Altronix AL400ULXB2 UL Listed Sub-Assembly Power Supply/Charger Boards Installation Guide
- June 4, 2024
- Altronix
Table of Contents
ULXB Series
AL400ULXB2 UL Listed Sub-Assembly Power Supply/Charger Boards
Installation Guide
Models Include:
AL400ULXB2
– 12 @ 4A or 24VDC @ 3A| AL1012ULXB
– 12VDC @ 10A
---|---
AL600ULXB
– 12 or 24VDC @ 6A| AL1024ULXB2
– 24VDC @ 10A
Installation Guide
Rev. ULXB-020419
Overview:
Altronix ULXB power supply/chargers convert a 115VAC / 60Hz input to a 12VDC or 24VDC output.
Agency Listings:
**** Altronix Model Number| UL Listed Sub-Assembly for US Installations|
UL Listed Sub-Assembly for Canadian Installations
---|---|---
* UL294 Access Control| **
UL603
Burglar Alarm
| UL1069 Hospital Signaling
and Nurse Call| ****
**** UL1481 Fire Alarm
| CSA C22.2 No.205-M1983
Signal Equipment
AL400ULXB2| | | | | ***
AL600ULXB| N/A
AL1012ULXB| N/A| N/A| N/A
AL1024ULXB2| | N/A|
Altronix Model Number| ANSI/UL 294 7th Ed. Access Control Performance Levels
---|---
Destructive Attack| Endurance Test| Line Security| Standby Power
AL400ULXB2| N/A – sub-assembly| IV| I| II
AL600ULXB| N/A – sub-assembly| IV| I| IV
AL1012ULXB| I| I| I| II
AL1024ULXB2| N/A – sub-assembly| IV| I| IV
Specifications:
Altronix Model Number| Input Rating 115VAC 60Hz| Output Voltage (Current)|
Class 2 Power- Limited Output| Maximum Charge Current
---|---|---|---|---
12VDC| 24VDC
AL400ULXB2| 3.5A| 4A| 3A| | 0.7A
AL600ULXB| 3.5A| 6A| 6A| –| 0.7A
AL1012ULXB| 2.6A| 10A| –| –| 0.7A
AL1024ULXB2| 4.2A| –| 10A| –*| 3.6A
All of the above UL Listed Sub-Assembly Power Supply/Chargers can be installed
in Trove1 and Trove2 Access and
Power Integration Systems and Maximal Series.
For UL603 applications, or if a power-limited output is required in the end-
product application, the DC output from the power supply must be connected to
a separately Listed control unit or accessory board that provides power-
limited outputs. The product(s) providing the power-limited output(s) must be
listed as appropriate for the particular end-product application (fire alarm,
burglar alarm, access control) and wired in accordance with the product’s
installation instructions. Class 1 wiring methods, separation of circuits, and
proper fire-rated enclosures all must be considered when connecting the DC
output of the power supply to the end-product devices. The auxiliary outputs
of these units are
power-limited.
Specifications (cont’d):
Output:
- Filtered and electronically regulated output. Battery Backup:
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Zero voltage drop when switched over to battery backup.
Supervision:
- AC fails supervision (form “C” contacts).
- Low battery and battery presence supervision (form “C” contacts).
Visual Indicators:
-
AC input, DC output, and BAT trouble LED indicators.
Additional Features: -
Short circuit and thermal overload protection. Board Dimensions (L x W x H approximate):
AL400ULXB2:
7.1” x 4.5” x 1.44” (180mm x 114mm x 37mm).
AL600ULXB:
7.1” x 4.5” x 2” (180.3 mm x 114.3 mm x 50.8 mm).
AL1012ULXB:
7.25” x 4.5” x 1.75” (184.2mm x 114.3mm x 44.5mm).
AL1024ULXB2:
8.4” x 4.5” x 1.9” (213.4mm x 114.3mm x 48.3mm).
Stand-by Specifications:
AL400ULXB2:
Output| Burg. Application 4 hr. of Stand-by/ 5 min. of Alarm| Fire
Applications 24 hr. of Stand-by/ 5 min. of Alarm| 60 hr. of Stand-by/ 5
min. of Alarm*| Access Control Applications Stand-by
---|---|---|---|---
12VDC / 40AH Battery| Stand-by = 4.0A Alarm = 4.0A| Stand-by = 1.0A Alarm =
4.0A| Stand-by = 300mA Alarm = 4.0A| 4 hrs./4A
24VDC / 12AH Battery| –| Stand-by = 200mA Alarm = 3.0A| –| –
24VDC / 40AH Battery| Stand-by = 3.0A Alarm = 3.0A| Stand-by = 1.0A Alarm =
3.0A| Stand-by = 300mA Alarm = 3.0A| 4 hrs./3A
AL600ULXB:
Output| Burg. Applications 4 hr. of Stand-by/ 5 min. of Alarm| Fire
Applications 24 hr. of Stand-by/ 5 min. of Alarm| 60 hr. of Stand-by/ 5
min. of Alarm*| Access Control Applications Stand-by
---|---|---|---|---
12VDC / 40AH Battery| Stand-by = 6.0A Alarm = 6.0A| Stand-by = 1.0A Alarm =
6.0A| Stand-by = 300mA Alarm = 6.0A| 4 hrs./6A
24VDC / 12AH Battery| –| Stand-by = 200mA Alarm = 6.0A| –| –
24VDC / 40AH Battery| Stand-by = 6.0A Alarm = 6.0A| Stand-by = 1.0A Alarm =
6.0A| Stand-by = 300mA Alarm = 6.0A| 4 hrs./6A
AL1012ULXB:
Output | Access Control Applications Stand-by |
---|---|
12VDC / 12AH Battery | 30 minutes of backup @ 10A |
AL1024ULXB2:
*** Output| 15 min. of Stand-by/ 5 min. of Alarm| Burg. Applications 4 hr.
of Stand-by/ 5 min. of Alarm| Fire Applications 24 hr. of Stand-by/ 5 min. of
Alarm| 60 hr. of Stand-by/ 5 min. of Alarm| Access Control Applications
Stand-by
---|---|---|---|---|---
24VDC / 12AH
Battery
| Stand-By = 8A Alarm = 10A| Stand-By = 1.5A Alarm = 10A| Stand-By = 200mA
Alarm = 10A| Stand-By = 100mA Alarm = 10A| 20 mins./8A
*** Output| 15 min. of Stand-by/ 5 min. of Alarm| Burg. Applications 4 hr.
of Stand-by/ 5 min. of Alarm| Fire Applications 24 hr. of Stand-by/ 15 min. of
Alarm| 60 hr. of Stand-by/ 15 min. of Alarm| Access Control Applications
Stand-by
24VDC / 65AH Battery| –| Stand-By = 8.0A Alarm = 10A| Stand-By = 1.5A Alarm =
10A| Stand-By = 500mA Alarm = 10A| 4 hrs./8A
Not evaluated by UL.
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA
70/NFPA 72/ANSI, the Canadian
Electrical Code and with all local codes and authorities having jurisdiction.
The product is intended for indoor use only.
-
Refer to Sub-Assembly Installation Instructions for mounting Rev. MS020119.
-
Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Fig. 1e, pg. 4).
-
Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] (Fig. 1a, pg. 4). Use 14 AWG or larger for all power connections (Battery, AC input, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
Keep power-limited wiring separate from non-power-limited wiring (115VAC / 60Hz Input, DC Output (refer to Specifications Chart, pg. 2), Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user-serviceable parts inside. Refer installation and servicing to qualified service personnel. -
Measure output voltage before connecting devices. This helps avoid potential damage.
-
Connect devices to be powered to the terminals marked [+ DC –] (Fig. 1d, pg. 4).
-
For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect the battery to terminals marked [– BAT +] (Fig. 1c, pg. 4).
Note: Separate enclosures must be used for housing 40AH or 65AH batteries.
7. It is required to connect appropriate signaling notification devices to [AC FAIL] & [BAT FAIL] (Fig. 1b, pg. 4) supervisory relay outputs. Use 22AWG to 18AWG wires. AC fail will report in 5 minutes. To delay the report for 6 hours cut the “AC Delay” jumper (Fig. 1, pg. 4).
