn the Tester on by selecting any measurement
Lift < 1000v,500v,250v,125v (4000MΩ)
OFF 400Ω/BZ, 1000VDC,750VAC > Right
Buttons and a display Indicators
- a). Button
HOLD/MAX.MIN : Instant-pressing the “HOLD” button the 1st time, the current values will be hold in the primary display., but it will return in the 2nd pressing ; pressing 2 seconds ,it will enter directly into the “MAX”status, and one another instant-pressing will switch to the “MIN”, if instant-pressing once more, it will recycle ,but exit if pressing 2 seconds again.
LOCK : In the insulation resistance testing function ,press the “LOCK” button ,and then push down the “ TEST” key, it will occur the high-voltage and enter the insulation resistance testing status. Press the “TEST” button once more ,it will shutoff the high-voltage and exit from the insulation resistance testing status.
TEST : In the insulation resistance testing function ,pressing and holding the “TEST” button, The meter will bring high-voltage, and enter into the insulation resistance testing, being free from the “TEST” , it will cutoff the high-voltage and exit form the insulation resistance testing.
ZERO/LIGHT : Iinstant-pressing the “ZERO/LIGHT” button in the 1st time, the current values in the primary display will be set zero,(mainly used for 400Ω, the low resistance testing), ,it will return if in the 2nd time. pressing for 2 seconds, it will enter directly into the “LIGHT” status, and the LCD backlight light up. After 15 seconds, the backlight is shut off automatically, the same as pressing for 2 seconds within 15s.
- b) Display Indicators
The Primary Display :Indicate the current function testing values The Secondary Display: It shows the output DCV while you test the insulation resistance, and the battery voltage while the ACV
- T he Analog Bar: indicate the current function testing value in synchronous with the primary display. :
-
- While testing the insulation resistance, the symbol “
- flashes frequently if the voltage is over 30V.
- While testing the insulation resistance, the symbol” •))) “ flashes frequently and the buzzer warns continually if the outside voltage is over 30V. the symbol “ •))) “ is indicated while LOΩ≤35Ω and the BZ warns continuously.
- While testing the insulation resistance, the symbol “
- LOCK: Push down the “LOCK” button while you test the insulation resistance and the symbol “ ” is indicated. LOBAT:The display shows “LOBAT” when the voltage drops below 7.5V
- MAX/MIN :Stand for the maximum or the minimum.
- ZERO : Digital zero adjusting。
- HOLD :The digital holding function for the primary display. AC,,DC,,:The indicator for the voltage property. V,,MΩ,,Ω The measured dimension units
INSULATION RESISTANCE MEASUREMENTS
- a) Turn the function switch from the “OFF” position to the left(4000 MΩ/1000V—4000/ MΩ500V—4000 MΩ/250V—1000 MΩ/125V),and chose one of the voltage-block( there are 4 ranges namely, 4 MΩ40 MΩ400 MΩ4000 MΩ, can be switched automatically for every voltage-block.)
- b) Connect two testing lines to the tested;
- c) Push down and hold the “TEST” button /or press the “ LOCK” keystoke first and then the “TEST” button, if the tested is electriferous and its voltage ( AC/DC) is over 30V, it will refuse work and no high-voltage testing occurs, simultaneity, it shows “>30V” on the LCD, the symbol “ ” flashes, and the buzzer warns frequently. if the tested is diselectriferous or its voltage is lower than 30V, it will enter into the formal testing process and brings the high-voltage. on the primary display, the insulation resistance in MΩ is indicated in-phase with analog bar; on the secondary display, the tested insulation voltage in V (DC) is indicated, the symbol “ ” flashes and the buzzer warns frequently
- d) Being free from the “TEST” button or pushing down the “TEST” button in the “LOCK “ status can exit from the “LOCK” status and shutoff the high-voltage,synchronously, the resistance values is indicated in the primary display will be held, and the secondary display still be in the status of monitoring the insulation voltage for the tested.
