LiftMaster LA250EVK Double Swing Gate Opener Kit Installation Guide
- June 5, 2024
- LiftMaster
Table of Contents
LA250EVK / LA300EVK **Swing Gate Operator Installation
Manual* T0341-427200
**www.deltadoors.nl
- For GB (UK, NI) specific information on national regulations and requirements see English part of the manual.
SAFETY INSTRUCTIONS AND INTENDED USE
About this Manual – Original Manual
These instructions are the original operating instructions according the
machinery directive 2006/42 EC. The instruction manual must be read carefully
to understand important product information. Pay attention to the safety and
warning notices. Keep the manual in safe place for future reference and to
make it available to all persons for inspection, service, maintenance and
repair. After installation pass the complete documentation to the responsible
person/owner.
Qualification of a competent installer
Only correct installation and maintenance by a competent installer
(specialist) / competent company, in accordance with the instructions, must
understand and ensure the safe and intended function of the installation.
Specialist is, who on the basis of their technical training and experience,
has sufficient knowledge in the field of powered gates and moreover is
familiar with relevant state occupational safety regulations and generally
accepted rules of technology in such an extent that he is also able to assess
the safe working condition of powered gates according to EN 13241, 12604,
12453 (EN12635)
The installer must understand the following:
Before installing the drive, check that the driven part is in good mechanical
condition, opens and closes properly and correctly balanced where applicable
Before first use and at least annually a specialist must inspect powered gate
regarding their safe condition. After installation, the installer must ensure
that the mechanism is properly adjusted and that the protection system and any
manual release function correctly (EU: EN 13241, EN12604, EN 12453, EN 12635;
GB (UK, NI) BS EN 13241, BS EN12604, BS EN 12453, BS EN12635). A regular
maintenance, inspection must be carried out according to the standards. The
installer must instruct other users on the safe operation of the drive system.
After successful installation of the drive system, the responsible installer,
in accordance with the EU: Machinery Directive 2006/42/EC; GB (UK, NI): Supply
of Machinery (Safety) Regulations 2008 SI 2008 No. 1597, must issue the EU: CE
/ GB (UK,NI): UK declaration of conformity for the gate system. The EU: CE /
GB (UK,NI): UKCA
mark label must be attached to the gate system. This is also obligatory in the
process of retrofitting on a manually operated gate. Further, a handover pack
and an inspection book must be completed.
After successful installation of the drive system, the responsible installer,
in accordance with the EU: Machinery Directive 2006/42/EC; GB (UK, NI): Supply
of Machinery
(Safety) Regulations 2008 SI 2008 No. 1597, must issue the EU: CE / GB
(UK,NI): UK declaration of conformity for the gate system. The EU: CE / GB
(UK,NI): UKCA
mark label must be attached to the gate system. This is also obligatory in the
process of retrofitting on a manually operated gate. Further, a handover pack
and an inspection book must be completed.
Please read the operating instructions and especially the precautions. The
following symbols are placed in front of instructions to avoid personal injury
or damage to property. Read these instructions carefully.
Warnings Symbols
The general warning symbol indicates a danger that can lead to injuries or
death. In the text section, the general warning symbols are used as described
below.
DANGER Symbol| WARNING Symbol| CAUTION Symbol| ATTENTION
Symbol
---|---|---|---
DANGER| WARNING| CAUTION| ATTENTION
Indicates a danger that leads directly to death or serious injuries.|
Indicates a danger that can lead to death or serious injuries.| Indicates a
danger that can lead to damage or destruction of the product.| Indicates a
danger that can lead to damage or destruction of the product.
Intended use
The swing gate operator is exclusively designed and tested for the operation
of smooth-running swing gates in the residential, and non-commercial sector.
Specification for gates are defined under mechanical requirements according to
EU: EN12604 / GB (UK, NI): BS EN 12604.
The maximum permissible gate size and the maximum weight must not be exceeded.
The gate must open and close smoothly by hand. Use the operator on gates which
comply with the applicable standards and guidelines. Regional conditions of
wind loads must be taken into account when using door or gate panels EU:
EN13241 / GB (UK, NI): BS EN 13241. Observe the manufacturer‘s specifications
regarding the combination of door and operator. Possible hazards within the
meaning of EU: EN13241 / GB (UK, NI): BS EN 13241 are to be avoided by
designing and installing the door/gate according to the relevant instructions.
This gate mechanism must be installed and operated in accordance with the
appropriate safety rules.
Improper use
It is not intended for continuous operation and use in a commercial
application.
The construction of the drive system is not designed for the operation of
gates outside of manufacturer’s specification.
It is not permitted on gates that travel with incline/decline.
Any improper use of the drive system could increase the risk of accidents. The
manufacturer assumes no liability for such usage. With this drive, automated
gates must comply with the current, valid international and country-
specific/local standards, guidelines and regulations (EU: EN 13241, EN12604,
EN 12453; GB (UK, NI) BS EN 13241, BS EN12604, BS EN 12453).
Only LiftMaster and approved accessories may be connected to the drive.
Incorrect installation and/or failure to comply with the following
instructions may result in serious
personal injury or damage to property.
Gate systems located in public areas and have only force limitation, can only
be operated under full supervision.
Additional safety devises should be considered in accordance with EU: EN
12453; GB (UK, NI) BS EN 12453.
1. SAFETY INSTRUCTIONS AND INTENDED USE
During operation, the gate should not under any circumstances obstruct public
path ways and roads (public area).
When using tools and small parts to install or carry out repair work on a gate
exercise caution and do not wear rings, watches or loose clothing.
To avoid serious personal injury due to entrapments, remove any locking device
fitted to the gate in order to prevent damage to the gate.
Installation and wiring must be in compliance with your local building and
electrical installation regulations. Power cables must only be connected to a
properly earthed supply.
Disconnect electric power to the system before installation, maintenance,
repairs or removing covers. A disconnecting device must be provided to the
mains power supply (permanently-wired installation) to guarantee all-pole
disconnection (isolating switch or by a separate fuse). The repairs and
electrical installations may be performed only by an authorised electrician.
Emergency Stop Button must be installed for emergency case based on the risk
assessment.
Ensure that entrapment between the driven part and the surrounding fixed parts
due to the opening movement of the driven part is avoided by respecting the
given safety distances in accordance with the EU: EN 13241, EN12604, EN 12453,
EN 12635; GB (UK, NI) BS EN 13241, BS EN12604, BS EN 12453, BS EN12635 and/or
with
safety devices (e.g. safety edge).
Testing of the safety function of the drive system is recommended to be
carried out at least once a month. Refer also to manufacturers instruction of
the gate system components.
After the installation a final test of the full function of the system and the
of the safety devices must be made and all users must be instructed in the
function and operation of the swing gate operator.
