Milesight UC50x Series LoRaWAN Controller User Guide

June 5, 2024
Milesight

**Milesight UC50x Series LoRaWAN Controller User Guide

**

Safety Precautions

Milesight will not shoulder responsibility for any loss or damage resulting from not following the instructions of this operating guide.

  • The device must not be remodeled in any way.
  • Do not place the device close to objects with naked flames.
  • Do not place the device where the temperature is below/above the operating range.
  • Make sure electronic components do not drop out of the enclosure while opening.
  • When installing the battery, please install it accurately, and do not install the reverseor wrong model.
  • Make sure both batteries are newest when install, or battery life will be reduced.
  • The device must never be subjected to shocks or impacts.

Declaration of Conformity

UC50x series is in conformity with the essential requirements and other relevant provisionsof the CE, FCC, and RoHS
Symbols

All information in this guide is protected by copyright law. Whereby, no organization or individual shall copy or reproduce the whole or part of this user guide by any means without writtenauthorization from Xiamen Milesight IoT Co., Ltd  Icon
For assistance, please contact
Milesight technical support:
Email: iot.support@milesight.com
Tel: 86-592-5085280
Fax: 86-592-5023065
Address: Building C09, Software ParkIII,
Xiamen 361024, China

Revision History

Date Doc Version Description
Jan. 20, 2021 V 1.0 Initial version
Nov.26, 2021 V 1.1 Description Update
Dec. 9, 2021 V 2.0 Update based on 2.0 hardware

Product Introduction

Overview

UC50x series is a LoRaWAN® controller used for data acquisition from multiple sensors. It contains different I/O interfaces such as analog inputs, digital inputs, digital outputs, serial port sand so on, which simplify the deployment and replacement of LoRaWAN® networks. UC50x series can be easily and quickly configured by NFC or wired USB port. For outdoor applications, it provides solar or built-in battery power supply and is equipped with IP67-rated enclosure and M12 connectors to protect itself from water and dust in harsh environments.

Features
  • Easy to connect with multiple wired sensors through GPIO/AI/RS232/RS485 interfaces
  • Long transmission distance up to 15 km with line of sight
  • Waterproof design including IP67 case and M12 connectors
  • Solar powered and built-in battery optional
  • Quick wireless configuration via NFC
  • Compliant with standard LoRaWAN® gateways and network servers
  • Quick and easy management with Milesight IoT Cloud solution

Hardware Introduction

Packing List

Packing List

If any of the above items is missing or damaged, please contact your sales Representative.

Hardware Overview

Hardware Overview

Data Interface 1:
Icon

Pin Description
1 5V/9V/12V OUT (Switchable)
2 3.3V OUT
3 GND
4 Analog Input 1
5 Analog Input 2
612 5-24V DC IN

Data Interface 2:
Icon

Pin Description
1 5V/9V/12V OUT (Switchable)
2 3.3V OUT
3 GND
4 GPIO1
5 GPIO2
6 RS232/RS485 (Switchable)

7
8| Reserved
Pin| RS232| RS485
6| TXD| A
7| RXD| B

  1. When both DC external power and batteries are connected, external power will be the preferred power supply option.
  2. For UC502, the DC interface can’t be to charge battery
Internal Interfaces

Internal Interfaces

DIP Switch:

Interface DIP Switch
Power Output 12V: 1 on 2 off 3 off

9V: 1 off 2 on 3 off
5V: 1 off 2 off 3 on
Analog Input| 4-20mA ADC: 1 off 2 on 3 on
0-10V ADC: 1 on 2 off 3 off
RS485| Add 120 Ω resistor between A and B: 1 on 2 off 3 off Add 1k Ω pull-up resistor on A: 1 off 2 on 3 off
Add 1k Ω pull-down resistor on B: 1 of 2 off 3 on

Note:

  1. Analog inputs are set to 4-20mA by default, power outputs are set to 12V by default.
  2. Power output on interface 1 is used for powering analog devices, power output on interface2is used for powering serial port devices.

Power Button:

Function Action LED Indication
Turn On Press and hold the button for more than 3s. Off → On
Turn Off Press and hold the button for more than 3s. On → Off
Reset Press and hold the button for more than 10s. Blinks.
Check On/Of Status Quickly press the power button. Light On : Device is

on.
Light Off: Device is off.

Dimensions (mm)

Dimensions \(mm\)

Hardware Switch

When using the analog input or power output of UC50x series, please follow the steps to switch the working mode of hardware interface:

  1. Remove the screw caps and take off the roof cover.
  2. Change DIP switches that are related analog inputs and power outputs as shown in Section 2.3.
  3. Put back the roof cover and screw the screws.
    Note: turn off the device before changing DIP switches.
    Hardware Switch

Operation Guide

Log in the ToolBox

UC50x series can be configured via NFC or Type-C port. Please select one of them to complete configuration.

