SEALEY TA305 AC/DC Clamp Meter and Multimeter Instruction Manual

June 5, 2024
SEALEY

SEALEY TA305 AC/DC Clamp Meter and Multimeter

Thank you for purchasing a Sealey product. Manufactured to a high standard, this product will, if used according to these instructions, and properly maintained, give you years of trouble free performance.

IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY. NOTE THE SAFE OPERATIONAL REQUIREMENTS, WARNINGS & CAUTIONS. USE THE PRODUCT CORRECTLY AND WITH CARE FOR THE PURPOSE FOR WHICH IT IS INTENDED. FAILURE TO DO SO MAY CAUSE DAMAGE AND/OR PERSONAL INJURY AND WILL INVALIDATE THE WARRANTY. KEEP THESE INSTRUCTIONS SAFE FOR FUTURE USE.

SAFETY

  • WARNING! To avoid possible electric shock or personal injury, follow these guidelines:
  • DO NOT use the meter if it is damaged. Before you use the meter, inspect the case. Pay particular attention to the insulation surrounding the connectors.
  • Inspect the test leads for damaged insulation or exposed metal. Check the test leads for continuity. Replace damaged test leads before using the meter.
  • DO NOT use the meter if it operates abnormally. Protection may be impaired. When in doubt, have the meter serviced.
  • DO NOT operate the meter around explosive gas, vapour, or dust. Don’t use it under wet conditions.
  • DO NOT apply more than the rated voltage, marked on the meter, between terminals or between any terminal and earth ground.
  • Before use, verify the meter’s operation by measuring a known voltage.
  • Use caution when working with voltage above 30V ac rms, 42V peak, or 60V dc. Such voltages pose a shock hazard.
  • When using the probes, keep your fingers behind the finger guards on the probes.
  • Connect the common test lead before you connect the live test lead. When you disconnect test leads, disconnect the live test lead first.
  • Remove the test leads from the meter and remove the clamp jaws from the conductor under test before opening the case or the battery cover.
  • DO NOT operate with the battery cover or portions of the case removed or loosened.
  •  To avoid false readings,which could lead to possible, electric shock or personal Injury, replace the batteries as soon as the low battery indicator appears.
  • To avoid electric shock, DO NOT touch any naked conductor with hand or skin.
  • DO NOT hold the meter anywhere beyond the finger guard.
  • Adhere to local and national safety codes. Individual protective equipment must be used to prevent shock and arc blast injury where hazardous live conductors are exposed.
  • DO NOT use the test leads with other equipment.
  • WARNING: When an input terminal is connected to dangerous live potential, this potential can occur at all other terminals! CAT Ill – Measurement (Category Ill is for measurements performed in building installation.) Examples are measurements on distribution boards, circuit breakers, wiring, including cables, bus-bars, junction boxes, switches, socket-outlets in the fixed installation, and equipment for industrial use and some other equipment, for example, stationary motors with permanent connection to fixed installation.
  • DO NOT use the meter for measurements within Measurement Categories IV.
  • WARNING! To avoid possible damage to the meter or to the equipment under test, follow these guidelines:
  • Disconnect circuit power and discharge all capacitors before testing resistance, diode and continuity.
  • Use the proper function and range for your measurements.
  • Before rotating the function switch to change functions, remove test leads from the circuit under test and remove the jaws from the clamped conductor.

INTRODUCTION

Designed for the automotive electrician and conforms to EN61010 CAT III 600V. Ideal for measuring current draw from vehicle components in situ. Features 12mm clamp. Supplied in pouch.
Measures:

  • AC and DC voltage
  • AC and DC current
  • Resistance
  • Audible continuity
  • Diode test

SPECIFICATION

  • Model no: TA305
  • Display: 3 3/4-digit LCD, with a max. reading of 3999
  • Negative Polarity Indication: negative sign shown on the display automatically
  • Over Range Indication: OL shown on the display
  • Jaw Opening Capability: 10mm
  • Max. Measurable Conductor: 10mm
  • Battery: 1.5V battery, AAA or equivalent x2
  • Low Battery Indication: shown on the display
  • Operation Environment: O°C to 40°C, < 75%RH
  • Storage Environment: -10°C- 50°C, < 85%RH
  • Size: 226 x 71 x 38mm
  • Weight: 185g (including batteries}

AC voltage

SEALEY TA305 AC DC Clamp Meter and Multimeter 6

  • Input impedance: 10MΩ
  • Frequency range: 40Hz – 400Hz
  • Max. allowable input voltage: 600V rms
  • Response: Average, calibrated in rms of sine wave

Note: The 400.0mV range is available only in manual range mode.
DC voltage

SEALEY TA305 AC DC Clamp Meter and Multimeter 7

  • Input impedance: range 400.0mV:> 100MΩ
  • Max. allowable input voltage: 600V DC

