bradfordwhite BNTH Brute Touchscreen Display Water Heater User Manual

June 5, 2024
bradfordwhite


**User’s Manual for

with Touchscreen Display**

FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler and heater installation and maintenance. proper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.

WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS

  • Do not try to light any appliance.
  • Do not touch any electrical switch; do not use any phone in your building.
  • Immediately call your gas supplier from a nearby phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency, or gas supplier.

Brute BOILERS AND VOLUME WATER HEATERS

FAMILIARIZING YOURSELF TO THE

The Bradford White Brute is offered in both Indoor and Outdoor models for all sizes, as both Boiler and Volume Water Heater. The appearance of the Indoor and Outdoor rates is drastically different as the Outdoor model has a weathertight door that covers the entire front of the unit. This weathertight door must be unlatched, lifted off, and set aside for all adjustments and servicing.

The only component and interior difference between the Indoor and Outdoor models is that all of the piping for the Outdoor model, with the exception of the Exhaust Vent, is at the BACK of the unit. See Figure 1
The gas connection, the air inlet, and the water inlet and outlet are all at the back of the outdoor unit. This is consistant for all sizes.

Sizes available are 150-850 MBTU/h. This illustration is of the 150 MBTU/h For complete details to all sizes and dimensions, please refer to the Brute Install and Operating Manual, Doc #1344

FOR YOUR SAFETY – PLEASE READ THIS BEFORE OPERATING

WARNING
If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury or loss of life.
A. This unit does not have a pilot. It is equipped with an ignition device that automatically lights the burner. Do not try to light the burner by hand.
B. Before operating the unit, check for any smell of gas in the area around it. Be sure to smell next to the floor, because some gas is heavier than air and will settle near the floor.
C. Use only your hand to turn the handle on the gas valve. Never use tools. If the valve handle will not turn by hand, don’t try to repair it. Call a qualified service technician. If you force the valve or try to repair it, this may result in a fire or explosion.
D. Do not use this unit if any part has been under water. Immediately call a qualified service technician to inspect the unit. Any part of the control system or any gas control which has been under water must be replaced.

WHAT TO DO IF YOU SMELL GAS

  • Do not try to light any appliance or device that uses gas.
  • Do not touch any electrical switch. Do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

LIGHTING THE UNIT

  1. STOP! Read the safety information listed above.
  2. Set the thermostat to the lowest setting.
  3. Turn off all electric power to the unit.
  4. This unit is equipped with an ignition device that automatically lights the burner. Do not try to light the burner by hand.
  5. Remove the front access panel.
  6. Turn off the manual gas valve. The valve is off when the valve handle is at a right angle to the gas pipe.
  7. Wait five minutes to allow any gas to clear. Smell for gas, including the area near the floor. If you do smell gas, STOP! Follow Step B in the safety information listed above. If you don’t smell gas, go to the next step.
  8. Slowly turn the manual gas valve to “ON.” The handle on the valve will be parallel to the gas pipe.
  9. Replace the front panel.
  10. Turn on the electric power to the unit.
  11. Set the thermostat to the desired setting.
  12.  If the unit will not operate, follow the instructions in “Turning Off the Gas to the Unit” and call your service technician or gas supplier.

TURNING OFF THE GAS TO THE UNIT

  1. Before doing any service work, turn off all electric power to the unit.
  2. Set the thermostat to the lowest setting.
  3. Remove the front access panel.
  4. Turn off the manual gas valve. The valve is off when the valve handle is at a right angle to the gas pipe.
  5. Replace the front panel.

SHUTTING DOWN THE BRUTE

It may sometimes be necessary to shut down the Brute. Here are the steps required to do this:

  1. Switch off the main electrical disconnect switch.
  2. Open the front cover and close the main manual gas valve.
  3. If freezing is anticipated, drain the Brute. (Also be sure to protect the piping in the building from freezing.)

The steps listed above may require qualified service personnel.

RESTARTING THE BRUTE
It may be necessary to restart the Brute – for example, after a power interruption. Here are the steps required to do this:

  1. Reset any errors using the Touchscreen Display. See the section on “About Lockouts, Holds, and Alerts.”
  2. Turn up the thermostat to call for heat.
  3. In approximately 2 seconds, the blower will operate. Ignition should occur after 35-40 seconds. It may take as long as 2-1/2 minutes.
  4. If ignition does not occur, wait 5 minutes and then repeat steps 1 through 3.
  5. If, after three attempts, the unit still does not light, shut down the boiler and call your service technician.

If the unit has been drained, follow these steps:

  1. See the “Installation and Operation Manual” for instructions on filling and purging the unit.
  2. Remove the front door. Turn on the gas shutoff valve.
  3. Switch on the main electrical disconnect switch. The pump and blower will start, and the igniter will be energized. After 35 seconds the gas valve will be energized, and ignition will occur. If ignition does not occur within 2-1/2 minutes switch “off” the main disconnect switch, wait 5 minutes and switch it “on” again. If after three attempts
    ignition does not occur, shut down the unit and call for service.

IN THE EVENT OF POWER FAILURE

The Brute will not operate during an electrical power outage. If there is an extended power outage with the danger of freezing, then the Brute (and all other water systems) should be completely drained. Before draining the unit, turn off the gas and turn off the main power switch. When you replace the unit in service, refer to the “Installation and  Operation Manual” for instructions on filling and purging.

Using the Touch Screen

Figure 39. Brute with Touch Screen
The Touch Screen
The Touch Screen is located front and center on the Brute and allows you to navigate into all of the functionality and control that is available to setup and customize your heating and/or hot water system.
Using the Touch Screen
A screen saver is programmed into the display. Simply touch the screen to wake it up. While under normal operation, the Touch Screen will automatically present this Home Screen. See Menu 1

The home screen shows a picture of the Brute controller. The color of the controller depends on the status of the Brute, as shown below.

Color Status Control Icon
Blue Normal operation
Red Lockout
Gray Standby mode (Burner switch off )
Gray and crossed out Communication problem
Yellow Hold state. This could be Anti short cycles, fan speed transitions,
etc.

Figure 40. Boiler Status Colors
To check the operation of the appliance, press the large Control Icon on the Home screen. The system will present a Status Summary screen for the appliance:

Screen Menu Icons

Home Upper left-hand corner Return to the Home page
Camera Upper left-hand corner Screen-shot of the current menu as a JPG file
Bell Upper left-hand corner System in Lockout, Reset required
Padlock Upper right-hand corner Locked or Unlocked. See Menu 3
Back Upper right-hand corner Return to previous

Sometimes a screen is used to present a list, and often the list is too long to present on a single screen view. To see the rest of the list, pull down the bar on the right side of the screen, or use the up-and-down arrows. To make a change, or to get more information about one of the items on the list, press the line for that item.

Login (required for some parameters)
To change some parameters, a Login (password) is required. The control system includes three levels of password protection:

OEM| Factory Password Setup and parameter changes are Available only to the factory.
---|---
Login| Installer Password Setup and parameter changes made when the system is installed, and some diagnostic and troubleshooting functions. The installer level password is “lnt” (lower case “LNT.”) See Menu 3
User| (no password required)
Non-critical adjustments and functions, including adjusting the Central Heat and Domestic Hot Water setpoints, monitoring the input and output variables, reading parameters from the controller, and reading the error log (For some special safety-related functions, besides entering the correct password, the system will ask you to go through an additional “verification” process. For more information, see the section on “Configuration.”)

When a password is necessary, the system will present the keyboard screen. See Menu 3.

Menu 3. Keyboard Screen

The passwords used by this system are “case sensitive” – it matters whether a letter in the password is capitalized or not. Pressing the Shift key toggles between capital and lower case letters. “BS” stands for “Back Space,” and also works as a Delete key. Anyone can view all of the parameters. However, to change most of the parameters, you will need a
password.
At the bottom of the screen, the system indicates that you need to enter a password.

Menu 4. Login Required

The screen used to log in is similar to the Keyboard screen.
It may be difficult for some operators to press the keys on this screen. In this case, use the back of a plastic pen, or a stylus, or a pencil eraser. (Do not use sharp metal tools – these may damage the plastic surface of the screen.)
Each time you press a key, the system will respond with a beep. If you are entering a password, an asterisk (*) will appear for each character you enter. The beeps and asterisks will help you enter the correct number of characters for your password. When changing a numerical value, the system presents a numerical entry screen, as shown below.

Menu 5. Numeric Entry Screen

Verification Process for SafetyRelated Parameters

The verification process allows the user to confirm that all the changes made are correct and that there have not been any inadvertent changes made.

  1. When you start to change a parameter that is related to safety, the system will present a warning which looks like this:
    Menu 6. Parameter Safety Warning
    WARNING
    Changing safety parameters should only be conducted by experienced, licensed boiler operators and mechanics. Hazardous burner conditions can happen with improper operations that may result in PROPERTY LOSS, PHYSICAL INJURY, or DEATH.
    Press OK to continue. The system will ask you to log in before you make a change. (For more information on logging in, see Section 8.2.)

  2. If you make a change in any group that could affect the safe operation of the unit, the control system will ask you to “verify” the change before it is accepted.

  3. Once all parameters have been changed, return to the configure menu. In the lower right-hand corner of the screen, you will see ‘VERIFY’ Press VERIFY, then press BEGIN to start verification.
    Notes
    • Once you change one of these safety-related parameters, you must finish the verification process for the group that includes the parameter, or the control system will not let the boiler operate. You can wait to do the verification until you have changed parameters in other groups, but before you return the boiler to service, you must complete the verification process for all groups that have been changed.
    • At the end of the verification process, you must press the Reset button on the front of the controller. See Figure 41. You have to do this within 30 seconds, or the verification will be canceled. To make it easy to reach the Reset button, open the door on the front of the boiler and slide out the control panel before beginning the verifi cation.
    Figure 41. Reset Button on Controller

  4. The system will present a listing for each group of parameters that need verification See Menu 7.
    Menu 7. Safety Parameter Confi rmation

  5. For each group, check the list carefully. Press Yes if all of the parameters in the group have been entered correctly. For each group, you are given 30 seconds to select Yes/No. A count-down timer is shown at the bottom of the screen.
    If you made changes in other safety-related groups, verify the entries in those groups in the same way. Do this until the following screen shows
    Menu 8. Safety Parameter Reset

  6. When the process is complete, the system will tell you to reset the control system. The Reset button is located on the front of the controller. You must press the Reset button within 30 seconds or the verification will be canceled. A count-down timer is shown at the bottom of the screen.

Checking Individual Parameters

  1. From the ‘Home’ screen (Menu 9), press the icon for the controller.
    Menu 9. ‘Home’ screen

  2. The Status Summary page for the controller will appear. This shows the current operating condition of the controller, and also shows some of the configuration settings.
    See Menu 10

Menu 10. Status Summary Screen
Notice the four buttons at the bottom of each Status Summary screen:

  • Configure – This allows an installer to change some of the setup parameters used by the system. A password may be required.
  • Operation – Used to adjust the setpoints, change the fan speed, turn a burner on or off, or turn the pumps on or off.
  • Diagnostics – allows you to run diagnostic tests, or check the inputs and outputs used by the system.
  • Details – This allows you to check the status of all of the setup parameters on the control system.

Setting the Date and Time on the System Display
The display includes an internal clock, which keeps track of the date and time. This setting is important because log entries for Lockouts and Alerts include time listings. If the Date and Time setting for the boiler is not correct, the listings in the Lockout and Alert logs will be incorrect.

To set the clock:

  1. Start at the ‘Home’ screen.
    Menu 11. ‘Home’ screen

  2. Press the Setup button on the lower right corner of the screen. The system will present the Setup screen.
    Menu 12. Setup Screen

  3. Press the Display Setup button at the bottom of the screen.
    Menu 13. Display Setup Screen

  4. Press the‘ Set Date/Time’ button.
    Menu 14. Date and Time

  5. Use the arrows to change the date and time, and then press the OK button.

Battery
The display has a removable battery (CR2032) to store time, date, lockout, and alerts in the event of a power failure. It has an expected lifetime of 10 years. The battery can be accessed from the back of the Touchscreen display.

The Configuration Menu

Is the gateway to the parameters that the factory, the installer, or the end- user will need in order to set up, service, maintain or adjust the unit. There are eighteen (18) items in the Configuration The menu can be viewed. Please Review Menu 17. There are 18 total Configuration Sub Menus. Please see the Installation and Operating Manual for the complete list. Each of these items will have Sub-Menus in which you can make parameter adjustments and configurations.

  1. From the Home Page screen (Menu 15), press the icon for the controller.
    Menu 15. Home Page Screen

  2. The Status Summary page for that controller will appear. See Menu 16
    Menu 16. Status Summary Screen

  3. Press the Configure button to start a configuration session for the controller.

The Configuration Sub-Menus ( ALL 18 )
There are 18 total Configuration Sub Menus. Please see the Installation and Operating Manual for the complete list. When using the Brute for hydronic heating, a call for heat must be supplied to the “T-T” terminals found on TB7 labeled “T-T or Interlock”. Once a call for heat is established, the control will start the appropriate (selected) pumps, and begin the ignition process.

System Identifi cation & Access

This sub-menu will display information regarding software, date codes, model numbers, and program name, as well as give the installer access to re-name the boiler and to change the Modbus addresses for lead-lag operation. Press the back arrow on the top right corner of the screen to return to the ‘Configuration Menu’.

CH – Central Heat Configuration

Menu 18. The Configuration Menu
Make sure that CH is Enabled and then press one of the black arrows (either side) to get to the Set-Point screen. Press on the ‘Setpoint’ box to make adjustments to setpoint, and modulation for a single boiler CH demand.

Setting Up 4-20 mA Setpoint

The Central Heat Configuration Menu (Menu 18) has three sub-menus and each of them can be reached by scrolling left or right thru the arrows on the left and right. See Menu 19. The three sub-menus are ‘Central Heat’, ‘Setpoint’, and ‘Modulation’. To set up a 4-20 mA Setpoint, you will need to go into the ‘Setpoint’ sub-menu fi first and change the Setpoint source from Local to S2 (J8-6) 4-20 mA. Then go to the ‘Modulation’ sub-menu and set the Modulation Source to Local. Both Setpoint and Modulation cannot have their source set as Local.

Menu 19. The Setpoint submenu
until you are on the ‘Setpoint’ sub-menu, then click on ‘Local’.

Click on the down arrow to see further options.

Choose S2 (J8-6) 4-20 mA, then press OK

Menu 20. CH Setpoint source
Then scroll over to the Modulation sub-menu and click on Modulation rate source.
Outdoor Reset Configuration

At this sub-menu, confirm that Central Heat is Enabled. Next, press onto the Maximum Outdoor Temperature, Minimum Outdoor Temperature, and Low Water Temperature to get to each and adjust their setpoints in those sub-menus.

DHW – Domestic Hot Water Confi guration

DHW – Domestic Hot Water is used to configure the DHW temperature parameters for water heaters (NTV) and for indirect water heaters that are used with boiler (NTH) systems. Press on the Setpoint box to get to the adjustment submenu. Then adjust it up or down to your desired DHW setpoint.

  Warm Weather Shutdown Configuration

From this sub-menu, you will be able to enable/disable the Warm Weather Shutdown feature and adjust the set point.

Demand Priority Configuration

From the Demand Priority Configuration, the installer can adjust the priority of the different demand types.
Central Heat, Lead-Lag, Domestic Hot Water
The control uses arrows as indicators to point to the loop with higher priority.

Modulation Configuration

From this sub-menu, the installer has the ability to adjust the range of modulation for the CH, and DHW demands. Brute is designed with a 5:1 turn-down ratio. Any change to the minimum and maximum modulation rates will affect the overall ratio of the boiler. The installer-level password will allow changes to these parameters. Consult the factory if an adjustment is needed to any of these parameters.

Pump Connections
The controller in the Brute energizes the pump contacts when it receives a call for heat. Once the call for heat is satisfied, the pump will remain on for the defined pump overrun time.

The Boiler Pump terminals (TB5 – max 7.4 FLA) are fed by 120V (violet wire) internally from the main power feed. The System and DHW contacts are dry contacts. Appropriate voltage must be supplied to the System and DHW pumps for proper operation.

The System pump connections are located on terminal block 5 (TB5) in the control panel. The System pump contacts are rated for 120Vac, 7.4 Amps. To use the contacts, power must be supplied on one terminal with the other terminal wired to the pump or a relay controlling the pump.

The DHW pump connections are located on terminal block 5 (TB5) in the control panel and are rated for 120Vac, 7.4 Amps. To use the contacts, power must be supplied on one terminal, and the other terminal wired to the pump or a relay controlling the pump. Additional 120VAC circuits may be required for the pumps.


200 Lafayette St.
Middleville, MI 49333
Warranty: 800-531-2111
www.BradfordWhite.com
Litho in U.S.A. © Bradford White 1802 Document 1345A-BW
H2374800A

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

bradfordwhite User Manuals

Related Manuals