- e) Subsequently, discharge the balance insulation voltage of the tested through the inner switch of the meter.
Turning the function switch can exit automatically from testing status during the process。
LOW RESISTANCE (CONTINUITY) MEASUREMENTS
- a). Set the range switch to 400Ω/BZ Position
- b). Connect the red test lead to the V Ω terminal and black to the COM terminal.
- c). Connect the tips of the test leads to both ends of the circuit under test. read resistance in Ω on the LCD. The two ranges(40.00/400.0Ω) can be switched automatically; the primary display of the resistance in Ω, flashes in synchronous with the analog bar.
- d). When the impedance on circuit is below approximately ≤35Ω.It will indicate by a continuous beeper.
- e) The current is from 200 to 220mA while the tested resistance is 0Ω
- f) The high voltage symbol “ “ flashes along with a primary display of “>30V” and the buzzer warns frequently if the voltage (AC/DC) is more than 30V.
AC/DC VOLTAGE MEASUREMENTS
- a). Set the range switch to ACV or DCV position
- b). Connect red test lead to “V Ω” terminal and black test lead to terminal “COM”.
- c). Connect test prods of test leads IN PARALLEL to the circuit being measured.
- d). Read the voltage value on LCD.
BATTERY SAVER (SLEEP MODE)
The meter will automatically enter the “sleep mode” if there is no function change or button press for 10minutes, but it works as soon as you turn the rotary function switch or push down any button.
POWER TOOLS AND AMALL APPLIANCES
This test would also apply to other similar equipment that has a line cord.
For double insulated power tools, the megohmmeter lead shown connected to the
housing would be connected to some metal part lf the tool(e..g chuck,blade).
Note: The switch of the device must be in the “ON” position and the main
power should be disconnected.
MOTORS
AC-Disconnect the motor from the line by disconnecting the wires at the motor
terminals or by opening the main switch. If the main switch is used and the
motor also has a starter then the starter must be held, by some means, in the
“ON” position. In the latter case, the measured resistance will include the
resistance of the motor, wire and all other components between the motor and
the main switch. If a weakness is in dicated, the motor and other components
should be checked individually. If the motor is disconnected at the motor
terminals, connect one megohmmeter lead to the grounded motor housing and the
other lead to One of the motor leads. DC-Disconnect the motor from the line.
To test the brush rigging, field coils and armature connect one megohmmeter
lead to the grounded motor housing and the other lead to the brush on the
commutator. If the resistance measurement indicates a weakness, raise the
brushes off the commutator and separately test the armature, field coils and
brush rigging by connecting one megohmmeter lead to each of them individually,
leaving the other connected to the grounded motor housing. The above also
applies to DC Gemerators.
CABLES
Disconnect the cable from the line. Also disconnect opposite end to avoid
errors due to leakage from other equipment. Check each conductor to ground and
/or lead sheath by connecting one megohmmeter lead to a ground and /or lead
sheather and the other megohmmeter lead to each of the conductors in turn.
Check insulation resistance between conductors by connecting megohmmeter leads
to conductors in pairs.
WARRANTY
Sper Scientific warrants this product against defects in materials and
workmanship for a period of one (1) year from the date of purchase, and agrees
to repair or replace any defective unit without charge. If your model has
since been discontinued, an equivalent Sper Scientific product will be
substituted if available. This warranty does not cover probes, batteries,
battery leakage, or damage resulting from accident, tampering, misuse, or
abuse of the product. Opening the meter to expose its electronics will break
the waterproof seal and void the warranty.
To obtain warranty service, ship the unit postage prepaid to:
SPER SCIENTIFIC LTD.
8281 East Evans Road, Suite #103
Scottsdale, AZ 85260
The defective unit must be accompanied by a description of the problem and
your return address. Register your product online at www.sperwarranty.com
within 10 days of purchase.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>