AC current

SEALEY TA305 AC DC Clamp Meter and Multimeter 8

  • Display: sine wave rms, average response
  • Frequency range: 50 ˜ 60Hz
  • Max. allowable input current: AC100A
  • Response: Average, calibrated in rms of sine wave
  • Temperature coefficient:   ±0.3% of reading/°C

DC current

SEALEY TA305 AC DC Clamp Meter and Multimeter 9

  • Max. allowable input current: DC100A
  • Temperature coefficient:   ±0.3% of reading/°C

Resistance

SEALEY TA305 AC DC Clamp Meter and Multimeter 10

Continuity

SEALEY TA305 AC DC Clamp Meter and Multimeter 11

Note: When the resistance is between 50Ω and 150Ω, the buzzer may or may not sound. When the resistance is more than 150Ω, the buzzer will not sound.
Diode

SEALEY TA305 AC DC Clamp Meter and Multimeter 12

CONTROLS

SEALEY TA305 AC DC Clamp Meter and Multimeter 2

  1. Trigger: Used to open and close jaws.
  2. Function switch: Select desired function as well as to turn meter on and off.
  3. Display: 3¾ – digit LCD, with max. reading of 3999 and unit indication.
  4. COM terminal: Plug in terminal for black test lead.
  5. terminal: “Plug in terminal for the red test lead.
  6. RANGE/ Button:
    • In voltage, current or resistance measurement function this button is used to switch between autorange mode and manual range mode as well as to select desired manual range.
    • (ii) In continuity or diode test function, this RANGE/ button is used to switch between continuity and diode test functions.
  7. HOLD Button: Used to enter/exit Data Hold mode.
  8. In dc current measurements this button is used for zeroing before measurement. In other measurements, this button can be used to enter/exit Relative mode.
  9. inger guard: Used to clamp conductor for current measurements
  10. Jaws : Buzzer Buzzer sounds if a button is pressed. Before the meter turns off automatically, the meter will emit 5 short beeps, 1 minute later it will emit a long beep then turn off automatically.

OPERATION

  • Data Hold Mode:  Press the “ HOLD ‘” button to hold the present reading on the display, will appear on the display as an indicator.  To exit the Data Hold mode, just press this button again, disappears.

  • Relative Mode: Selecting relative mode makes the meter store the present reading as a reference for subsequent measurements and zero the display.Press the button. The meter enters relative mode and stores the present reading for subsequent measurements. The triangle symbol appears on the display as an indicator. The display reads zero. When a new measurement is taken, the display shows the difference between the reference and the new measurement. To exit Relative mode, press the button again and the disappears.
    Note:
    (i) For measurement functions which have both autorange mode and manual range mode, the meter changes to manual range mode automatically when you select Relative mode. Select the desired manual range before you select Relative mode.
    (ii) When you use Relative mode, the actual value of the object under test must not exceed the full-range reading of the selected range. Use a higher range if necessary.

  • Manual Ranging and Autoranging: The meter defaults to autorange mode in measurement functions which have both autorange mode and manual range mode. When the meter is in autorange mode, “Auto” is displayed.
    Press the RANGE/ button to enter the manual range mode. The symbol “Auto“ disappears. E ach press of the RANGE/ button increases the range. When the highest range is reached, the meter scrolls to the lowest range. To exit the manual range mode, press and hold down the RANGE/ button for about 2 seconds. The meter returns to the autorange mode, and “Auto“ appears.
    Note: Only voltage, current and resistance measurement functions have autorange mode and manual range mode.

  • Measuring AC/DC Voltage: Connect black test lead to the COM terminal and the red test lead to the terminal. Set the function switch to the V position for DC, V for AC.Connect the test leads across the source or circuit to be tested. Read the reading on the display. The polarity of the red test lead connection will be indicated as well.
    Note : To avoid electric shock or damage to the meter, do not apply a voltage higher than 600V between terminals.

  • Measuring DC Current: Set the function switch to the A position.If the display does not read zero, press the button for zeroing.Press the trigger and clamp the jaws around the conductor to be tested. Make sure that the jaws are perfectly closed.
    Note:

    •  Only one conductor should be clamped.
    • The conductor should be in the centre of the jaws to get an accurate reading.
    • DO NOT touch any conductor with any part of the body.
  • Read the reading on the display.
    Note:

    • Remove all the test leads from the meter before using the meter for current measurements.
    • After you set the function switch to the A position, wait 5 to 10 minutes before proceeding. This is necessary for accurate measurements.
    •  The meter’s measuring capacity is 100A. Measuring a current higher than 100A will cause a larger measurement error.
    • The reading on the display also indicates the current direction: A positive reading (negative sign “-” does not appear) indicates that the current direction is from the meter’s front to its back. (Note: Current direction is the opposite of electron flow direction).
  •  DO NOT use the meter to measure a circuit’s current if the circuit’s voltage exceeds 600V.

  • Measuring AC Current Set the function switch to the position. Press the trigger and clamp the jaws around the conductor to be tested. Make sure the jaws are perfectly closed.
    Note:

    • Only one conductor should be clamped.
    • The conductor should be in the centre of the stand to get an accurate reading.
    • DO NOT touch any conductor with any part of the body.
  • Read the reading on the display.
    Note:

    • Remove all test leads from the meter before using the meter for current measurements.
    • After the function switch is set to the position, wait 5 to 10 minutes before proceeding. This is necessary to obtain accurate measurements.
    • The meter’s measuring capacity is 100A. Measuring a current higher than 100A will cause a larger measurement error.
    • DO NOT use the meter to measure a circuit’s current if the voltage exceeds 600V.
  • Measuring resistance Connect the black test lead to the COM terminal and the red test lead to the terminal. Set the function switch to the Ω position.Connect the test leads across the object to be tested. Read the reading on the display.
    Note:
    (i) If the resistance is more than 1MΩ it may take several seconds for the reading to stabilise. This is normal for high resistance
    measurements.
    (ii) If the input terminals are in an open circuit state, the over range indicator ”OL” will be shown on the display.
    (iii) Before measurement, disconnect all power to the circuit to be tested and discharge all capacitors thoroughly.

  • iode test: Connect the black test lead to the terminal. (The red test lead is positive “+”.) Set the function range switch to the position. Then press the RANGE button until the symbol appears on the display. Connect the red test lead to the anode of the diode to be tested and the black test lead to the cathode of the diode. Read the approximate forward voltage drop of the diode on the display.

  • Continuity test: Connect the black test lead to the COM terminal and the red test lead to the terminal.Set the range function switch to the position. Then press the RANGE/ until the symbol appears on the display.Connect the test leads across the circuit to be tested.If the resistance is less than about 50Ω, the built-in buzzer will sound.
    Note:Before test, disconnect all power to the circuit to be tested and discharge all capacitors thoroughly

  • Automatic Power Off : If the meter has not been used, or the function switch rotated for about 15 minutes, the meter will turn off automatically and go intoSleep mode. To ‘wake’ the meter from Sleep mode, rotate the function switch or press a button. If the RANGE/ button is pressed to ‘wake’ the meter from Sleep mode, when the function switch is in the or position, the automatic power-off feature will be disabled.

maintenance

Periodically wipe the case with a damp cloth and mild detergent. DO NOT use abrasives or solvents. Cleaning terminals  Dirt or moisture in the terminals can affect readings. Clean the terminals as follows. Turn off the meter and remove test leads. Shake out any dirt that may be in the terminals. Soak a new swab with alcohol. Work the swab around in each terminal. Replace battery
WARNING! Remove the test leads from the meter and remove the jaws from the conductor under test before opening the case or the battery cover.
When the low battery indicator appears on the display the batteries should be replaced immediately.Remove the screw on the battery cover, replace the batteries with new batteries of the same type. Refit the battery cover and screw

Environment Protection

Recycle unwanted materials instead of disposing of them as waste. All tools, accessories and packaging should be sorted, taken to a recycling centre and disposed of in a manner which is compatible with the environment. When the product becomes completely unserviceable and requires disposal, drain any fluids (if applicable) into approved containers and dispose of the product and fluids according to local regulations.

Battery Remova l; sEE SECTION6.3 ABOVE Under the Waste Batteries and Accumulators Regulations 2009, Jack Sealey Ltd are required to inform potential purchasers of products containing batteries (as defined within these regulations), that they are registered with Valpak’s registered compliance scheme. Jack Sealey Ltd Batteries Producer Registration Number (BPRN) is BPRN00705.

Weee Regulations Dispose of this product at the end of its working life in compliance with the EU Directive on Waste Electrical and Electronic Equipment (WEEE). When the product is no longer required, it must be disposed of in an environmentally protective way. Contact your local solid waste authority for recycling information.

SEALEY TA305 AC DC Clamp Meter and Multimeter 5

NOTE: It is our policy to continually improve products and as such we reserve the right to alter data, specifications and component parts without prior notice.
IMPORTANT : No liability is accepted for incorrect use of this product.
WARRANTY: Guarantee is 12 months from purchase date, proof of which will be required for any claim.

Sealey Group, Kempson Way, Suffolk Business Park, Bury St Edmunds, Suffolk. IP32 7AR

TEL: 01284 757500
TEL: 01284 703534
Email: sales@sealey.co.uk
Web site:www.sealey.co.uk

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

SEALEY User Manuals

Related Manuals