NFC Configuration

  1. Download and install “Milesight ToolBox” App from Google Play or Apple App Store.
  2. Enable NFC on the smart phone and launch Milesight ToolBox.
  3. Attach the smart phone with NFC area to the device to read device information.
  4. Basic information and settings of the device will be shown on ToolBox App if it’s recognized successfully. You can read and configure the device by tapping the Read/Write device on the App. In order to protect the security of the device, password validation is required when first configuration. The default password is 123456.
    NFC Configuration

Note

  1. Ensure the location of smart phone NFC area and it’s recommended to take off phone case.
  2. If the smart phone fails to read/write configurations via NFC, keep the phone away and backto try again.
  3. UC50x series can also be configured by dedicated NFC reader, which can be purchased from Milesight IoT.

USB Configuration

  1. Download ToolBox software from Milesight IoT website.

  2. Open the case of UC50x and connect the UC50x to computer via type-C port.
    USB Configuration

  3. Open the ToolBox and select type as “General”, then click password to log in ToolBox. (Default password: 123456 )
    USB Configuration

  4. After logging in the ToolBox, you can click “Power On” or “Power Off” to turn on/off device and change other settings.
    Operation Guide

LoRaWAN Settings

LoRaWAN settings is used for configuring the transmission parameters in LoRaWAN® network.

Basic LoRaWAN Settings:
Go to “LoRaWAN -> Basic” of ToolBox software or “Setting -> LoRaWAN Settings” for ToolBoxApp to configure join type, App EUI, App Key and other information. You can also keepall settings by default.
Operation Guide

Parameters Description
Device EUI Unique ID of the device which can also be found on the label.
App EUI Default App EUI is 24E124C0002A0001.
Application Port The port used for sending and receiving data, default port

is 85. Note: RS232 data will be transmitted via another port.
Working Mode| UC501: Class A and Class C are available;
UC502: Class A.
Join Type| OTAA and ABP mode are available.
Application Key| Appkey for OTAA mode, default is 5572404C696E6B4C6F52613230313823.
Device Address| DevAddr for ABP mode, default is the 5th to 12th digits of SN.
Network Session Key| Nwkskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.
Application Session Key| Appskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.
Spread Factor| If ADR is disabled, the device will send data via this spread factor.
Confirmed Mode| If the device does not receive ACK packet from network server, it will resend data 3 times at most.
Rejoin Mode| Reporting interval ≤ 30 mins: the device will send specific mounts of LoRaMAC packets to check connection status every 30 mins; If no reply after specific packets, the device will re-join.
| Reporting interval > 30 mins: the device will send specific mounts of LoRaMAC packets every to check connection status every reporting interval; If no reply after specific packets, the device will re-join.
ADR Mode| Allow network server to adjust datarate of the device.
Tx Power| Tx power of the device.

Note:

  1. Please contact sales for device EUI list if there are many units.
  2. Please contact sales if you need random App keys before purchase.
  3. Select OTAA mode if you use Milesight IoT cloud to manage devices.
  4. Only OTAA mode supports rejoin mode

LoRaWAN Frequency Settings:
Go to “LoRaWAN - > Channel” of ToolBox software or “Setting -> LoRaWAN Settings” for ToolBox APP to select supported frequency and select channels to send uplinks. Make sure the channels match the LoRaWAN® gateway
Operation Guide

If frequency is one of CN470/AU915/US915, you can enter the index of the channel that you want to enable in the input box, making them separated by commas.
Examples:
1, 40: Enabling Channel 1 and Channel 40
1-40: Enabling Channel 1 to Channel 40
1-40, 60: Enabling Channel 1 to Channel 40 and Channel 60
All: Enabling all channels
Null: Indicates that all channels are disabled
Operation Guide

Note:
For -868M model, default frequency is EU868;
For -915M model, default frequency is AU915.

Interface Settings

UC50x series support data collection by multiple interfaces including GPIOs, analog input sand serial ports. Besides, it can also power the terminal devices by power output interfaces. Basic settings are as follows:
Go to “General -> Basic” of ToolBox software or “Setting -> General Settings” page to change the reporting interval.
Operation Guide

Parameters Description
Reporting Interval Reporting interval of transmitting data to network server.

Default: 20 mins, Range: 1-1080 mins.
Note: RS232 transmission will not follow the reporting interval.
The device returns to the power supply state| If the device loses power and return to power supply, the device will be on or off according to this parameter.
Interface 1/2 3V3 Output| Enable 3.3V power output. After enabled, the power output will supply power continuously.
Change Password| Change the password for ToolBox APP or software to read/write this device.

