SIGNALFIRE Sentinel-485 Series Sentinel Modbus User Manual

June 5, 2024
SIGNALFIRE

Signal-Fire

SIGNALFIRE Sentinel-485 Series Sentinel Modbus

SIGNALFIRE Sentinel-485 Series Sentinel Modbus

The SignalFire Sentinel Node is an Intrinsically Safe device with the following features:

  • RS485 connection to a single Modbus RTU sensor device
  • Configurable Modbus register polling map
  • Can power an attached Modbus sensor at 8V or 13V with configurable warm-up time
  • Low power operation from an intrinsically safe high capacity lithium primary battery pack
  • Optional solar battery system for routing nodes, high power draw sensors, or rapid data collection
  • Sends data to a SignalFire Buffered Modbus Gateway
  • AES 128bit Encryption

Specifications

  • Enclosure Size: 3.5” tall × 5.0” wide × 5.0” deep

  • Power Source:
    Internal IS Lithium battery pack
    SignalFire Part Number: 3BIS
    External Solar battery system
    SignalFire Part Number: Sentinel-HCSolar
    DC-DC Converter
    SignalFire Part Number: DCDC-Sentinel
    Other external power supply meeting the power entity parameters from the control drawing.

  • Temperature Rating: -40°C to +60°C

  • Radio Frequency: 902-928MHz Ism Band, FHSS radio, internal antenna

  • Compliance: Certified for use in Class I, Division 1 groups C and D. EXi [EXi] FCC/IC Certified.

WARNING: Use of this equipment in a manner not specified by the manufacturer may impair the protection provided by the equipment.
WARNING: The use of any parts not supplied by the manufacturer violates the safety rating of the equipment.
The associated apparatus provides intrinsically safe outputs. Refer to control drawing “Sentinel – Control Drawing – Modbus, Thermocouple, RTD, and Float Stick” for requirements when used in a Class I Division 1 area.SIGNALFIRE
Sentinel-yTherm-XXXX Sentinel Node Thermocouple-1

Connections and Components

SIGNALFIRE Sentinel-yTherm-XXXX Sentinel Node
Thermocouple-2

Radio LEDs

  • The Radio TX LED (green) flashes each time a radio packet is sent. This LED will blink rapidly while searching for the radio network.
  • The Radio RX LED (red) blinks on each received radio packet.

Status LEDs

  • The Active LED (green) will blink at boot up and will blink rapidly when the sensor is being powered and read.
  • The ERROR LED (red) will blink to indicate an error condition.

Scan/Checkin Button

  • If this button is pressed the Sentinel will take a reading from the RTD and send those values to the gateway.

Setup

The nodes need to be set up for correct operation before being fielded. The configurable items include:

  • Network selection
  • Check-in period selection
  • RTD mode enable

All settings are made using the SignalFire Toolkit PC application and a serial programming cable.
WARNING: Perform the steps in this section (Setup) in a safe location only.

Using the SignalFire Toolkit
The SignalFire Toolkit application can be downloaded at www.signal- fire.com/customer. After installation, launch the software and the main toolkit window will open:

Select the COM port associated with the Sentinel Node and click “Auto-Detect Device on COM Port.” This will open the device configuration window, where all device settings can be configured.SIGNALFIRE Sentinel-yTherm-XXXX Sentinel
Node Thermocouple-3

  1. COM Settings
  2. Node Information
  3. Configurable Node Settings
  4. Register Values

Network Setting
The network is set using the SignalFire Toolkit. The network, network group, and corporate ID/encryption key settings must match those of the gateway for them to communicate.

Encryption

To protect your over-the-air data and prevent tampering, SignalFire networks come with encryption. Legacy products use a Corporate ID, but can be switched over to use an encryption key if the firmware and ToolKit are up to date.
To set up a legacy Sentinel to use encryption, click the checkbox labeled Enable Encryption inside the Set Corporate ID box. All newer Sentinels come with this option enabled with “signalfire” as the default encryption key.

SIGNALFIRE-Sentinel-RTD-Sentinel-Node-RTD-Security-
Sensor-4

The box will then change into a Set Encryption Key box, and it will prompt instead for the encryption key you would like to use. Note that keys may not contain spaces or angle brackets. Enter it and then press Set. If you are setting up a new network, you will need to set the encryption key on all of your devices. If you are adding a Sentinel to a legacy network, you can simply set the Corporate ID without clicking the Enable Encryption box, and it will remain compatible with the older system.
It is also possible to hide your encryption key so it cannot be read. This is the most secure option, but if you forget your key, there is no way to recover it – you have to reset the key on every device on its network. To enable this option, select Set Encryption Key Unrecoverable under the Settings menu.

System Check-In Period
This setting controls how often the node will read the Modbus device and forward the register data to the gateway.

Modbus Sensor Warm-up Time
The sensor warm-up time controls how long power is applied to the Modbus sensor prior to data collection. The default is 2 seconds which is used for most simple sensors, some may require longer warm-up times. Contact your sensor manufacturer or SignalFire for details.

Operating Mode

The Sentinel Modbus node requires that the Sentinel is configured with a list of Modbus registers to be read from the attached sensor using the SignalFire Toolkit application prior to installation.
The preconfigured set of registers is automatically read from the Modbus sensor device and forwarded to the Modbus gateway on a pre-defined schedule (1 minute to 5 minutes is typical). The register data is then buffered in the gateway and is available to be read by the RTU at any time at the same Modbus ID as the attached Modbus device. Unlike other Sentinels, the Sentinel Modbus will not appear on the Gateway’s list of nodes unless it has at least one program step.

Sensor Connections

Wiring Requirements
To ensure intrinsic safety is maintained it is required that the installer follow these guidelines when connecting sensors to the SignalFire node. See pictures for proper wire routing examples.

  • Sensor wires entering the enclosure must be run as pictured.
  • The battery wire must be routed through the battery cable hold-down clamp.
  • Strip the wires so that there is minimal exposed un-insulated wire when inserted into the screw terminal.
  • All wiring should be neat and orderly.

SIGNALFIRE-Sentinel-RTD-Sentinel-Node-RTD-Security-
Sensor-8

Plug the internal lithium battery pack into the connector labeled LITHIUM BATTERY as show below. Be careful to insert the battery connector as pictured with the locking tab facing up.
Forcing the battery connecter in backward or into the SOLAR BATTERY connector can damage the battery pack fuse making it inoperable.

Only connect either the Lithium batter OR the Solay battery. Never connect both at the same time.SIGNALFIRE Sentinel-yTherm-XXXX Sentinel Node
Thermocouple-7

Sensor Connection

Connect the Thermocouple wires to the interface board. Any error with the thermocouple or interface board will be shown in the Status register. See table on Page 9 for details.
SIGNALFIRE Sentinel-yTherm-XXXX Sentinel Node
Thermocouple-8

The Sentinel Modbus node has a single terminal block for connection to a Modbus sensor. The Sentinel has a current limiting resistor of 150 ohms. The voltage available to the sensor depends on the sensor current load. See the graphs below for details:  SIGNALFIRE Sentinel-yTherm-XXXX Sentinel Node
Thermocouple-9

If the Sentinel-Solar is used the maximum load current is limited to 14mA.

RS-485 Modbus Communication

Communication Settings
The Sentinel Modbus needs to have its serial RS-485 parameters set to match the device it’s communicating with. Default settings are a baud rate of 9600bits/s, UART mode 8N1 (8 data bits, no parity bit, 1 stop bit), command timeout of 1000ms, and command pause of 100ms. This should be sufficient for most devices but check your device’s datasheet to confirm. Note that the Gateway and Sentinel’s RS-485 settings are unrelated and do not need to match. SIGNALFIRE Sentinel-yTherm-XXXX Sentinel Node
Thermocouple-10

The Modbus ID should match the ID of the connected Modbus device. Click Find Sensor Modbus ID if the ID of the connected sensor is unknown. Make sure that there are no duplicate Modbus IDs in a given network; the gateway will only cache one set of data for each Modbus ID, so the duplicate will be overwritten.

Modbus Program Steps Configuration
The register set to poll on each check-in must be defined using program steps. The Sentinel Modbus can have up to 34 program steps. A program step consists of a function code, starting address, and number of consecutive registers. Possible function codes are: 

  • 0x01: Read discrete output (limit: 1 coil)
  • 0x02: Read discrete input (limit: 1 coil)
  • 0x03: Read holding register
  • 0x04: Read input register
  • 0x05: Write discrete output SIGNALFIRE Sentinel-yTherm-XXXX Sentinel Node Thermocouple-12

The register address entered is subtracted by the offset in the Register Addressing Mode. The offset can be 0 or 1. For example, with One Based Addressing, a holding register of address 3990 should be entered as function code 0x03, address 3991.

A count of 25 registers per step can be set unless using Enron Modbus. In that case, the limit is 12 registers per step. Keep in mind that one 32-bit floating point register should be read as two 16-bit registers. When writing the steps to the Sentinel, a warning will pop-up if too many registers are requested.
Click Read Steps from Sentinel to view the current program steps in the table. To add a new program step, fill in the next empty line. To delete a step, click on the line number and press the Delete key. Lines can also be copy/cut and pasted. Once all the desired program steps have been entered, click Write Steps to Sentinel to save the changes.
Modbus Program Steps Configuration (Legacy)
If using toolkit version 2.2.18 or earlier, the menu to enter program steps will be different. Click Read Current Program Steps from Device to view the current program steps in the table. They can then be deleted or re-ordered using the buttons to the right of the table. To add a new program step, fill in the 4 boxes at the bottom, and click Add New Program Step. If the step is valid, it will be added to the table. Finally, click Write New Program Steps to Device to save the changes.

Note: In the legacy menu, the Register Addressing Mode is locked to One Based Addressing, so 3990 should be entered as 3991.

Read/Write Modbus Registers
Modbus registers of devices that have an RS-485 interface can be read and written through the Gateway when the device is in remote configuration mode. This is useful for testing or for setting configuration parameters in the end Modbus device. For information on remote configuration, see the Gateway manual. Once the Modbus remote configuration window has been brought up, select ‘Tools’ and then ‘Read/Write Modbus Registers.’

Create the register list by entering the Modbus ID (defaults to the Modbus id of the device), starting address, number of registers and click Apply to Table. The form will populate with the number of registers starting at the start address and a default data type of unsigned 16-bit integer.

Click ‘READ Registers’ to read the current Modbus registers from the device. The Data Type and Register Value fields can be edited, and the changes will be highlighted. Click WRITE Registers to write the changes to the Modbus registers in the device. SIGNALFIRE Sentinel-yTherm-XXXX Sentinel Node
Thermocouple-16

Both 16-bit (default) and 32-bit register sizes are supported. Whenever Modbus registers are read, the register size is changed to match the incoming data. The Data Type pull-down only lists data types that support the register size and unsupported data types in the register list are changed to the default data type for the register size.

Remote Modbus Register Mapping

The Sentinel Node sends data to a SignalFire Telemetry Modbus Gateway. The data that is sent to the gateway is available at the gateway in registers where it can then be read by a Modbus RTU. In addition to the pre-configured registers read from the attached sensor, the Sentinel will send system information in 16-bit registers listed in the table below. This data is accessible at the same Modbus ID as the connected Modbus device.

Status Registers

Register Number| Register Address (Offset)|

Description

---|---|---
49986| 9985 or 65522| Checkin Interval (in seconds)
49987| 9986 or 65523| Status (0=no errors, 1=low battery (3V Threshold), 2=failed sensor read, 3=low battery and failed sensor read)
49988| 9987 or 65524| Major revision number for the mainboard
49989| 9988 or 65525| Minor revision number for the mainboard
49990| 9989 or 65526| Major revision number for the radio
49991| 9990 or 65527| Minor revision number for the radio
49992| 9991 or 65528| High 16 bits of SFTS node address
49993| 9992 or 65529| Low 16 bits of SFTS node address (the radio ID)
49994| 9993 or 65530| Modbus ID readback
49995| 9994 or 65531| Received signal strength of last packet from the Sentinel
49996| 9995 or 65532| Battery voltage of the Modbus client, in millivolts
49997| 9996 or 65533| Minutes until this device will time out, unless new data is received
49998| 9997 or 65534| Number of registers cached for this device
49999| 9998 or 65535| Remote device type. 45 for Sentinel Modbus

Note: The status registers are only available from the 49987-49999 (9986-9998) address range if the Gateway is running firmware 7.52 or higher. 49986 (9985) is available if the Gateway is running firmware 8.28 or higher.

Mounting and Care

The unit comes with a watertight ½” NPT conduit fitting on the bottom mounting plate. The Sentinel is then directly mounted to the sensor with a short section of conduit.

Direct Mount to Sensor with Short Conduit
This mounting method uses a short conduit run from the sensor and the unit is held in place by the conduit.

SIGNALFIRE-Sentinel-RTD-Sentinel-Node-RTD-Security-
Sensor-11

WARNING: The Sentinel must be mounted in a location free of high vibrations. Over time vibrations can damage the Sentinel or battery pack, which could impair its safety ratings. Do not mount directly to continuous vibrating equipment such as pumps or compressors.

Internal Lithium Battery Replacement

Battery Packs can be changed with the node in place.

  1. Open the cover from the enclosure.
  2. Unplug the battery from the PCB, by depressing the locking clip on the connector.
  3. Loosen the screw holding the battery door and slide the old battery out.
  4. Slide in the new battery pack and tighten the battery door screw.
  5. Connect the battery to the main PCB battery connector.
  6. Install the enclosure cover.

WARNING: Use of any battery other than the SignalFire part number 810-0008-02 will impair the protection provided by the equipment.
WARNING: If the internal battery is installed the external solar battery system or other power source may not be connected!

Cleaning Instructions

The outside of the enclosure may be cleaned with water, mild soap, and a damp cloth as needed. High pressure washing is not recommended.
WARNING: Electrostatic Discharge Hazard! Care must be taken to avoid the potential of creating a change on the enclosure or antenna. Do not wipe with a dry cloth. Do not brush against the enclosure with clothing or gloves.

Configuration / Debug
Debug and configuration information is available if a connection is made via the debug port on the main board. A USB converter cable (available from SignalFire) must be used for this interface.  Debug and advanced configuration may be done using the SignalFire Toolkit PC application.
WARNING: Only connect to the debug port in a safe area!

Technical Support and Contact Information
SignalFire Telemetry
140 Locke Dr, Suite B
Marlborough, MA 01752
978-212-2868
support@signal-fire.com 

Revision History

Revision Date Changes/Updates
1.1 10/09/12 Initial release
1.2 11/7/14 Updated entity parameters
1.3 6/5/15 Updated design
1.4 8/1/16 Added section on Encryption
1.5 3/6/17 Added graphs for sensor voltage
1.6 9/13/17 Updated warnings
1.7 1/17/2019 Updated low battery register to general status register Minor

formatting updates
1.8| 3/25/2020| Remote Modbus R/W
1.9| 7/9/2020| Updated Modbus program steps menu, new checkin register
1.10| 5/24/2021| Specified low battery alarm threshold
1.11| 1/20/2022| Updated screen shots. Added usage of Find Sensor Modbus ID button. Added description of register count.
1.12| 6/3/22| Added detail on battery connection

APPENDIX – FCC and IC Statements

Changes or modifications not expressly approved by SignalFire Telemetry, Inc could void the user’s authority to operate the equipment. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.
    Only the supplied coil antenna (Part number 810-0012-01) which is permanently soldered to the PCB may be used. This antenna has a maximum gain of 3dB.

WARNING!
FCC and IC Radiation Exposure Statement:
This equipment complies with FCC’s and IC’s RF radiation exposure limits set forth for an uncontrolled environment under the following conditions:

  1. This equipment should be installed and operated such that a minimum separation distance of 20cm is maintained between the radiator (antenna) & user’s/nearby person’s body at all times.
  2. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.

Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a maximum (or lesser) gain approved for this transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.r.i.p.) is not more than that necessary for successful communication.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals