FLOMEC 4-20mA Module G2 1 Inch Stainless Steel Flowmeter Owner’s Manual
- June 5, 2024
- Flomec
Table of Contents
FLOMEC 4-20mA Module G2 1 Inch Stainless Steel Flowmeter
4-20mA MODULE
FOR USE WITH MOST FLOMEC TURBINE METERS WITH Q9 DISPLAY
FLOMEC QSE meters have their own 4-20mA module
Please save these instructions for future reference. Read carefully before
attempting to assemble, install, operate or maintain the product described.
Protect yourself and others by observing all safety information. Failure to
comply with instructions could result in personal injury and/or property
damage.
Please refer to back cover for information regarding this product’s warranty
and other important information.
DO NOT RETURN THIS PRODUCT TO THE STORE!
Please contact Great Plains Industries, Inc.® before returning any product. If
you are missing parts, or experience problems with your installation, contact
our Customer
Support Department. We will be happy to assist you.
Call: 888-996-3837 or
316-686-7361
Email: meters@gplains.com
BEFORE YOU BEGIN
Usage Requirements
- This 4-20mA module is not FM Approved. Therefore, use of this module with an approved metering system voids FM Approval.
- This 4-20mA module requires an input power of 8-32 volts DC (24 VDC is recommended).
- This 4-20mA module is designed for use with most* FLOMEC meters that are equipped with the Q9 display option. The 4-20mA module can be field calibrated through the configuration menu options on the Q9 display.
FLOMEC QSE meters have their own 4-20mA module.
UNPACKING/INSPECTION
Inspect
- After unpacking the unit, inspect carefully for any damage that may have occurred during transit. Check for loose, missing or damaged parts. Shipping damage claims must be filed with carrier.
- See General Safety Instructions, and all Cautions, Warnings, and Dangers as shown.
SPECIFICATIONS
Mechanical|
---|---
Housing material:| Nylon 6/6
Strain relief:| Hubble PG7. Grip range (Cable Outside Diameter)
0.11 – 0.26 in. (2.8 – 6.6 mm)
Housing port thread:| Female 1/2-20 UNF-2B (Compatible with PG7)
Cable| Belden 9363 (22 AWG-3 conductor
with drain wire and shield)
Cable length| 10 ft. (3m), provided
Operating Temperature| 0° to +140°F (-18° to +60°C)
Higher Process Fluid Temperatures Obtainable with G2 Stainless Steel
Meters| When installed on G2 Stainless Steel Flowmeters, see Ambient and
Fluid Temperature Limits graph on next page for higher process fluid
temperature Limits.
If wider process fluid temperature ranges are desired, reference information on FLOMEC® Remote Kits.
Storage temperature:| -40° to +180°F (-40° to +82°C)
Power:|
Type:| Loop powered
Voltage minimum:| 8 VDC
Voltage maximum:| 32 VDC
Isolated:| No
Primary Output (4-20mA):
Type:| Loop
Minimum:| 4 mA
Maximum:| 25 mA
Scaled Pulse Output:
Type:| Open Collector (NPN), Current Sinking
External Pull Up Voltage 1| 8.0 to 26 VDC
Internal Pull Up Voltage
2
| 5.0 VDC
- NOTE: Customer supplied external voltage with separate power supply and a minimum external pull up resistance of 820 ohms.
- NOTE: 5VDC supplied internal on the 4-20mA board, no external supply or pull up resistor required. Internal pull up is fixed at 100K ohm
AMBIENT AND FLUID TEMPERATURE LIMITS
NOTE: The upper limit of the “Useable Combination” area can be increased by 10°F (6°C) when lithium batteries are installed in the Q9 Display.
Dimensions
| Length (A)| Height (B)| Width (C)| Strain Relief (D)
---|---|---|---|---
4-20mA Module
| 3.45 in. (88 mm)| 0.90 in. (23 mm)| 2.18 in. (55 mm)| 0.86 in. (22 mm)
Module shown installed on G2 1” stainless steel flowmeter
Figure 1
Note: This 4-20mA module is designed for use with most* FLOMEC meters that are equipped with the Q9 display option. The 4-20mA module can be field calibrated through the configuration menu options on the Q9 display.
FLOMEC QSE meters have their own 4-20mA module.
APPROVAL RATINGS
INSTALLATION
Installing Module
NOTE: Factory installed 4-20mA modules will have the zero set to the
meter’s minimum specified flow rate and the span will be set to the meter’s
maximum specified flow rate.
-
Remove the display electronics from the front of the turbine.
NOTE: If you are installing more than one module at a time, take care to keep the proper electronics paired with the original turbine.
NOTE: If your display currently has batteries installed, you will need to remove them to enable the 4-20mA and scaled pulse output to function. -
Disconnect 2-pin coil connector from display. Make sure coil remains firmly attached to meter body (DO NOT pull on wires or attempt to remove from meter body).
-
Connect the 4-20mA Module to the 10-pin connector located on the backside of the computer electronics (see Figure 2).
-
Reconnect the coil connector to the 2-pin terminal block on the other end of the computer backside. Once the cables are installed on the display, the housing of the display can be placed on top of the 4-20mA module (see Figure 2).
-
Install the computer electronics to the front side of the turbine. Tighten the four screws snugly.
Module shown installed on G2 1” stainless steel flowmeter
Figure 2
Wiring
The 4-20mA module comes pre-wired for external connections to external power and provides an open collector output, which can be set to either raw or scaled pulse output. The wires are color coded to connect as shown in Figures 3 & 4.
Wire Color Feature
Red| 4-20mA (+)
Black| 4-20mA (-)
White| Pulse Out (+)
Uninsulated| Pulse Out (-)
NOTE: The 4-20mA board provides a pulse output on the White wire with the cable shield as the ground (return). This is set to raw pulse output as the default setting on the Q9 display. If your application requires a scaling of the pulse output, refer to the installation instructions to enable the scaled pulse feature and refer to the Q9 owner’s manual for instructions on the configuration of the scaled pulse feature.
- If using the scaled pulse output feature, use the scaled K-factor in the user interface device.
- The ground of the pulse output must be galvanically isolated from the 4-20mA loop ground (return).
NOTE: The internal and external options for the pull up resistance and
voltage is selectable by the header on the 4-20mA board (see Figures 4a & 4b).
When the Jumper is on the top two pins, the “external resistor required”
option is selected (Figure 4a). This external resistor can be installed as
shown on Figure 3, but could also be built into the existing customer
equipment.
When the Jumper is located on the bottom two pins, the “internal resistor”
option is selected (Figure 4b).
OPERATION
Adjusting ZERO and SPAN
To set or adjust ZERO and SPAN settings, refer to the Q9 Owner’s Manual (Non-
Agency) Configuration Mode (Daughter Board Options) and Calibration Mode
Section for further instructions.
NOTE: The Q9 Display controls the 4-20 mA settings. It is recommended to
verify and set (if necessary) the most optimal Calibration Method of the Q9
Display (see Q9 Owner’s Manual referenced above) before adjusting 4-20mA
settings.
You can download the Q9 Owner’s Manual (Non-Agency) here:
or visit flomecmeters.com to download owner’s manuals and other technical documents.
TROUBLESHOOTING
Symptom | Possible Cause(s) | Corrective Action |
---|---|---|
1. Incorrect or no input power. |
2. Not wired correctly.
3. Broken connection.
4. Defective PC board connector.
5. Defective unit.
6. Batteries installed.
| 1. Supply correct power requirements.
| 2. Check owner’s manual for correct installation.
A. No output signal.
| 3. Check resistance to determine location of break.
4. Contact distributor or factory for replacement
| 5. Contact distributor or factory for replacement.
| 6. Remove batteries and cycle loop power.
| 1. ZERO and SPAN not set correctly on the Q9 display.| 1. Check Q9 owner’s
manual for instructions on how to set ZERO and SPAN for meter.
B. Signal not between 4-20mA when fluid is flowing.
| 2. 4-20 mA Module output signal “ZERO” and “SPAN” does NOT match customer’s
recording device “ZERO” and “SPAN” settings.| 2. Reconfigure 4-20mA Module
output signal “ZERO” and “SPAN” to match Customer’s recording device “ZERO”
and “SPAN” (or vice versa).
| 3. Q9 display calibration is NOT optimized for best results.| 3. Verify Q9
display value is giving correct flowrate.
C. Scaled Pulse output not working or not shown in Q9 configuration options
menu.| 1. Batteries being installed will disable the Scaled Pulse output
feature.| 1. Remove batteries, cycle loop power and reconfigure the Scaled
Pulse output feature on Q9 display.
D. Pulse output values are not giving accurate total volumes.
| 1. Customer’s “pulse Input device” (pulses per unit of volume) does not
match module pulse output (pulses per unit of volume).| 1. Reconfigure module
pulse output (or customer’s “pulse input device”) to match in pulses per unit
of volume (module output pulses per unit of volume = input pulses per unit of
volume).
| 2. Q9 display calibration is NOT optimized for best results.| 2. Verify Q9
display value is giving correct volume totals.
E. Q9 display value not giving correct Flowrate.
| 1. Q9 display showing velocity or volume totals instead of flowrate.
2. Q9 display calibration is not optimized for best results.
| 1. Press “top button” of Q9 display until flowrate is displayed (see Operation Section in Q9 owner’s manual).
2. If “1” above is not the Issue, See Operation/Calibration Section of this manual
---|---|---
F. Q9 display value not giving correct volume totals.
| 1. Q9 display showing velocity, flowrate, or accumulative total instead of batch total.
2. Q9 display calibration is not optimized for best results.
| 1. Press “bottom button” of Q9 display until correct volume is displayed (see Operation Section in Q9 owner’s manual).
2. If “1” above is not the Issue, see Operation/Calibration Section of this manual.
PARTS LIST
Part Number | Description |
---|---|
901002-52 | Seal |
PARTS & SERVICE
For warranty consideration, parts, or other service information, please contact your local distributor. If you need further assistance, contact the GPI Product Support Department in Wichita, Kansas, during normal business hours.
A toll free number is provided for your convenience.
1-888-996-3837
To obtain prompt, efficient service, always be prepared with the following
information:
- The model number of your meter.
- The serial number or manufacturing date code of your meter.
- Part descriptions and numbers.
For warranty work, always be prepared with your original sales slip or other evidence of purchase date.
IMPORTANT: Please contact GPI before returning any parts. It may be possible to diagnose the trouble and identify needed parts in a telephone call.
CAUTION
Do not return this product without prior approval from the GPI Product Support Department. Due to strict government regulations, GPI cannot accept parts unless they have been drained and cleaned.
WEEE DIRECTIVE
FLOMEC® TWO-YEAR LIMITED WARRANTY
Great Plains Industries, Inc. 5252 E. 36th Street North, Wichita, KS USA
67220-3205, hereby provides a limited warranty against defects in material and
workmanship on all products manufactured by Great Plains Industries, Inc. This
product includes a 2-year warranty.
Manufacturer’s sole obligation under the foregoing warranties will be limited
to either, at
Manufacturer’s option, replacing or repairing defective Goods (subject to
limitations hereinafter provided) or refunding the purchase price for such
Goods theretofore paid by the
Buyer, and Buyer’s exclusive remedy for breach of any such warranties will be
enforcement of such obligations of Manufacturer. The warranty shall extend to
the purchaser of this product and to any person to whom such product is
transferred during the warranty period.
The warranty period shall begin on the date of manufacture or on the date of
purchase with an original sales receipt. This warranty shall not apply if:
A. the product has been altered or modified outside the warrantor’s duly
appointed representative;
B. the product has been subjected to neglect, misuse, abuse or damage or has
been installed or operated other than in accordance with the manufacturer’s
operating instructions.
To make a claim against this warranty, or for technical assistance or repair,
contact your
FLOMEC distributor or contact FLOMEC at one of the locations below.
In North or South America contact
Great Plains Industries, Inc.
5252 East 36th St. North
Wichita, KS 67220-3205
USA
888-996-3837
www.flomecmeters.com
(North America)
Outside North or South America contact
GPI Australia
(Trimec Industries Pty. Ltd.)
12/7-11 Parraweena Road
Caringbah NSW 2229
Australia
+61 02 9540 4433
www.flomec.com.au
The company will step you through a product troubleshooting process to determine appropriate corrective actions.
GREAT PLAINS INDUSTRIES, INC., EXCLUDES LIABILITY UNDER THIS WARRANTY FOR
DIRECT, INDIRECT, INCIDENTAL AND CONSEQUENTIAL DAMAGES INCURRED IN THE USE OR
LOSS OF USE OF THE PRODUCT WARRANTED HEREUNDER.
The company herewith expressly disclaims any warranty of merchantability or
fitness for any particular purpose other than for which it was designed.
This warranty gives you specific rights and you may also have other rights
which vary from
U.S. state to U.S. state.
NOTE: In compliance with MAGNUSON MOSS CONSUMER WARRANTY ACT – Part 702 (governs the resale availability of the warranty terms).
© 2021 Great Plains Industries, Inc., All Rights Reserved.
Great Plains Industries, Inc. /
888-996-3837 /
flomecmeters.com
References
- Great Plains Industries Fuel Transfer Pumps and Flow Meter Systems — GREAT PLAINS INDUSTRIES
- FLOMEC Flow Meters - Flow Meter & Instrumentation Manufacturer
- Great Plains Industries Fuel Transfer Pumps and Flow Meter Systems — GREAT PLAINS INDUSTRIES
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>