EUROTRONIC Air Quality Sensor Z-Wave Plus Installation Guide

June 5, 2024
EUROTRONIC

Air Quality Sensor Z-Wave Plus
Installation & Operation Guide

Included in delivery

1 x Air Quality Sensor Z-Wave Plus
1 x Micro USB power supply
1 x Quick Start Manual
NOTE! The following figures are for illustration purposes only and may differ from the actual product.

EUROTRONIC Air Quality Sensor Z Wave Plus - 3 NOTE! Please check the scope of delivery for completeness and intactness.

Safety Instructions

Avoid potential dangers by reading the following safety instructions carefully.

SAFETY INSTRUCTIONS
– Air Quality Sensor Z-Wave Plus is designed for use in buildings.
– Operate Air Quality Sensor Z-Wave Plus only as described in the user manual.
– Air Quality Sensor Z-Wave Plus should only be put to use in a dry and dust- free place, away from direct sunlight.
– Do not keep using the device when there is obvious damage.
– Air Quality Sensor Z-Wave Plus may not be rebuilt, modified, or opened.
– The CO2 measured value of the Z-Wave Plus air quality sensor is hydrogen- based. The Air Quality Sensor Z-Wave Plus must therefore not be used for CO2 detection in safety-relevant applications.

WARNING!
Risk of fatal injury and accidents to infants and children! The packaging material represents a risk of stuff location. Never leave children unattended when the packaging material is nearby.
Children often underestimate the risks involved. Always keep children away from the packaging material.
The device is not a toy.

Intended use

The product provides comprehensive information on indoor air quality.
For reasons of safety and approval (CE), you must not modify and/or alter the product. If you use the product for purposes other than those described, the product may be damaged. In addition, improper use may result in hazards such as short circuits, fire, electric shock, etc.
Read the operating instructions carefully and keep them in a safe place. Only pass the product on to third parties together with the operating instructions.

Product description

The brand new Z-Wave sensor in ultra-slim design housing provides comprehensive information on indoor
air quality. Based on this information it is possible to always ensure a healthy living climate.

  • Ultra-flat design housing

  • Use of high-precision, Swiss sensor technology

  • Multicolor LED for signaling ventilation recommendations

  • Returns the following values:
    – VOC value (volatile organic compounds) in ppm
    – CO2 value (as CO2-equivalent) in ppm
    – Temperature (°C) and humidity (%)
    – Dew point (°C)

  • Supports Z-Wave Plus S2 security (encryption)

  • Z-Wave repeater function

  • Operation with a plug-in power supply unit

Operating the device

Button

EUROTRONIC Air Quality Sensor Z Wave Plus - 5

Button Interaction Result/Behavior
Network press three times
within 1 second Air Quality Sensor Z-Wave Plus will react to inclusion or

exclusion commands.
Network| hold for 10 seconds| Factory resets the Air Quality Sensor Z-Wave Plus.

LEDs

EUROTRONIC Air Quality Sensor Z Wave Plus - 6

Color State Meaning
red permanently illuminated Air quality is bad.

(LED signaling can be disabled via Configuration Command Class)
orange| permanently illuminated| Air quality is average.
(LED signaling can be disabled via Configuration Command Class)
green| permanently illuminated| The air quality is good.
(LED signaling can be disabled via Configuration Command Class)
red| lights constantly for 5 seconds| A task has failed.
green| blinking| The device is ready to be included or excluded.
green| lights constantly for 5 seconds| A task was completed successfully.
2x red
3x green| blinking pattern| LGS Z-Wave Plus is reset to factory default settings.

Network behavior

On factory default, the device does not belong to any Z-Wave network Air Quality Sensor Z-Wave Plus needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.
Air Quality Sensor Z-Wave Plus can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Please consult the manual of your Z-Wave Controller on how to activate Inclusion or
Exclusion mode.
If Air Quality Sensor Z-Wave Plus has been added to a network, it has to be removed prior to being added to another wireless network.

Interoperability
This product can be operated in any Z-Wave network with other Z-Wave certified devices from other manufacturers. All non-battery-operated nodes within the network will act as repeaters regardless of vendor to increase the reliability of the network.
Security
Air Quality Sensor Z-Wave Plus supports secure communication. Air Quality Sensor Z-Wave Plus will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise Air Quality Sensor Z-Wave Plus will automatically turn into a lower level of security.

A Security Enabled Z-Wave Controller must be used to fully utilize the Air Quality Sensor Z-Wave Plus.

Power supply

Connect the Micro-USB cable to a plug-in power supply (Output: 5.0V DC 1.0A, 5W) and to the air quality sensor, and afterward to a power outlet.