- Output Voltage Selection Dip Switch. Not applicable for AL1012ULXB and AL1024ULXB2.
- AL1012ULXB terminals marked [– DC +]
- AL1024ULXB2 terminals marked [– BAT +]
Wiring:
Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non-power-
limited wiring (120VAC, Battery).
Maintenance:
The unit should be tested at least once a year for the proper operation as
follows:
Output Voltage Test: Under normal load conditions, the DC output voltage
should be checked for proper voltage level.
Battery Test: Under normal load, conditions check that the battery is
fully charged, and check the specified voltage (12VDC @ 13.2 or 24VDC @ 26.4)
both at the battery terminal and at the board terminals marked [– BAT +] to
ensure that there is no break in the battery connection wires.
Replacing Batteries: Disconnect existing batteries. Connect the battery
to the terminals marked [– BAT +]. Use two (2) 12VDC batteries connected in
series for 24VDC operation.
LED Diagnostics (AL400ULXB2 and AL600ULXB):
Red (DC) | Green (AC) | Red (BAT) | Power Supply Status |
---|---|---|---|
ON | ON | ON | Normal operating condition. |
ON | OFF | ON | Loss of AC. The standby battery is supplying power. |
OFF | ON | OFF | No DC output, Battery Trouble. |
OFF | OFF | OFF | Loss of AC. Discharged or no stand-by battery. No DC output. |
ON | ON | OFF | The battery is missing / Low. |
LED Diagnostics (AL1012ULXB and AL1024ULXB2):
Red (DC) | Green (AC) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Loss of AC. Stand-by is battery supplying power. |
OFF | ON | No DC output. |
OFF | OFF | Loss of AC. Discharged or no stand-by battery. No DC output. |
Terminal Identification:
Terminal Legend | Function/Description |
---|---|
L, G, N | Connect 115VAC to these terminals: L to hot, N to neutral _(Fig. 1a, |
pg. 4).
** + DC – | AL400ULXB2: 12VDC @ 4A or 24VDC @ 3A continuous output
(Power-Limited output) (Fig. 1d, pg. 4).
AL600ULXB: 12VDC or 24VDC @ 6A continuous output (Non-Power-Limited output)
(Fig. 1d, pg. 4).
AL1012ULXB: 12VDC @ 10A continuous output (Non-Power-Limited output) (Fig.
1d, pg. 4).
AL1024ULXB2: 24VDC @ 8A continuous, 10A in alarm (UL1481). 24VDC @ 10A (UL294)
(Non Power-Limited output) (Fig._ 1d, pg. 4).
AC FAIL NO, C, NC
| Used to notify loss of AC power, e.g.connect to audible device or alarm panel. The relay is normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 minute of the event. To delay reporting for up to 6 hrs., cut the “AC Delay” jumper and reset power to unit (Fig. 1b, pg. 4).
BAT FAIL NO, C, NC
| Used to indicate low battery condition, e.g. connect to the alarm panel. Relay is normally energized when DC power is present. Contact rating 1A @ 28VDC. A removed battery is reported within 1 minute. Battery reconnection is reported within 1 minute. Low battery threshold: approximately 21VDC (Fig. 1b, pg. 4).
+ BAT – ***
| Stand-by battery connections (Fig. 1c, pg. 4). AL400ULXB2, AL600ULXB, AL1012ULXB maximum charge current 0.7A. AL1024ULXB2 maximum charge current 3.6A.
- AL1012ULXB terminals marked [– DC +]
- AL1024ULXB2 terminals marked [– BAT +]
UL Model Reference Chart:
UL Listed Sub-Assembly Board | **** Power Supply Series | **** Enclosures |
---|---|---|
AL400ULXB2 | AL400ULX | Maximal11 |
Trove2
AL600ULXB| AL600ULX| Maximal33| BC300, BC400, BC800 (Maximal), Trove1 and
Trove2
AL1012ULXB| AL1012ULX| Maximal55| BC300, BC400, BC800 (Maximal), Trove1 and
Trove2
AL1024ULXB2| AL1024ULX| Maximal77| BC300, BC400, BC800 (Maximal), Trove1 and
Trove2
Notes:
Altronix is not responsible for any typographical errors.