CLAUDGEN CRXSL CONSORT Wireless controller Installation Guide
- June 5, 2024
- CLAUDGEN
Table of Contents
Recessed Ceiling Heaters
Catalog Numbers
HE7230SL, HE7245SL, HE7260SL,
HE7230RX, HE7245RX, HE7260RX
Installation and Operating Manual
CONSORT Wireless controller CRXSL
SLPB| SLVT| SLVTB
General Information
1.1 Introduction
This instruction manual describes the CLAUDGEN Recessed Warm Air Ceiling
Heaters. The heater is designed for discreet positioning in a suspended 600mm
ceiling within retail or commercial premises. It can fit a recess as shallow
as 210mm.
1.2 General
All installations must be in accordance with the regulations in force in the
country of use.
These instructions must be handed to the user on completion of the
installation.
Installers and service engineers must be able to demonstrate competence and be
suitably qualified in accordance with the regulations in force in the country
of use.
To ensure continued and safe operation it is recommended that the appliance is
serviced annually.
The heater outlet/inlet must not be obstructed during use.
1.3 Electrical Supply
CONSORT CRXSL and SL Controllers
CRXSL | SLPB
| SLVT| SLVTB
---|---|---|---
The electrical supply is 230/240V single phase, Neutral and Earth. The maximum
cable inlet size is 4mm².
It is recommended that the electrical supply to the base unit in the heater is
via an appropriately switched isolator in accordance with the regulations in
force in the country of use and must be via a fused isolator having a contact
separation of greater than 3mm on all poles. There are no exceptions.
BMS control, time switches, room thermostats, and door interlocks can be
installed at the discretion and responsibility of the installer.
All units must be wired in accordance with I.E.E regulations for the
Electrical Equipment of Buildings and the installer should ensure that a
suitable isolating switch is connected to the mains supply.
1.4 Controller SL
models
The HE7230SL, HE7245SL, and HE7260SL heaters are supplied without a
controller. The SL
models will not work without the controller. See section
5.1 for more details.
1.5 Controller RX
models
The HE7230RX, HE7245RX, and HE7260RX heaters are supplied without a
controller. The RX
models will not work without the CRXSL. See section 5.2
for more details
1.6 Location
All units should be installed horizontally. It is recommended that the ceiling
heater is installed within the ceiling void or roof space. Care must be taken
to allow complete free air movement into the inlet grilles of the unit to
ensure the correct working operation of the heater. If the HE7230SL/RX or
HE7245SL/RX heaters are mounted close to the wall or corner the discharge
opening should be facing the wall. The minimum distance from the wall or
corner is 0.8m or 1.2m for the HE7260SL/RX.
1.8 Clearance distances
|
---|---
It is recommended that a minimum clearance of 50mm is allowed around the case
and 30mm above the heater. The clear-ance allows for cable entry and prevents
combustible surfaces from overheating. The minimum mounting height (floor to
the grille) is 2.2m for the HE7230SL/RX,| HE7245SL/RX and 2.5m for the
HE7260SL/RX. The recommended mounting height is 2.5m for the
HE7230SL/RX, HE7245SL, RX, and 3m for the HE7260SL/RX.
1.9 Health and Safety
Sole liability rests with the installer to ensure that all site safety
procedures are adhered to during installation.
Sole liability rests with the installer to ensure that protective safety wear
such as hand, eye, ear, and head protection is used during the installation of
the product.
Do not rest anything, especially ladders against the product.
1.10 Standards
Units conform to the European electrical standard BS EN 60335-2-30
Dimensions
Installation Details.
Fig.1 Air discharge of HE7230SL/RX and HE7245SL/RX
ENSURE THE AIR OUTLET OF HE7230SL/RX AND HE7245SL/RX IS NEAREST TO THE WALL OR
CORNER.| Fig.2 Air discharge of HE7260SL/RX
---|---
The wire or chain used to mount the heater can be attached to 4 of the M6
studs or the 4 x M6 threaded inserts as shown in the diagram.
Electrical Connections.
4.1 Electrical Connections.
These units are suitable for connection to a230/240 Volt 50 Hz single-phase
supply.
The appliance shall be connected to the supply via an appropriate switched
fused double pole isolator having a contact separation of greater than 3mm.
Test for correct operation and refit the cover.
For connection to the mains supply, it will be necessary to open the terminal
cover at the side/ back of the unit to connect the supply from the controls
prior to refitting the cover.
Wire in accordance with the wiring diagrams. For safety reasons, a sound earth
connection must always be made to the unit before it is put to use. The unit
should be wired in accordance with IEE Regulations for the Electrical
Equipment of Buildings.
4.2 Electrical connections for SL and RX models
Fig.8 Heater with the terminal cover open | SLVTB
---|---
Operation.
5.1 SL models
The heaters HE7230SL, HE7245SL, and HE72
60SL can be controlled by CONSORT CRXSL or any SL wireless controller. Each
CRXSL or SL controller can control any number of heaters providing they are in
the RF range. For more details please follow the instructions supplied with
the controller.
CONSORT CRXSL and SL Controllers
CRXSL | SLPB | SLVT | SLVTB |
---|
5.2 RX Models
The heaters HE7230RX, HE7245RX, and HE7260RX can be controlled by CONSORT
wireless controller CRXSL. The heaters will not work without a controller.
Each controller has a unique identification code, it can control an unlimited
number of heaters in the same room and will not interfere with other
controllers within the building. For more details please follow the
instructions supplied with the controller.
CONSORT Wireless controller CRXSL
Servicing & Maintenance.
6.1 Maintenance
ALWAYS ENSURE THAT THE MAIN EXTERNAL ELECTRICITY SUPPLY IS SWITCHED OFF BEFORE
COMMENCING ANY MAINTENANCE ON THIS HEATER.
To obtain the best results from the heater, it is essential to avoid the
accumulation of dust and dirt within the unit on the air inlet and discharge
grilles. For this reason, regular cleaning is necessary.
Cleaning of the fan is best carried out with a soft brush.
The product should be serviced annually.
Servicing shall be undertaken by a competent person.
6.2 General
If the heater does not operate a competent service engineer should be called
to identify the nature of the fault.
All heaters are fitted with motor thermal protection. Other faults in relation
to the element, motor, and wiring should be identified using conventional
fault-finding techniques.
In the event that electrical components are replaced, please ensure that
electrical safety checks in accordance with the regulations in force in the
country of use are undertaken.
6.3 Thermal cut-out
The units are protected from overheating in the event of fan failure or
obstruction of the free airflow, by thermal cutouts. If this happens the
thermal cutouts switch off the appliance. The appliance will not operate until
the heater is disconnected from the main supply and it has cooled down.
If this fault occurs again, refer to section ‘6.4 fault finding’.
6.4 Fault Finding
If the heater will not operate, disconnect it from the mains and arrange
for a certified electrician to attend and investigate the reason.
6.5 Replacing the Fan Heater
a) Remove the grille.
b) Disconnect the internal wiring from the blower
c) Remove the four screws fixing the fan heater assembly to the back of
the case.
d) The fan heater assembly can now be eased forward and removed from the
heater case.
e) Fit replacement fan heater and reassemble in reverse order.
6.6 Spares
It is essential when ordering spare or replacement parts to state the model
number and the serial number on the rating label fixed to the side of the unit
below the terminal cover.
In the interest of progress the Company reserve the right to vary
specifications from time to time without notice. The material listed is
offered subject to the Company’s General Conditions of Sale, a copy of which
can be obtained on request.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>