EUROTRONIC Air Quality Sensor Z Wave Plus - 8

IMPORTANT:
When using the air quality sensor, make sure that the sensor is not disconnected from the power supply, because during the first 12 hours of operation the sensor learns your corresponding room profile and also resulting air quality variations via a self-calibrating algorithm.
After these 12 hours, the sensor guarantees you precise measurement results.
If the power supply is interrupted, this calibration process starts again.
Please also make sure that the room, in which the air quality sensor is operated, is ventilated vigorously at least once a week. This is important for the learning algorithm of the sensor.
Note: If the measured values remain high for a long time, manual recalibration may be helpful. To do this, briefly interrupt the power supply. After 12 hours, the sensor guarantees precise measurement results again.

Add Air Quality Sensor Z-Wave Plus to a Z-Wave network

Start inclusion mode of your primary Z-Wave Controller.
Press the network button three times within 1 second.
While the inclusion is active, the LED is blinking green. If the inclusion was successful the green LED will light up for 5 seconds. Otherwise, the red led will light up for 5 seconds to indicate failure.

Remove Air Quality Sensor Z-Wave Plus from a Z-Wave network

Start the Exclusion mode of your primary Z-Wave Controller.
Press the network button three times within 1 second.
While the inclusion is active, the LED is blinking green. If the inclusion was successful the green LED will light up for 5 seconds. Otherwise, the red led will light up for 5 seconds to indicate failure.

Factory reset

Press and hold the network button for at least 10 seconds. The Air Quality Sensor Z-Wave Plus will indicate the reset blinking pattern once the reset is completed.
Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Z-Wave

Parameter number Size in Byte Name Description
1 1 The temperature on Change Reporting 0x00 No on change reporting (only

time-based reports).
Ox01 – 0x32 report if temperature changed by delta = 0,1°C – 5,0°C default: 0x05
2| 1| Humidity in Change Reporting| 0x00 No on change reporting (only time- based reports). Ox01 – Ox0A report if humidity changed by delta = 1% …10% default: 0x05
3| 1| Unit Temperature| 0x00 Temperature reports in Celsius Ox01 Temperature reports in Fahrenheit default Ox00
4| 1| Resolution Temperature| 0x00 No resolution (example 22°C) Ox01 1/10 resolution (example 22.3°C)
0x021/100 resolution (example 22.35°C) default: Ox01
5| 1| Resolution Humidity| Ox00 No resolution (example 33%) Ox01 1/10 resolution (example 33.4%)
0x021/100 resolution (example 33.45%) default Ox00
6| 1| VOC-on Change Reporting| Ox00 No on change reporting (only time-based reports)
Ox01 – OxOA report if VOC reading changed by 100ppb – 1000ppb default: 0x05
7| 1| CO2-eq on Change Reporting| Ox00 No on change reporting (only time-based reports)
Ox01 – OxOA report if CO2-eq reading changed by 100ppm – 1000ppm default 0x05
8| 1| Air quality indication via LED| Ox00 No air quality indication via LEDs
Ox01 Indicate measured air quality via LEDs default: Ox01

  • Availability of the Command Class after adding the Air Quality Sensor Z-Wave Plus to your Z-Wave network
U Unsecure
S0 Z-Wave Security standard  S0
S2 Z-Wave Security standard  S2

Association

Air Quality Sensor Z-Wave Plus can be associated with other devices.

Group No.| Description| Commands| Max supported
Nodes
---|---|---|---
1| Lifeline| DEVICE_RESET_LOCALLY_NOTIFICATION, NOTIFICATION_REPORT,
SENSOR_MULTILEVEL_REPORT,| 1
2| Temperature| SENSOR_MULTILEVEL_REPORT| 5

Configuration

Air Quality Sensor Z-Wave Plus can be configured during runtime.

Parameter number Size Byte Name Description
1 1 The temperature on Change Reporting Ox00 No on change reporting (only

time-based reports).
Ox01 – 0x32 report if temperature changed by delta = 0,1°C – 5,0°C default: 0x05
2| 1| Humidity in Change Reporting| Ox00 No on change reporting (only time- based reports). Ox01 – OxOA report if humidity changed by delta = 1% …10% default 0x05
3| 1| Unit Temperature| Ox00 Temperature reports in Celsius Ox01 Temperature reports in Fahrenheit default: Ox00
4| 1| Resolution Temperature| Ox00 No resolution (example 22°C) Ox01 1/10 resolution (example 22.3°C)
0x021/100 resolution (example 22.35°C) default: Ox01
5| 1| Resolution Humidity| Ox00 No resolution (example 33%) Ox01 1/10 resolution (example 33.4%)
0x021/100 resolution (example 33.45%) default Ox00
6| 1| VOC-on Change Reporting| Ox00 No on change reporting (only time-based reports)
Ox01 – OxOA report if VOC reading changed by 100ppb – 1000ppb default: 0x05
7| 1| CO2-eq on Change Reporting| Ox00 No on change reporting (only time-based reports)
Ox01 – OxOA report if CO2-eq reading changed by 100ppm – 1000ppm default 0x05
8| 1| Air quality indication via LED| Ox00 No air quality indication via LEDs
Ox01 Indicate measured air quality via LEDs default: Ox01

Multilevel Sensor

Air Quality Sensor Z-Wave Plus measures the room temperature and automatically reports sensor readings to associated devices. Per default, the reporting threshold is ± 0.5°C. This parameter can be altered via the configuration command class.
Sensor type: „Air Temperature“
Scale: Celsius and Fahrenheit
Precision: 0,1 and 2

Air Quality Sensor Z-Wave Plus measures the humidity and automatically reports sensor readings to associated devices. Per default, the reporting threshold is ±5%. This parameter can be altered via the configuration command class.
Sensor type: „Humidity“
Scale: Prozent and absolut
Precision: 0,1 and 2
Air Quality Sensor Z-Wave Plus measures the dewpoint and automatically reports sensor readings every 30 minutes to associated devices.
Sensor type: „Dewpoint“
Scale: Celsius and Fahrenheit
Precision: 1
Air Quality Sensor Z-Wave Plus measures the CO2 -eq concentration and automatically reports sensor read- ings to associated devices. Per default the reporting threshold is ±500ppm. This parameter can be altered via the configuration command class.
Sensor type: „Carbon dioxide CO2-level“
Scale: Parts/million (ppm)
Precision: 0
Air Quality Sensor Z-Wave Plus measures the VOC concentration and automatically reports sensor readings to associated devices. Per default the reporting threshold is ±500ppb. This parameter can be altered via the configuration command class.
Sensor type: „Volatile Organic Compound level“
Scale: Parts/million (ppm)
Precision: 3

Notification

Air Quality Sensor Z-Wave Plus will send notifications to the Z-Wave Controller.

Notification type Reason Description
Home Health The air pollution level has changed Pollution level

0x01: Clean
0x02: Slightly polluted
0x03: Moderately polluted
0x04: Highly polluted

Troubleshooting

Problem Reason Solution
red LED lights constantly for 5 seconds A task has failed. •  Z-Wave

Controller out of range.
•  Repeat the task as needed.

Cleaning

NOTE: RISK OF DAMAGE! Improper handling of the Air Quality Sensor Z-Wave Plus can lead to damage.
– Do not immerse the Air Quality Sensor Z-Wave Plus in water or other liquids.
– Do not use aggressive cleaning agents, brushes with metal or nylon bristles, or sharp or metallic cleaning objects such as knives, hard spatulas, and the like. These can damage the surfaces.
– Clean the Air Quality Sensor Z-Wave Plus with a soft, dry cloth.

Technical specifications

Device description Air Quality Sensor Z-Wave Plus
IAN 4.26001E+12
Article Number 700088
Supply Voltage Power supply, Output:

5.0V DC 1.0A, 5W
Current|
Measuring range (CO)2| 0 – 3.000 ppm
Measuring range (VOC)| 0 – 2.200 ppb
Measuring range (temperature)| -40 to +125 °C
Measuring range (rel. humidity)| 0 – 100 %
Radio Frequency| 868,42 MHz
Output Power| +4dBm
Method of operation| Type 1
Dimensions (W x H x D)| 68 x 68 x 17 mm
Weight| 47,7g
Degree of protection| IP20
Degree of pollution| 2
Signalization| Multicolor-LED
Color| white

Technical modifications are subject to change. All descriptions for compatibility are without engagement.

Disposal

Advice on environmental protection:
From the date of implementation of European guidelines 2002/96/EC and 2006/66/EC, into national law, the following applies: Electric and electronic devices and batteries may not be disposed of in the household waste. The consumer is obliged to return electric and electronic devices and batteries to the public collection points established for them or to the point of sale. The particulars of this are regulated by the applicable state laws. The symbol on the product, operation instructions or packaging points to these provisions. You make an important contribution to the protection of the environment by reusing or recycling old equipment/batteries or making use of them in other ways.

Declaration of conformity:
Hereby, Eurotronic Technology GmbH declares that the Air Quality Sensor Z-Wave Plus is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the
following internet address: https://eurotronic.org/service/downloads/.

Warranty

The 24-months warranty period begins on the day of purchase. Please keep the receipt as evidence of purchase. During the warranty period, defective radiator thermostats may be sent to your dealer or the address below. Please ensure sufficient postage is paid. A new or repaired device will then be sent to you free of charge. No new warranty period begins with the repair or replacement of the device.
After the warranty period has expired, you also have the option of sending the defective device to the specified address with sufficient postage for repair. Repairs after the warranty period have expired are subject to a charge. Your statutory rights are not limited by this warranty.

Contact information

If you wish to receive further technical support or information about other Eurotronic products, please contact us via E-Mail or telephone.

Eurotronic Technology GmbH
Südweg 1
36396 Steinau-Ulmbach
Germany| Telephone: +49 (0) 6667 91847-0
eMail: [email protected]
Web: www.eurotronic.org
---|---

https://eurotronic.org/produkte/sensoren/luftguetesensor/

Made in Germany
www.eurotronic.org

Stand-12/2021

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EUROTRONIC User Manuals

Related Manuals