Gate systems must meet the force limitation according EU: EN 12453, EN
60335-2-103; GB (UK, NI) BS EN 12453, BS EN 60335-2-103.
Additional safety device (safety edge,.) must be considered in accordance to
the standard by changes to the system.
It is important to make sure that the gate always runs smoothly. Gates which
stick or jam must be repaired immediately. Employ a qualified technician to
repair the gate, never attempt to repair it yourself. This device is not
intended for use by persons (including children) with restricted physical,
sensory or mental abilities or lack of experience or knowledge, unless they
are supervised by a person responsible for their safety or have received
instruction in how to use the device. If necessary, control equipment MUST be
mounted within sight of the gate and out of reach of children. Children should
be supervised to ensure that they do not play with the device. Do not allow
children to operate push button(s) or remote(s). Misuse of the gate operator
system can result in serious injury.
The warning signs should be placed in clearly visible locations.
The gate opener should ONLY be used if the user can see the entire gate area
and is assured that it is free of obstacles and the gate operator is set
correctly. No one may pass through the gate area while it is moving. Children
must not be allowed to play in the vicinity of the gate.
The full protection against potential crushing or entrapment must work
immediately when the drive arms are installed.
There may be existing hazards on mechanical, electrical installation or the
closing edges of the gate by crushing, impact points:
- Structural failure, leaf, hinges, fixings, travel stops, wind load
- Crush, hinge area, under the gate, safety distance on fixed object
- Electrical failure (Control – faults in safety systems)
- Impact, swept area, hold to run, force limitation, presence detection
Appropriate measures must be taken to ensure safe operation of the gate system according the standards.
Never start up a damaged drive.
Use the manual release only to disengage the drive and – if possible – ONLY
when is gate closed. Operation of the emergency manual release can lead to
uncontrolled
movements of the gate. The Timer-to-Close (TTC) feature, the myQ Smartphone
Control app, are examples of unattended operation of the gate.
Any device or feature that allows the gate to close without being in the line
of sight of the gate is considered as unattended open/close.
The Timer-to-Close (TTC) feature, the myQ Smartphone Control, and any other
myQ devices can ONLY be activated when Liftmasters photo cells are installed
(TTC
works only in close direction). The gate shall only be operated in the direct
sight line to the gate.
IMPORTANT INFORMATION!
-
This procedure is also required on private installations (new or retrofitted to a manually operated gate).
This installation and operating manual must be retained by the user. -
The manufacturer accepts no liability/warranty claims resulting from use other than intended use and after the warranty expires.
-
The legal remedy is the sole responsibility for all associated rights.
NOTE: Observe the installation and operating manual.
-
Always monitor the function of the system and rectify the cause immediately in the event of a malfunction.
-
Carry out an annual inspection of the system. Call a specialist.
-
Safety distances must be respected between the gate leaf and the environment in accordance with related standards.
-
The operator can be installed Only on stable and rigid gate leaves. Gate leaves must not bend or twist when opening and closing.
-
Assure that the hinges of the gate leaf are installed and working correctly and not creating any obstacles.
-
Installation of two operators on same door leaf is strictly prohibited.
-
Observe the corresponding requirements of the local, national regulations for compliance with the measures to protect human health, which must be observed when
contacting other people, including employees, suppliers and customers (e.g. safety distance, mask requirement, etc). -
Precise information can be requested from the local authorities.
DELIVERY SCOPE
LA250EVK (2 x motor units)
LA300EVK (2 x motor units)
TOOLS NEEDED
OVERVIEW OF GATE OPERATOR
- Motor 1
- Motor 2
- Control board
- Post bracket
- Gate bracket
- Infrared photocells
- Flashing lamp
**MECHANICAL INSTALLATION
**
Herewith you start the mechanical installation of the gate operator.
5.1 Dimensions of Gate and Operator
LA250EVK
5.2 Post Bracket Position and A &B Dimensions
Determine the A and B dimensions based on the opening angle provided in Table
1 to confirm the position where the post bracket will be mounted.
- To ensure that the motor does not touch the pillar, please define your C dimension using the B-60 mm formula.
- For optimal mechanical advantage, A and B dimensions shall be equal or not differ by more than 40 mm.
NOTE: Smaller A and B dimensions determine the higher peripheral speed of
the leaf. Higher differences between A and B dimensions cause greater speed
and force variations during the gate opening and closing movement. It is
always good practice to use all available travel of the operator.
All crushing points must be secured by entrapment protection according to EU:
EN 12453, EN 60335-2-103; GB (UK, NI): BS EN 12453, BS EN 60335-2-103.
LA250EVK with external hard stop, using max 300 mm travel
Table 1:
__
mm
|
A
---|---
100| 120| 140| 160| 180
__
__
__
B
| 100| n.a.| 110°| 105°| 105°| 100°
120| 110°| 110°| 100°| 95°| 95°
140| 100°| 100°| 100°| 90°| 80°
160| 95°| 95°| 90°| 85°| 75°
180| 90°| 90°| 80°| 75°| 70°
Example installation
LA300EVK with internal hardstop, using max travel 300 mm Table 1:|
LA300EVK without internal hardstop, using max travel 350 mm
---|---
__
mm
|
A
| __
mm
|
A
---|---|---|---
100| 120| 140| 160| 180| 100| 120|
140| 160| 180
__
__
__
B
| 100| n.a.| 110°| 105°| 105°| 100°| __
__
__
B
| 100| n.a.| 120°| 120°| 120°| 120°
120| 110°| 110°| 100°| 95°| 95°| 120| 115°| 115°| 115°| 110°| 100°
140| 100°| 100°| 100°| 90°| 80°| 140| 105°| 110°| 110°| 105°| 100°
160| 95°| 95°| 90°| 85°| 75°| 160| 100°| 100°| 100°| 95°| 90°
180| 90°| 90°| 80°| 75°| 70°| 180| 95°| 95°| 95°| 90°| 85°
Example installation
MECHANICAL INSTALLATION
5.3 Post Bracket Installation
LA250EVK
- Using the post bracket as a reference, mark and drill the holes for the post bracket.
- Attach the post bracket using the correct fastening material based on existing installation (building/material substance). Please consult the gate manufacturer.
- The slots on the post bracket allow for alignment. When the post bracket is level tighten the nuts.
LA300EVK
- Using the post bracket as a reference, mark and drill the holes for the post bracket.
- Attach the post bracket using the correct fastening material based on existing installation (building/material substance). Please consult the gate manufacturer.
- The slots on the post bracket allow for alignment. When the post bracket is level tighten the nuts.
NOTE: For brick or concrete posts please use correct dowels and screws.
Please maintain correct distance to the post edges. For metal posts please
consider the post thickness and weld or bolt the bracket directly to post. For
timber posts please use correct screws and if required use reinforcement
plates.
Caution: The fastened brackets must not loosen after installation and
during operation.
5.4 Operator Mounting and Travel Distance Adjustment
- Align the holes on the operator to the post bracket holes and connect using the circlip pin and circlip.
- Release the operator clutch with the release key (see page 8).
- Bring gate leaf to the CLOSED position.
NOTE: The system must operate with:
LA250EVK only with external gate hard stops in both directions.
LA300EVK with external gate or internal operator hard stops in both
directions.
4.1 Installation with external gate hard stops: (gate hard stops already
installed):
a. For LA250EVK: pull out the tube completely and make 1 complete turn of the
tube in clockwise direction see (picture 4.1.a).
For LA300EVK (with internal operator hard stops removed): pull the operator
trolley to the max. closed position leaving 25 mm free space from absolute end
position.
(see picture 4.1.a).
b. Connect the operator arm with the gate leaf bracket (see picture 4.1.b or
4.1.c).
c. Preliminary fix the gate bracket on the gate leaf. Ensure that the gate
touches the external hard stop. Consider the dimensions A and B from Table 1.
d. Manually open and close the gate to the required positions. Ensure the
operator arm does not bind and gate is moving smoothly.
For LA300EVK please ensure that in the OPEN position the trolley is having
min. 25 mm free space.
e. Make permanent connection of the gate bracket at chosen correct position.
4.2 Installation with internal operator hard stops, LA300EVK only: (no gate
hard stops installed):
a. Release the CLOSE position hard stop and bring it to the required position
within available range. Fix it.
b. Manually move the trolley to the hard stop.
c. Connect the gate leaf bracket to the trolley of the operator (see picture
4.1.c).
d. Make a preliminary connection of the gate bracket to the gate leaf. Ensure
the gate leaf does not change its position.
e. Manually move the gate leaf to the OPEN position and if no obstruction
release the OPEN position hard stop and move it until it hits the trolley and
fix it.
If there is an obstruction during manual movement, please check the A, B and C
dimensions from the Table 1 and make required corrections.
f. Once the required positions are defined make permanent connection of the
gate bracket at chosen correct position.
4.3 A combination of operator and gate hard stops is allowed for LA300EVK.
Please use the respective set up procedures as described above.
5. Repeat the procedure for the unit on the opposite side.
5. MECHANICAL INSTALLATION
5.6 Emergency Release Mechanism
To disengage the release mechanism turn the protective cap to the side, enter
the key and turn it 90°. Pull the clutch up. To re-engage the release
mechanism, push the clutch down and turn the key 90°.
NOTE: Same procedure applies for left and right-hand units.
5.7 Control Box Installation
The control box must be installed at a safe location that enables the
installer to have access at all times to the logic board without the risk of
the gates crushing or trapping.
It is advised that you must have full view of the gates when programming the
logic board.
Install the control box in an appropriate and accessible position. The
installation has to be done in accordance with local electrical regulation.
Motor 1 Connection
NOTE: The operator wired to the MOTOR 1 terminal will always open first
and close last. Consider this for Basic and Advanced Settings (see Programming
section).
- Feed the motor1 cable through a cable gland.
- Connect motor cables to the MOTOR 1 terminals as follows:
red cable to RED terminal, green cable to GRN terminal , white cable to WHT terminal on control board.
Motor 2 Connection
NOTE: The operator wired to the MOTOR 2 terminal will always open last and close first. Consider this for Basic and Advanced Settings (see Programming section).
- Feed the motor 2 cable through a cable gland.
- Connect motor cables to the MOTOR 2 terminals as follows: red cable to RED terminal, green cable to GRN terminal , white cable to WHT terminal on control board.
5.8 Power Wiring
Power wiring must be done by a certified electrician specialist
Congratulations! Herewith the mechanical installation of your gate operator
is finished. Please proceed with Programming andBasic Settings to be able to
start operation.
WIRING DIAGRAM
PROGRAMMING
7.1 Display, Programming Buttons and Function Setting
Programming buttons function (4 buttons):
Button | Function |
---|---|
S | program / delete remote controls and specific functions |
P | enter programming mode, select function and save |
+/- | Navigate through the menu and change the value on display |
Function and programmed values are shown on LED display.
Function setting – programming mode
LED display shows following values after control board is powered:
| Control board is pre-programmed to relevant application (see below under
“Application” and “Stand-by Mode” for status description).
---|---
| “E0”, in case the control board has not been programmed yet or reset by
function “Factory Default”. From this status, an Input or transmitter command
will be always ignored.
7.2 General Programming Overview
Herewith you start programming of your gate operator.
The programming is divided in 2 sections:
- Basic Settings (Page 11)
- Advanced Settings (Page 14)
After Basic Settings are done, following parameters will be learned automatically during Learning phase:
- Travel length from FULL CLOSED to FULL OPEN position.
- Opening and closing force for each motor.
NOTE:
- Basic Settings and Learning phase must be completed to enable operation.
- After the Learning phase and Programming are finished the operator will work as per default settings.
- Advanced Settings cannot be accessed if Basic Settings and Learning phase are not completed.
- Before making the programming ensure that the relevant safety devices are connected.
Programming Procedure Overview
- Press and hold “P” button for 5 seconds to enter the menu. “AP” on the display indicates the first available function in menu.
- Use “+“ and “–” buttons to navigate between the functions.
- Press “P” button to select the required function.
- The default setting or previously programmed value will appear. This will be indicated by flashing of value on display.
- Use “+” or “–“ buttons to select the required value. Press “P” button to confirm selection.
- The programmed function is shown on display.
- To change the setting of another function, repeat the sequence from the points #2 to #6
- To exit to the Function menu, press “P” button for 5 seconds, then the board will go in Stand-by mode.
If “P” button is not pressed to confirm new value setting, new settings will
be saved after 3 minutes and programming will exit menu and return into Stand-
by mode.
NOTE: To operate the gate or execute any command, setting menu must be
finished by pressing the “P” button for 5 seconds, or by selecting FE
Function, or waiting 3 minutes for automatic exit and return into Stand-by
mode.
PROGRAMMING
7.3 Wing Movement Direction
Before programming, move the gate manually in the middle position and re-
engage release mechanism (see page 8).
Press and hold the “–“ button on the control board and ensure that the motors
are moving in CLOSE direction. If correct, immediately let go of the “-“
button and gate stops.
If motors are moving in OPEN direction, go to the functions “d1“ and “d2” and
change the direction settings.
Once CLOSE direction is set correctly, leave the gate in the middle position.
The operator is ready for the Learning phase.
Note: gate can be moved with „ + “ and „ – „ buttons prior to final settings
if required.
Press and hold the “+“ button on the control board to move the gate into OPEN
position. When button is released operator stops.
Press and hold the “–“ button on the control board to move the gate into CLOSE
position. When button is released operator stops.
7.4 Basic Settings
Basic Settings Overview
LED | Function | |
---|---|---|
Basic Settings (mandatory) | ||
AP | Application | |
d1 | Direction Motor 1 | |
d2 | Direction Motor 2 | |
LL | Limit Learning Phase |
7.4.1 Application Settings
Application function shown on display.
This function is already pre-set at factory at value 07.
| Swing gate, two motors for LA250/LA300 application (defauft)
---|---
More settings available on-demand:
| No application selected
---|---
| Swing gate, one motor for LA250/LA300 application
Values 01-05 are not suitable for LA250/LA300 application and shall not be
chosen.
7.4.2 Direction Motor 1 Settings
Direction Motor 1 function shown on display
Defines movement direction of the Motor 1.
| Motor 1 is moving in closing direction
---|---
| Motor 1 is moving in opening direction
7.4.3 Direction Motor 2 Settings
Direction Motor 2 function shown on display. Defines movement direction
of the Motor 2. Not available for “one motor” application.
| Motor 2 is moving in closing direction
---|---
| Motor 2 is moving in opening direction
7.4.4 Limit Learning
Before starting a Learning phase ensure that:
- Other Basic Settings are completed
- Internal/external hard stops are installed (for swing gates)
- First movement will be in CLOSE direction.
Available Learning methods:
Standard Learning Mode (Automatic)
- Press and hold “+ and –“ buttons for 2 seconds.
- The automatic learning process starts. LL will flash on the display during the complete process.
- Wing 2 moves in the CLOSE direction until the hard stop is reached and stops.
- Wing 1 moves in a CLOSE direction until the hard stop is reached and stops for 2 seconds. Then Wing 1 starts in the OPEN direction until the hard stop is reached.
- Wing 2 moves in the OPEN direction until hard stop is reached, stops for 2 seconds and then moves in the CLOSE direction until the hard stop is reached, and stops.
- Wing 1 moves in a CLOSE direction until hard stop is reached and stops.
- The Standard Learning phase is finished. LL will appear on display and the board will return in standby mode after 3 seconds.
NOTE: In single motor application, “Wing 2” actions are not used.
Following settings are done during Standard Learning Mode:
- Travel length from FULL CLOSED to FULL OPEN position.
- Opening and closing force for each motor.
- 15% of total travel in both directions is assigned for Soft Stop.
- Wing delay in opening and closing position is 2 seconds. Shall you need to change the delay please go to Advanced Settings: Delay Motor 2 (d0) and Delay Motor 1 (dC).
PROGRAMMING
Advanced Learning Mode (manual setting of Soft Stop position)
-
Press and hold “+ and –“ buttons for 2 seconds.
-
Automatic learning starts. LL will flash on the display during complete process.
-
Wing 2 moves in CLOSE direction until hard stop is reached, and stops.
-
Wing 1 moves in CLOSE direction until a hard stop is reached, and stops for 2 seconds.
-
Wing 1 starts in OPEN direction at default speed. To define start of the Soft Stop for Wing 1 in OPEN direction press “P” button at required start point. Wing
1 will continue opening until hard stop is reached, and stops. -
Wing 2 moves in OPEN direction at default speed.
-
To define start of the Soft Stop for Wing 2 in OPEN direction press “P” button at required start point. Wing 2 will continue opening until hard stop is reached, stops for 2 seconds and then moves in CLOSE direction at default speed.
-
To define start of the Soft Stop for Wing 2 in CLOSE direction press “P” button at required start point. Wing 2 will continue closing until hard stop is reached, and stops.
-
Wing 1 moves in CLOSE direction at default speed.
-
To define start of the Soft Stop for Wing 1 in the CLOSE direction press “P” button at required start point. Wing 1 will continue closing until hard stop is reached, and stops.
-
Advanced Learning phase is finished. LL will appear on display and board will return in stand-by mode after 3 seconds.
NOTE: In single motor application, “Wing 2” actions are not used.
Following settings are programmed during Advanced Learning mode:
- Travel length from FULL CLOSED to FULL OPEN position.
- Opening and closing force for each motor.
- Starting positions of the Soft Stops.
- Wing delay in opening and closing position is 2 seconds. Shall you need to change the delay please go to Advanced Settings: Delay Motor 2 (d0) and Delay Motor 1 (dC).
NOTE: To stop the Learning phase press “S” button. The Learning process
will be interrupted, “LE” will flash on LED display. After 5 seconds “LL” will
appear on display indicating readiness to start the Learning phase again.
If Learning process was not completed, it needs to be re-done.
ATTENTION: The learning phase must be completed to enable operation.
7.5 Stand-by Mode
After the control board is powered on and programming is finished, the LED
display lights completely for 2 seconds and goes into the stand-by mode.
During Stand-by mode the LED display shows current gate status.
| Two motors (default)| One motor
---|---|---
Motor is opening, upper section of the display flashes.| |
Motor stops at the opening position, upper section of the display is on.| |
Motor is closing, lower section of the display flashes.| |
Motor stops at the closed position, lower section of the display is on.| |
Motor stops in the middle, middle of the display is on.| |
Herewith the Basic Settings are completed. You can leave Programming and operate your gate or proceed with Advanced Settings.
7. PROGRAMMING
7.6 Programming and Erasing of Remote Controls, Radio Accessories and myQ
Devices
Program remote control devices (transmitters and wireless wall controls):
NOTE: the remote controls delivered with the operator are already factory
pre- learned to the operator (top button near the LED) and do not require
extra programming.
-
Press and release “S” button. An LED spot turns ON in the display. The operator will stay in Radio programming mode for 3 minutes.
Any radio accessory device can be learned within first 30 seconds. During the remaining 2.5 minutes only myQ devices can be learned. -
Chose the required button on your transmitter and hold it until the dot in the display turns off.
To program a new remote control repeat the sequence. To program a wireless keypad, please follow the respective manual of the accessory.
Programming Transmitter in Partial opening
Press and hold “S“ and “+“ buttons at the same time, until the LED spot starts
flashing. Press and hold the desired free button on transmitter to program the
Partial Opening
Mode. The LED spot turnsoff when the programming is finished. If there is a
light connected to SPEC contact it will flashonce.
Program myQ gateway (828EV):
1. Connect
Connect ethernet cable (1) provided with gateway to router (2).Use the plug
valid for your country ( not all models). Connect power (3) to the internet
gateway (4). When the internet gateway connects to the internet, the green
light (5) will stop blinking and will light solid. A connected set of IRs is
mandatory for myQ operation.
2. Create an account
Download the free myQ App from App Store or Google Play Store and create an
account. If you already have an account, use your username and password.
3. Register the internet gateway
Enter the Serial Number located on the bottom of the internet gateway when
prompted.
4. Add myQ devices
To add your gate operator to the registered gateway follow the instructions on
the app. When adding a new myQ capable gate operator press and release “S”
button on operator control board. An LED spot turns ON in the control board
display.
Note: After you add a device, the blue light on the internet gateway will
appear and stay on. Press “S” button on the operator control board to exit the
radio programming mode.
5. Test
After having installed and registered correctly you may now test the following
features: open or close the gate, request status GATE OPEN or GATE CLOSED.For
more functions see www.liftmaster.eu Erase radio
control devices (transmitters, wireless wall controls, wireless keypads):
Press and hold “S” button for > 6 seconds. All radio control devices
(transmitters, wall controls, keypads) are erased. The LED spot in the display
turns OFF. Note: It is not possible to erase radio control devices
individually.
Erase myQ devices:
- Erase remote control devices first as indicated above.
- Within next 6 seconds press and hold “S” button. An LED spot turns ON in the display.
- Press and hold “S” button for > 6 seconds. All myQ devices are erased. The LED spot in the display turns OFF.
NOTE: It is not possible to erase myQ devices individually. It is not possible to erase myQ devices only.
7. PROGRAMMING
7.7 Advanced Settings
Herewith you start with Advanced Settings.
7.7.1 Overview Advanced Settings
LED | Function |
---|---|
tr |
__
| r1| | IR1 photocell
| r2| | IR2 photocell
| r3| | IR3 photocell
| i1| | Input 1 command
__
| i2| | Input 2 command
| i3| | Input 3 command
__
| Pd| | Partial Opening Motor 1 only
__
| d0| | Delay Motor 2 in OPEN
__
| dC| | Delay Motor 1 in CLOSE
| tC| | Timer To Close (TTC)
| rt| | Reversal time after impact
| EL| | E-lock
| | rb| Relief Motor 1 for E-lock
LED| Function
---|---
| FL| | Flashing Light
|
__
| PF| Pre-Flashing
__
| SP| | Special contact
__
| St| | START Speed in OPEN and CLOSE
| Cn| | Maintenance counter
__| PS| | Password
|
__
| F1| Force Motor 1 in Open (protected by PS)
| | F2| Force Motor 1 in Close (protected by PS)
| | F3| Force Motor 2 in Open (protected by PS)
| | F4| Force Motor 2 in Close (protected by PS)
|
__
| S1| Speed Motors in OPEN (protected by PS)
|
__
| S2| Speed Motors in CLOSE (protected by PS)
|
__
| SF| SOFT-STOP Speed in OPEN and CLOSE (protected by PS)
| Fd| | Factory default
| FE| | Finish and Exit
7.7.2 Transmitter Settings
The transmitter function defines how Transmitter commands are working.
Note: Under settings “01”, “02” and “03”, TTC timer will be overridden by
a transmitter command and will CLOSE the gate.
Under setting “04”, active TTC timer countdown will be re-set to start again
by the Transmitter command.
| Residential Mode: Open – Close – Open
---|---
| Standard Mode: Open – Stop – Close – Stop – Open (Default)
| Automatic with Stop Mode: Open – Stop – Close – Open
| Car Park Mode: Open, to complete Open position. Additional com- mand during
the opening will be ignored
7.7.3 Infrared Photocells Settings
IR functions define functioning mode of Infrared Photocells (IR).
IRs will be auto-learned when installed. Each of the 3 IR sets can be
programmed individually.
NOTE: Depending on the chosen settings the Partial Opening inputs or Remote
Controls commands will not be executed in both OPEN or CLOSE direction if the
IR beam is obstructed.
If IRs are removed, the control board power must be turned OFF/ON for two
times to unlearn.
For check and maintenance of the photocells see the manual of the photocells.
| IR active on CLOSE movement. If IR beam is obstructed, gate re- verses in
complete OPEN position (Default).
---|---
| IR active on OPEN movement. If IR beam is obstructed gate stops. When
obstruction disappears the gate continues to OPEN.
| IR is active on OPEN and CLOSE movement. If IR beam is obst- ructed on CLOSE
movement, gate stops and after the obstruction disappears gate reverses in
complete OPEN position. If IR beam is obstructed on OPEN movement, gate stops.
When obstruction disappears the gate continues to OPEN.
| IR active on CLOSE movement. If IR beam is obstructed, gate re- verses in
complete OPEN position. The activated TTC function will be overridden 2
seconds after the beam obstruction is eliminated and will start CLOSE movement
not waiting till the end of TTC time end.
7.7.4 Input Settings
Inputs function defines the way Input commands from external accessories are
executed. Each of the 3 Inputs can be programmed individually.
NOTE: Under settings “01”, “02” and “03”, TTC timer will be overridden by
an Input command and will CLOSE the gate. Under setting “06”, active TTC timer
countdown will be re-set to start again by an Input command
7. PROGRAMMING
| Open – Close – Open
---|---
| Open – Stop – Close – Stop – Open (Default)
| Open – Stop – Close – Open
| Partial opening Motor 1 only
| STOP (NC contact)
| Open, to complete OPEN position. Additional Open command during the opening
will be ignored
| Close, to complete CLOSE position. Additional Close command during the
closing will be ignored
| Open – Stop – Open – Stop
| Close – Stop – Close – Stop
| Open, hold to run
| Close, hold to run
7.7.5 Partial Opening Motor 1
Partial opening Motor 1 only gives you the ability to open active leaf to a
pre-set value only.
NOTE: Pd command will work starting from Close limit position and during
closing movement. If a Pd command is executed from a complete OPEN position,
the gate will close.
An Open or transmitter command will always override the Pd command.
| 50% opening travel
---|---
| 75% opening travel (default)
| 100% opening travel
- Press and hold „S“ and „+“ buttons on the control board at the same time, until the LED spot starts flashing.
- Press and hold the desired free button on the transmitter to program the Partial Opening Mode.
- The LED spot turns off when the programming is finished. If there is a light connected to SPEC contact it will flash once.
7.7.6 Delay Motor 2 in Open Direction
Delay Motor 2 in OPEN direction function defines time delay for Motor 2 in the
OPEN
direction. Not available for single motor application.
Not executed during reversal or after IR beam interruption in both directions.
| no delay (both wings start opening at the same time)
---|---
| 1 second
| 2 seconds (Default)
| 3 seconds
| 4 seconds
7.7.7 Delay Motor 1 in Close Direction
Delay Motor 1 in CLOSE direction function defines time delay for Motor 1 in
CLOSE direction. Not available for the single motor application.
Not executed during reversal or after IR beam interruption in both directions.
| no delay (both wings start in the same time)
---|---
| 1 second
| 2 seconds (Default)
…
| … seconds
| 20 seconds
7.7.8 Timer To Close
Timer to close (TTC) function enables automatic closing of the gate from a
complete OPEN position after a pre-set period of time. Minimum one pair of
LiftMaster Infrared Photocells (IR) has to be installed to monitor closing
movement to enable TTC operation.
TTC will not work if IR are protecting opening movement only.
TTC will also work with activated partial opening. If TTC function is active,
timer is counting down, and the IR beams are interrupted, the
TTC timer shall re-start.
7.7.9 Reversal Time after Impact
Reversal time after impact function defines reversal behavior after obstacle
obstruction during closing or opening movement.
This reversal behavior is valid both for motor force detection and safety edge
application.
| 2 seconds reversal and Stop
---|---
| Reversal back up to the end limit position (Default)
| During Closing movement, upon impact gate reverses up to Open position.
During Opening movement, upon impact gate reverses for 2 seconds and stops
7.7.10 E-Lock / Mag-Lock Settings
E-Lock function defines e-lock/mag-lock behavior.
24VDC – 500mA e-lock or mag-lock can be connected.
| e-lock/mag-lock not installed (Default)
---|---
| e-lock active for 1 second prior to Motor 1 start in Open direction
| e-lock active for 2 seconds prior to Motor 1 start in Open direction
| Magnetic lock, constantly active at gate CLOSED, constantly inactive during
OPEN and CLOSE movement, gate OPEN or STOP position. Magnetic lock will be
deactivated in Battery Back-up mode.
7. PROGRAMMING
7.7.10a Relief Motor 1 for E-Lock
Relief Motor 1 for E-Lock function enables to briefly push Motor 1 in CLOSE
direction before engaging e-lock to relieve excess pressure on e-lock. Not
available if
EL Function is set to “00” or “03” (e-lock not connected / mag-lock
connected).
| deactivated (Default)
---|---
| 1 second activated
| 2 seconds activated
7.7.11 Flashing Light Settings
Flashing Light function allows to select which type of Flashing Lamp is
connected.
24VDC- max 500 mA Flashing lamp (FLA1-LED) can be connected.
| no flashing lamp installed (Default)
---|---
| continuous 24V supply – for flashing lamp with own control board (FLA1-LED)
| interrupted 24V supply – for flashing lamp without own control board
7.7.11a Pre-Flashing
Pre-Flashing function defines time interval of pre-flashing of the flashing
lamp prior to gate movement. Function not active if Flashing Lamp (FL)
Function is set to “00”.
| no pre-flashing (Default)| | 3 seconds
---|---|---|---
| 1 second| | 4 seconds
| 2 seconds| | 5 seconds
7.7.15 Password Protected Functions and Setup
7.7.15a Password Setup
Learning Phase must be completed and Password must be set before doing changes
for Password protected functions, like Force and Speed.
Chose the “PS” function to program password.
NOTE: “00” cannot be used as password. It is only used as a default setting.
Functions protected by password can’t be accessed if the new password is not
set.
Password will be required to change protected Functions after the setup.
Password Setup Procedure
- Choose “PS” function and press “P” button.
- “00” flashes on display.
- Use “+” and “–” buttons to set the new password.
- Press “P“ button.
- New set password value remains on display for 2 seconds. Then display changes to “PS“.
Please note your password where it can be found later.
7.7.12 Special Contact Settings
Special Contact function defines relay activation time.
A 24V max 500mA relay can be connected to manage other devices, e.g. courtesy
light. The time set here will also control the countdown for myQ remote light.
7.7.13 Start Speed in Open and Close Directions
Start Speed function allows switching the Soft-Start in OPEN and CLOSE
directions ON and OFF.
| deactivated (Default)
---|---
| Soft Start active: motors will accelerate gradually until they reach
standard speed.
| Hard Start active, motors will start at the regular Speed and for the
first second the force sensor will not be considered.
7.7.14 Maintenance Counter
The maintenance Counter function allows to set maintenance intervals in
cycles.
4 seconds pre-flashing of the Flashing Lamp will be a signal the interval is
reached.
If PF Function (Pre-Flashing) is active then 4 seconds of pre-flashing will be
added to the set time. To reset counter after maintenance is done, it will be
enough to program the cycles one more time.
ATTENTION
Any changes done to the Password protected functions (Force and Speed) require
verification of speed and force according to EU: EN 12453, EN 603352-103; GB
(UK, NI) BS EN 12453, BS EN 60335-2-103.
| No password selected (Default)
---|---
| Selection available
7. PROGRAMMING
7.7.15b Password Use
- Choose “PS” function and press “P” button.
- “00” flashes on display.
- Use “+” and “–” buttons to enter the correct password and press “P” button to confirm.
- If correct password is entered, the display shows the value for 2 seconds and changes to “PS”.
- Choose the protected function to set.
NOTE: If the entered password is not correct, “00” will flash for 5
seconds, then change to “PS”. Use correct password to access protected
functions.
Attention: The password-protected Advanced Settings can only be executed by a
trained professional. The requirements of the EU: EN 12453, EN 13241; GB (UK,
NI) BS EN 12453, BS EN 13241 must be fulfilled.
7.7.15c Password Change
- Choose the “PS” function and press “P” button.
- “00” flashes in the display.
- Use “+” or “–” buttons to enter current password and press “S” button. Value starts flashing.
- Use the “+” or “–” buttons to enter a NEW password and press “P” button.
- Changed password value remains on display for 2 seconds. Then display changes to “PS“.
NOTE: If wrong (current) password was entered, “00” will flash for 5
seconds and change to “PS”. The password is not changed.
If password is lost, use Factory Default function (Fd) to go back to default
settings. All settings (apart from Radio Memory) will be deleted. See page 18.
7.7.15d Force Motors 1 and 2 in Open and Close Directions
Force Motor 1 in OPEN Direction
Force Motor 1 in OPEN direction allows force adjustment on top of force set
during the Learning phase. Password must be entered to access this function.
| Standard force(Default)| | +30%
---|---|---|---
| +15%| | +50%
Force Motor 2 in OPEN Direction
Force Motor 2 in OPEN direction allows force adjustment on top of force set
during the Learning phase. Password must be entered to access this function.
| Standard force(Default)| | +30%
---|---|---|---
| +15%| | +50%
Force Motor 2 in CLOSE Direction
Force Motor 2 in CLOSE direction allows force adjustment on top of force set
during the Learning phase.Password must be entered to access this function.
| Standard force(Default)| | +30%
---|---|---|---
| +15%| | +50%
7.7.15e Speed Motors 1 and 2 in Open and Close Directions
Speed Motors 1 and 2 in OPEN Direction
Speed Motor 1 and 2 in OPEN direction allows opening speed adjustment compared
to the speed set during Learning phase. Password must be entered to access
this function.
| Standard speed (Default)
---|---
| +10%
| +20%
| +30%
| +50%
| -10%
| -20%
---|---
7. PROGRAMMING
Speed Motors 1 & 2 in CLOSE Direction
Speed Motor 1 and 2 in CLOSE direction allows closing speed adjustment
compared to the speed set during Learning phase. Password must be entered to
access this function.
| Standard speed (Default)
---|---
| +10%
| +20%
| +30%
| +50%
| -10%
| -20%
---|---
7.7.15f Soft-Stop Speed
Soft-Stop Speed function allows adjustment of the Soft-Stop speed compared to
default values set during Learning phase. Soft-Stop speed is 50% of the
standard speed as per default setting. Standard speed change impacts the Soft-
Stop speed. Password must be entered to access this function.
| Standard speed (Default)
---|---
| +10%
| +20%
| +30%
| +50%
| -10%
| -20%
---|---
7.8 Factory Default
Factory default function resets control board to the original factory set-ups.
All settings, including limit settings, will be erased. LED display will show
“E0”.
Programmed remote controls will remain learned. If Remote control accessories
need to be erased refer to the respective Radio Controls Programming section
of this manual.
| no reset (Default)
---|---
| reset to the factory default settings
7.9 Finish and Exit
To exit the programming phase and save all changes,
move to FE function and press “P” button. The control board will go into
Stand-by mode and is ready to work.
There are also other ways to exit the programming and save settings:
- Press and hold “P” button for 5 seconds
- Wait 3 minutes after the last changes in the programming for automatic exit
BATTERY BACKUP
Battery Back-Up Mode
2 Optional 12V, 2.2Ah lead batteries SKU 490EV (optional, not included) can be
mounted inside the E-Box. Follow the manual of SKU 490EV for exact
installation procedure. A Flashing lamp (if mounted) will flash 2 seconds
every 10 minutes indicating BBU mode and power loss. Control board will switch
into stand-by mode with active radio receiver accepting radio control device
commands only. All other accessories and peripheral devices will not be
functioning.
When in Battery Back-up mode, myQ Smartphone Control and wireless myQ devices
will be disabled. Full charged battery capacity shall support up to ~20 cycles
at a rate of 2 per hour. After 24 hours of BBU mode the battery shall provide
power for 1 complete opening and closing cycle. Please note that only the
specified battery canbe use. Use of any other battery leads to loss of
warranty and loss of liability of LiftMaster for any related damages resulting
from use of unspecified batteries.
ERROR CODES
LED | Error code | Issue | Possible reason | Solution |
---|---|---|---|---|
E0 | Press transmitter, but no gate movement | AP is set to 00 | Check if AP |
is set to 00. If yes, change to correct application setting.
|
E1
|
Gate do not close, but can open.
| 1) IR1 is not connected, or wire is cut.| 1) Check if IR1 is not connected,
or wire is cut.
2) IR1 wire is shorted out or reverse connected.| 2) Check IR1 connection,
change wires if needed.
- IR1 is not aligned or blocked for a moment.
| 3) Align IR transmitter and receiver to make sure both LED is on, instead of blinking. Make sure there is nothing hanging on gate that may cause IR blocking.
|
E2
|
Gate can close when it is at open limit, but cannot open when it‘s at close limit.
| 1) IR2 is not connected, or wire is cut.| 1) Check if IR2 is not connected,
or wire is cut.
2) IR2 wire is shorted out or reverse connected.| 2) Check IR2 connection,
change wires if needed.
3) IR2 is not aligned or blocked for a moment.| 3) Align IR transmitter and
receiver to make sure both LED is on, instead of blinking. Make sure there is
nothing blocking the IR.
|
E3
|
Press transmitter, but no gate movement.
| 1) IR3 is not connected, or wire is cut.| 1) Check if IR3 is not connected,
or wire is cut.
2) IR3 wire is shorted out or reverse connected.| 2) Check IR3 connection,
change wires if needed.
- IR3 is not aligned or blocked for a moment.
| 3) Align IR transmitter and receiver to make sure both LED is on, instead of blinking. Make sure there is nothing hanging on gate that may cause IR blocking in short time.
**E4**
|
E4
|
Press transmitter, but no gate movement.
| 1) Safety edge is not connected with 8.2kohm resistor.| 1) Check if the 8.2 kOhm safety edge is properly connected or if the
8.2 kOhm resistor is installed.
- Safety edge wire is shorted out.| 2) Check safety edge wires and replace wire if needed.
- Safety edge is pressed.| 3) Check if safety edge is pressed.
|
E5
|
Press transmitter, but no gate movement.
| 1) STOP swtich is open.| 1) Check if STOP switch is open or damaged.
2) STOP switch is not connected.| 2) Check if STOP switch is disconnected. If
yes, then reconnect STOP switch or change the respective Input setting to
other value.
**E7**
| E7| Press transmitter, but no gate movement.| Control board amplifier for Motor 1 fail.| Switch off power for 20 seconds and reset to check if control board recovers. If not, change control board.
**E8**
| E8| Press transmitter, but no gate movement.| Control board amplifier for Motor 2 fail.| Switch off power for 20 seconds and reset to check if control board recovers. If not, change Control board.
**E9**
| E9| Press transmitter, but no gate movement.| Control board memory
mistake.| Switch off power for 20 seconds and reset to check if control board
recovers. If not, change control board.
| F1| Motor 1 stop and reverse during open or close.| Motor 1 is blocked.|
Check and remove obstruction. Clean gate.
| F2| Motor 2 stop and reverse during open or close.| Motor 2 is blocked.|
Check and remove obstruction. Clean gate.
| F3| Motor 1 stop and reverse during open or close.| Motor 1 stall or speed
sensor is damaged.| Check if motor 1 stalled or speed sensor is damaged.
| F4| Motor 2 stop and reverse during open or close.| Motor 2 stall or speed
sensor is damaged.| Check if motor 2 stalled or speed sensor is damaged.
**F5**
| F5| Press transmitter, but motor has no action.| Radio module fail.| Switch off power for 20 seconds and reset to check if control board recovers. If not, change control board.
**F6**
| F6| Gate reverse during closing.| Low battery power.| Charge battery.
**F7**
| F7| Press transmitter, but no gate movement.| Control board damaged.| Switch off power for 20 seconds and reset to check if control board recovers. If not, change control board.
**F9**
|
F9
| Press transmitter or push button, but motor has no action.| AP menu is reset
to factory default.| Relearn limits.
| LE| Motor stops suddenly.| Press C button during limit learning.| Relearn
limits.
TECHNICAL DATA
| | LA250EVK| LA300EVK
---|---|---|---
Input Voltage| VAC| 220-240
Input frequency| Hz| 50/60
Motor Voltage| VDC| 24V
“Standby consumption (without accessories)”| W| 3.7| 4.2
Motor Rated Power (LA250EVK = 2 x LA250-24) (LA300EVK = 2 x LA300-24)|
W
|
100
|
100
Rated Force| N| 800| 830
Maximum Motor Pushing/Pulling Force| N| 1250| 1500
Cycles per hour| | 8| 10
Max. cyles per day| | 25| 30
Max. wing weight
|
m / kg
| 1.5m / 250kg 2m / 200kg 2.5m / 150Kg| 2m / 300kg 2.5m / 250kg 3m / 200Kg
Max. opening angle| | 110°| 120°
Time to open to 90°| s| 15-18| 15-18
Piston /Screw travel length| mm| 300| 350 (w/o internal hardstops) 300 (with
internal hardstops)
Cable length| m| 1.5
End Limit System| | Encoder with hard stops
Operating Radio Frequency
Sending power
|
MHz
| RX 433MHz (433.30MHz, 433.92MHz, 434.54MHz) RX 868MHz (868.30MHz, 868.95MHz, 869.85MHz) TX 865.125MHz, 865.829MHz, 866.587MHz
<10mW
Code| | Security+ 2.0
Max. nr of remotes| | 180
Max. nr. of keypads| | 4
Max. nr. of myQ devices| | 16
External accessory power| | 24VDC – max. 500mA
Flahing lamp connector| | 24VDC – max. 500mA
E-Lock /Magnetic lock conenctor| | 24VDC – max. 500mA
External relay| | 24VDC – max. 500mA
Safety edge| | 8,2 kOhm
Max. nr. of IRs| | 3
Max. nr. of external inputs| | 3
Battery back-up unit| | 2 x 12V, 2.2Ah SKU 490EV
Ingress protection Motor| IP| 44| 44
Ingress protection control board| IP| 65| 65
Noise Level| dB| < 70 db(A)| < 70 db(A)
Working temperature| °C| -20°C to +55°C| -20°C to +55°C
Weight (kit)| Kg| 19,6| 20,5
Transmitter Frequency|
TX4EVF
| 868MHz (868.30MHz, 868.95MHz, 869.85MHz)
Sending power| <10mW
Battery| CR2032 3V
MAINTENANCE
Replace Batteries in The Remote Control
The battery of the remote control:
The batteries in the remote have an extremely long life. If the transmission
range decreases, the batteries must be replaced. Batteries are not covered by
the guarantee.
Please observe the following instructions for the battery:
Batteries should not be treated as household waste. All consumers are required
by law to dispose of batteries properly at the designated collection points.
Never recharge
batteries that are not meant to be recharged.
The danger of explosion!
Keep batteries away from children, do not short-circuit them or take them
apart. See a doctor immediately, if a battery is swallowed. If necessary,
clean contacts on battery
and devices before loading. Remove flat batteries from the device immediately!
Increased risk of leakage!
Never expose batteries to excessive heat such as sunshine, fire or similar!
There is increased risk of leakage!
Avoid contact with skin, eyes and mouth. Rinse the parts affected by battery
acid with plenty of cold water and consult a doctor immediately. Use only
batteries of the same type. Remove the batteries if the device is not being
used for a long time.
Replacing battery:
To replace battery, turn remote control around and open the case with a
screwdriver. Lift cover and lift control board below. Slide battery to one
side and remove. Watch polarity of battery! Assemble again from in reverse
direction.
ATTENTION!
Danger of explosion if battery is replaced improperly. Replacement only by
identical or equivalent type (CR2032) 3V.
CAUTION
Risk of explosion if the battery is replaced by an incorrect type.
Do not ingest battery, Chemical Burn Hazard.
This product contains a coin battery. If swallowed, button batteries can cause
injuries or death.
WARNING
- Keep batteries out of sight and out of the reach of children, button/coin batteries can be dangerous for children.
- Dispose of used button batteries immediately. Do not use defect/swallowed batteries.
- Check periodically if the battery compartments is secure, stop using if defect.
- If batteries might have been swallowed or placed inside any part of the body, seek immediate medical attention.
The drive mechanism
The drive mechanism is maintenance-free. Check the gate fittings and the drive
mechanism at regular intervals (monthly) are securely fixed. Release the drive
and check
that the gate functions properly. Unless the gate runs smoothly it will not
operate correctly with the drive mechanism. The drive cannot eliminate the
problems caused by a
gate that does not work correctly.
Limit switch adjustment and force regulation
These settings must be checked and undertaken properly during the installation
of the opener! Due to weathering, minor changes can occur during the operation
of the opener
that need to be addressed by a new setting. This can particularly happen in
the first year of operation. Follow the instructions for setting travel limits
and force (refer to section Limit Learning Phase, pages 11 and 12) carefully,
and re-check the automatic safety reverse after each resetting!
Disassembly
IMPORTANT Notice! Follow the safety notices. See “Safety instructions”
(pages 2 and 3). The sequence is described in the “installation” section, but
in the opposite order.
Ignore the setup instructions.
DISPOSAL
Our electrical and electronic equipment may not be disposed of with household
waste and must be disposed of after use properly in accordance with WEEE
Directive EU: 2012/19/EU; GB UK(NI): SI 2012 nr. 19 on waste electrical and
electronic equipment in order to ensure that materials are recycled.
Collecting waste electrical equipment separately means environmentally-
friendly disposal and is completely free of charge for the consumer. WEEE reg.
no. in Germany: DE66256568. Any waste packaging left over with the end
consumer must be collected separately from mixed waste, in accordance with the
Directive. Packaging may not be disposed of with household waste, organic
waste or in nature. Packaging material must be separated according to its
material and disposed of in the recycling containers provided and in certain
council recycling bins.
Our batteries are marketed in compliance with the law. The ‘crossed-out waste
bin’ indicates that batteries may not be disposed of with household waste.
Batteries included in the product (technical data). In order to avoid causing
harm to the environment or people’s health, used batteries must be returned
for regulated dis- posal at council recycling centres or via retail outlets,
as is prescribed by law. Batteries may only be brought for disposal once fully
discharged and, in the case of lithium batteries, with their terminals taped
over. The batteries can be easily removed from our equipment for disposal.
Registration number in Germany: 21002670.
WARRANTY
Your statutory rights are not affected by this manufacturer‘s warranty. Please see www.liftmaster.eu for terms of the warranty.
DECLARATION OF CONFORMITY
The manual consists of these operating instructions and the declaration of
conformity.
The radio equipment type (TX4EVF) is in compliance with Directive 2014/53/EU
and for UK with Radio Equipment Regulation SI 2017 No. 1209.
The full text of the EU declaration of conformity is available at the
following internet address: https://doc.chamberlain.de
Chamberlain GmbH
Saar-Lor-Lux-Str. 19
66115 Saarbrücken
Germany
WEEE-Reg.Nr. DE66256568
www.liftmaster.eu
info@liftmaster.eu
Documents / Resources
|
LiftMaster LA250EVK Double Swing Gate Opener
Kit
[pdf] Installation Guide
LA250EVK, LA300EVK, Double Swing Gate Opener Kit
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>