RS485 Settings

  1. Connect RS485 device to RS485 port on interface If you need UC50x to power the RS485 device, please connect the power cable of RS485 device to 5V/9V/12V power output on interface 2.
  2. Go to “General -> Serial” of ToolBox software or “Setting -> Serial Setting” to enable RS485 and configure serial port settings. Serial port settings should the same as RS485 terminal devices.
    Operation Guide Parameters| Description
    ---|---
    Interface 2(Pin 1) 5V/9V/12V| Enable 5V/9V/12V power output of interface 2 to supply power to RS485 terminal devices. It’s 12V by default and you can change DIP switches to change voltage.
    Power Output Time Before Collect| UC50x will power the RS485 terminal devices for a period of time before collecting data for terminal device initialization.
    Baud Rate| 1200/2400/4800/9600/19200/38400/57600/115200 are available.
    Data Bit| 8 bit is available.
    Stop Bit| 1 bit/2 bit are available.
    Parity| None, Odd and Oven are available.
    Execution Interval| The execution interval between each Modbus command.
    Max Resp Time| The maximum response time that the UC50x waits for the reply to the command. If it does not get a response after the max response time, it is determined that the command has timed out.

Max Retry Time

| Set the maximum retry times after device fails to read data from RS485

terminal devices.

Modbus RS485 bridge LoRaWAN| If this mode is enabled, UC50x will transparent Modbus RTU commands from network server to RS485 terminal devices and send Modbus reply originally back to network server.
Port: Select from 2-84, 86-223.

Note: When you use power output to power RS485 Modbus slave devices, it only supplies power when reporting interval is coming. It’s suggested to power slave devices with external power during the PoC test.

  1. Click to add Modbus channels, then save configurations
    Operation Guide
Parameters Description
Channel ID Select the channel ID you want to configure, 16 channels

selectable.
Name| Customize the name to identify every Modbus channel.
Slave ID| Set Modbus slave ID of terminal device.
Address| The starting address for reading.
Quantity| Set read how many digits from starting address. It fixes to 1.
Type| Select data type of Modbus channels.
Sign| The tick indicates that the value has a plus or minus sign.

Example: If you configure as following picture, UC50x will send Modbus read command to terminal device regularly: 01 03 00 00 00 01 84 0A
Operation Guide

  1. For ToolBox software, click “Fetch” to check if UC50x can read correct data from terminal devices. You can also click “Fetch” on the top of list to fetch all channel data.
    Operation Guide
    Note: Please do not click “Fetch” frequently since response time to reply is differ for every terminal device.

For ToolBox App,

a. Tap every Modbus channel, click “Collect” and attach smart phone to device to make device collect data.

b. Click “Fetch” and attach smart phone to make APP read the data. You can also tap“Collect All” and “Fetch All” to fetch all channel data.

RS232 Settings

  1. Connect RS232 device to RS232 port on interface If you need UC501 to power theRS232device, connect the power cable of RS232 device to 5V/9V/12V power output on interface 1.
  2. Go to “General - > Serial” of ToolBox software or “Setting - > Serial Setting” to enable RS232 and configure serial port settings. Serial port settings should the same as RS232 terminal devices.
    Operation Guide
Parameters Description
Interface 2(Pin 1) 5V/9V/12V Enable 5V/9V/12V power output of interface 2 to

supply power to RS232 terminal devices continuously. Only UC501 supports this feature.
Note: Power output is 12V by default and you can change DIP switches to change voltage.
Baud Rate| 300/1200/2400/4800/9600/19200/38400/57600/115200 are available.
Data Bit| 8 bit is available.
Stop Bit| 1 bit/2 bit are available.
Parity| None, Odd and Oven are available.
Port| The port used for RS232 data transmission.

GPIO Settings

  1. Connect devices to GPIO ports on interface 2.

  2. Go to “General - > GPIO” of ToolBox software or “Setting - > GPIO Setting” to enable GPIOport
    Operation Guide

  3. Select GPIO type according to your requirements.

    • Digital Input: detect high or low status of devices;
    • Digital Output: Send voltage signal to trigger devices;
    • Counter: pulse counter.

Digital Input:

Select initial status of digital input. If pull up is selected, falling edge will be triggered; if pull down is selected, rising edge will be triggered. After selection, click “Fetch” to check current status of digital input.
Operation Guide

Digital Output:

Click “Switch” to check if UC50x can trigger devices by digital output or click “Fetch” to check current status of digital output
Operation Guide

Pulse Counter:

Operation Guide

Parameters Description
Digital Input Initial status of counter.

Pull Down: Increase 1 when detecting rising edge Pull Up/None: Increase 1 when detecting falling edge
Digital Filter| It’s recommended to enable when pulse period is greater than 250 us.
Keep last value when power off| Keep the counted values when the device powers off.
Start/Stop| Make the device start/stop counting.
Note: UC50x will send non-changable counting values if you do not click “Start”.
Refresh| Refresh to get latest counter values.
Clear| Count the value from 0.

AI Settings

  1. Connect analog device to analog input ports on interface 1. If you need UC50x to power the analog device, connect the power cable of analog device to 5V/9V/12V power output on interface 1.

  2. Go to “General - > AI” of ToolBox software or “Setting - > AI Setting” to enable analog input.
    Operation Guide

  3. Select analog input type according to analog device type. Note: Ensure DIP switches has changed before changing “Analog Input Signal Type” to 0-10V.

  4. Enable “Interface 1 (Pin 1) 5V/9V/12V” and configure “Power Output Time Before Collect”, UC50x will power the analog devices for a period of time before collecting data.
    Operation Guide
    Note: When you use power output to power analog devices, it only supplies power when reporting interval is coming. It’s suggested to power slave devices with external power during the PoC test.

  5. For ToolBox software, click “Fetch” to check if UC50x can read correct data from analog devices.
    Operation Guide

For ToolBox App,

a. Click “Collect” and attach smart phone to device to make device collect data. b. Click “Fetch” and attach smart phone to make APP read the data.
Operation Guide

Maintenance

Upgrade

ToolBox Software:

  1. Download firmware from www.milesight-iot.com to your PC.
  2. Go to “Maintenance -> Upgrade” of ToolBox software, click “Browse” to import firmware and upgrade the device. You can also click “Up to Date” to search for the latest firmware of the device and upgrade.
    Operation Guide

ToolBox App:

  1. Download firmware from www.milesight-iot.com to your smart phone.
  2. Open ToolBox App and click “Browse” to import firmware and upgrade the device.

Note:

  1. Operation on ToolBox is not supported during the upgrade.
  2. Only Android version ToolBox supports the upgrade feature.
    Operation Guide

Backup

UC50x devices support configuration backup for easy and quick device configuration in bulk. Backup is allowed only for devices with the same model and LoRa frequency band. Please select one of following methods to backup device:

ToolBox Software:

  1. Go to “Maintenance -> Backup and Reset”, click “Export” to save current configuration as json format backup file.
  2. Click “Browse” to select backup file, then click “Import” to import the configurations.
    Operation Guide

ToolBox App:

  1. Go to “Template” page on the App and save current settings as a template. You can also edit the template file.
  2. Select one template file which saved in the smart phone and click “Write”, then attach to another device to write configuration.
    Operation Guide

Reset to Factory Default

Please select one of following methods to reset device:
Via Hardware: Open the case of UC50x and hold on power button more than 10s.
Via ToolBox Software: Go to “Maintenance   - > Backup  and Reset” to click “Reset”.
Operation Guide

Via ToolBox App: Go to “Device -> Maintenance” to click “Reset”, then attach smart phone with NFC area to UC50x to complete reset.
Operation Guide

Installation

UC50x series support wall mounting or pole mounting. Before installation, make sure you have the mounting bracket, wall or pole mounting kits and other required tools.

Wall Mounting:

  1. Fix the wall plugs into the wall, then fix the mounting bracket to the wall plugs with screws.
  2. Put the device on the mounting bracket, then fix the bottom of the device to the bracket with a fixing screw.
    Installation1

Pole Mounting:

  1. Straighten out the hose clamp and slide it through the rectangular rings in the mounting bracket, wrap the hose clamp around the pole. After that use a screwdriver to tighten the locking mechanism by turning it clockwise.
  2. Put the device on the mounting bracket, then fix the bottom of the device to the bracket with a fixing screw.
    Installation

Milesight IoT Cloud Management

UC50x series can be managed by Milesight IoT Cloud platform. Milesight IoT cloud is a comprehensive platform that provides multiple services including device remote management and data visualization with the easiest operation procedures. Please register a Milesight IoT Cloud account before operating following steps.

  1. Ensure Milesight LoRaWAN® gateway is online in Milesight IoT Cloud. For more info about connecting gateway to cloud please refer to gateway’s user guide.
    Milesight IoT Cloud Management

  2. Go to “My Devices” page and click “+New Devices”. Fill in the SN of UC50x and select associated gateway.

  3. For UC501, click and go to “Basic Settings” to change class type the same as device settings.
    Milesight IoT Cloud Management

  4. After UC50x is online in Milesight IoT Cloud, click  and go to “Interface Settings” to select used interfaces and customize the name, sign and formulas.
    Note: Modbus channel settings should be the same as the configuration in ToolBox.
    Milesight IoT Cloud Management

Device Payload

UC50x Series use the standard Milesight IoT payload format based on IPSO. Please refer to the UC50x Series Communication Protocol; for decoders of Milesight IoT products please click here.

www.milesight-iot.com

Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals