**CLAUDGEN RAC10HL Screen Zone Installation Guide
**
General Information
Warnings
All installations must be in accordance with the regulations in force in the
country of use. These instructions must be handed to the user on completion of
the installation. Installers and service engineers must be able to demonstrate
competence and be suitably qualified in accordance with the regulations in
force in the country of use.
To ensure continued and safe operation it is recommended that the appliance is
serviced annually.
The manufacturer offers a maintenance service. Details are available on
request.
The air curtain outlet/inlet grille must not be obstructed during use.
Any modifications made to the unit not approved by Consort will void any
manufacturers warranty and potentially create a hazard.
Health and Safety
Please read this instructions thoroughly before installing the appliance. Sole liability rests with the installer to ensure that all site safety procedures are adhered to during installation. Sole liability rests with the installer to ensure that protective safety wear such as hand, eye, ear and head protection is used during installation of the product. Ensure that all anchoring points are suitable for the weight of the appliance.
Electrical Supply
For full electrical loadings, please refer to the technical data sheets within
this manual.
It is recommended that the electrical supply to the base unit in the air
curtain is via an appropriate switched isolator in accordance with the
regulations in force in the country of use and via a fused isolator having a
contact separation of greater than 3mm in all poles.
BMS control, time switches, room thermostats and door interlocks can be
installed at the discretion and responsibility of the installer.
All units must be wired in accordance with I.E.E. regulations for the
Electrical Equipment of
Buildings and the installer should ensure that a suitable isolating switch is
connected in the mains supply.
Electrically heated supply is 415V 3 phase, Neutral and Earth. Max cable inlet
size is 4mm² or 6mm² (refer to individual technical specification).
Remote unit is wired to the base unit via a cat5/6 ethernet cable.
Location
All units should be installed horizontally directly over the door opening. It
is recommended that the air curtain is installed on the inside of the
building, within the ceiling void or roof space.
Care must be taken to allow complete free air movement into the inlet grilles
of the unit to ensure correct working operation of the air curtain. The
discharge opening should be as close to the top of the door as possible and
cover the entire door width.
Units can be mounted adjacent to each other to cover the full door opening
across wider entrances.
Clearance Distance
It is recommended that a minimum clearance of 50mm is allowed around the case
sizes detailed below. The clearance allows for cable entry and prevents
combustible surfaces overheating.
The minimum mounting height (floor to grille) is 2m. The maximum mounting
height is 4m.
Standards
The heater conforms to the following standards
Electrical Equipment (Safety) Regulations 2016 SI. 2016 1101
Electromagnetic Compatibility Regulations
2016 SI. 2016 No. 1091
Radio Equipment Regulations 2017 SI. 2017
No. 1206
The Ecodesign for Energy Related Products and Energy Information (Amendment)
(EU Exit)
Regulations 2019. SI. 2010 2617
The Restriction of use of Certain Hazardous
Substances. SI. 2012 No. 3032
The Supply of Machinery (Safety) Regulations
2008 (SI 2008/1597)
Introduction
Introduction
This instruction manual describes the ScreenZone Large Commercial Recessed
range of
air curtains. They are designed for discreet positioning in a suspended
ceiling or bulkhead in the doorways of retail or commercial premises up to 4m
ceiling height.
The air curtains comprise multiple modular blower units 500mm wide and with
nominal maximum power output of 6kW 3Ph 415V.
Models are available in 1000mm, 1500mm and 2000mm lengths, made up of 2, 3 and
4 blower units. For wider doorways, up to 7 air curtains can be easily
interconnected using CAT5/CAT6 RJ45 networking cable.
It is recommended that this control cable is run separately within its own
trunking to avoid external interference.
The air curtain can be controlled by
Touchscreen controller (supplied with the heater), mechanical switches (not
supplied) or BMS.
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE THERE IS A CORROSIVE
ATMOSPHERE.
Mechanical switch Controller
Optional HE8408 mechanical switch. ( not supplied with the heater) More details at Installer wiring section. This controller will provide 2 fan speed and 3 heat setting options.
Touchscreen Controller
Each air curtain is supplied with an electronic controller giving option for 8
fan and 8 heat settings which can be mounted up to 50m from the air curtain.
Optional BMS control, remote thermostats and door interlocks can be installed.
The electronic touch screen controller shown on the picture below allows the
user to control either a single air curtain, or a network of up to 7 air
curtains with the same settings.
The controller is designed to be mounted on a surface double gang back box,
and is powered by an RJ45 connection. The controller will not fit metal or dry
lining back box.
The cable length between the base unit and the controller can be up to 50
metres.
Dimensions
**Air Curtain Dimensions
Dimension in mm
**
Fixing Locations
M8 threaded fixing are located as shown.
20mm knock-out fixings are also available alongside the threaded fixings.
Technical Specifications
4.1 General Data | RAC10 | RAC15 | RAC20 |
---|
Maximum height| M| 4.0
Door width| M| 1.0| 1.5| 2.0
Heat medium| | Electric heating element
Heat output selected at the installation| kW| 8 / 12| 12 / 18| 16 / 24
Fan type| | EC Centrifugal 133 x 180
Fan control| | Electronic fan speed control
Switching type| | Colour Screen Controller with Touch Screen
Weight| kg| 34| 51| 84.0
Electrical Data
Supply voltage| | 415V 3ph 50Hz
Total load| kW| 9 / 12| 18| 24
Max current per phase| A/pha| 13 / 16.5| 16.5 / 25| 25 / 34
Max motor power| W| 196| 294| 392
External fuse size amps| A/pha| 16 / 20| 20 / 32| 32 / 40
Controller| | Touch colour screen controller
Controller wiring| | CAT5 / CAT6 with RJ45 connectors
Cable terminal size| | 10mm² Max|
Mains terminal block position| | Corner of base unit.
Terminals N; L1; L2 & L3
Control terminal position| | Corner of base unit RJ45 type
Air Data
Air volume Air velocity| Max speed| m³/h| 1164| 1475| 2013
Max speed @ 0M| m/s| 8| 5.4
Max speed @ 1M| m/s| 5| 4.2
Max speed @ 2M| m/s| 1.6| 2.1
Max speed @ 3M| m/s| 0.8| 1.0
Delta T| Max speed| °C| 26| 25| 21
Min speed| °C| 20| 19| 19
Noise level @ 3m| Max speed| dBA| 61
Min speed| dBA| 50
Dims Data
Length w/o grille| mm| 1024| 1534| 2044
Width w/o grille| mm| 454
Height| mm| 270
Length with grille| mm| 1082| 1592| 2102
Depth with grille (width)| mm| 270 – 277
Wiring Details
Installer Wiring
Factory Wiring
Network Wiring – Controller
CAT5 cable with RJ45 connectors can be used to network up to 7 air curtains in
a daisy-chain configuration.
The DIP switches 1, 2 and 3 are used to configure each air curtain with a
unique address.
DIP switch setting 000X is reserved for when a controller or BMS is not used.
E.g. air curtain 1 DIP switches set to 1000.
External and door switches are connected between COM and SW1 or SW2.
Their behaviour can be configured in the controller settings menu.
E.g. air curtain 2 DIP switches set to 0100.
All possible addresses are:
1 100X
2 010X
3 110X
4 001X
5 101X
6 011X
7 111X
Network Wiring – Switches
The aircurtain can be also controlled by mechanical switches.
In this configuration touchscreen controller or BMS controls will not work.
To operate heater by mechanical switches, the DIP switches on the main pcb
need to be set to 000X.
The DIP switch 4 is used to select fan speed range.
For installation height of 2 – 3m set the DIP switches to 0000.
For installation height of 3 – 4m set the DIP switches to 0001.
SW1 – on / off
SW2 – low speed / high speed
SW3 – 1/3 heat output
SW4 – 2/3 heat output
CAT5 cable with RJ45 connectors can be used to network up to 7 air curtains in
a daisy-chain configuration.
The 2 DIP switches on all 7 connected aircurtains must be set to different
address.
All possible addresses are:
1 100X
2 010X
3 110X
4 001X
5 101X
6 011X
7 111X
Heat Output Configuration
The air curtain is supplied configured for standard power output.
RAC10HL – 8kW
RAC15HL – 12kW
RAC20HL – 16kW
Fig. 1 Heating Element connection as supplied
This configuration is suitable for installation height from 2 to 3m or where
maximum power usage must be limited for other reasons. As supplied, the each
blower unit configured for 4kW power output. Cable links are supplied to
increase the output to the rated 6kW. Once the links are installed the heaters
are configured to maximum power output.
RAC10HL – 12kW
RAC15HL – 18kW
RAC20HL – 24kW
Fig. 2 Heating Element with links installed
Disassembly / Assembly
-
Each panel of the heater is secured by 2x slotted screws. The other side of the panel is hinged.
After installation, panels can be easily opened for cleaning or servicing.
-
For installation, panels should be removed.
Where two panels meet, the hinge is a machine screw and nut assembly, requiring a 10mm spanner and #2 Pozidrive screwdriver.
The outside edge hinge pin is fixed in place.
-
Remove panels by rotating and sliding inwards from the edge.
-
The surround is held in place by 12 (RAC10HL), 16 (RAC15HL) or 20 (RAC20HL) #2 Pozidrive screws.
-
For installation, remove surround and fit unit back-box into recess first. The lip of the back-box should be recessed 3-10mm from the surface of the ceiling.
-
After wiring and testing, the surround and panels should be refitted.
Installation Details
Mounting
All units should be installed horizontally directly over the door opening. It
is recommended that the air curtain is installed on the inside of the
building, within the open room space against a wall or ceiling.
Care must be taken to allow complete free air movement into the inlet grilles
of the unit to ensure correct working operation of the air curtain. The
discharge opening should be as close to the top of the door as possible and
must cover the entire door width.
Units can be mounted adjacent to each other to cover the full door opening
across wider entrances.
ENSURE AIR OUTLET LOUVRES ARE NEAREST TO DOOR APERTURE.
Electrical Supply
These units are suitable for connection to a 415 Volt, 50Hz 3 phase and
neutral supply for electrically heated 8-24kW models.
The appliance shall be connected to the supply via an appropriate switched
fused double pole isolator having a contact separation of greater than 3mm.
Test for correct operation and refit the cover.
For safety reasons, a sound earth connection must be made to the unit. The
unit should be wired in accordance with IEE Regulations for the Electrical
Equipment of Buildings.
Installation
It is the sole responsibility of the installer to ensure that the points of
attachment to the building are sound. Consultation with the
consultant/architect or owner of the building is recommended to ensure that a
sound, mechanically stable installation is achieved.
All attachments must be capable of supporting the weight of the product .
-
Step 1
Disassemble the heater following section 7. -
Step 2
Either drop rods or catenary wire can be used to fasten the air curtain to the ceiling support structure.
The mounting points can be seen in section 3. -
Step 3
The height between the ceiling face and the edge of the air curtain case needs to be adjusted to 3-10 mm to enable the grille assembly to fit flush against the ceiling. Adjust accordingly. -
Step 4
Refit grille assembly and panels following section 7.
Ensure the grille sits flush against the ceiling.
Installation – Wiring
With hatches open, connect the electrical supply and controller interconnecting wiring to the appropriate terminals on the controller base unit (See relevant wiring diagram section 4).
Fault detection and LEDs
When the air curtains are powered up in standby mode, a green LED on the main
board shows that the 12V power supply is working correctly:
When heat or cold blow is demanded the secondary PCBs are powered. A second
LED on the main PCB shows that the second 12V power supply is working
correctly:
A fault with the auxiliary power is indicated by a flashing orange LED on the
main PCB:
A green LED on the secondary PCBs shows that they are receiving 12V power:
The air curtain monitors the fan speed, power output and heatsink temperature. In the event of a fault the red LED on the secondary PCB flashes:
The red LED flashes a number of times and then pauses. The number of flashes denotes the fault.
Number of flashes | Fault |
---|---|
1 | Power measurement when triacs switched off: |
Response: Auto run motor
2| Motor fault
Response: Disable heating
3| Triac heatsink overheat: Response: Reduce heating
4| Low power measurement when triacs switched on:
Causes: Thermal cutout tripped, blown fuse, missing phase
BMS Connection MODBUS Protocol]
BMS Connection
The heater is compatible with BMS systems using MODBUS protocol.
The connection to BMS system can be made using one of the RJ45 connectors.
Only one means of control can be used at the same time. If BMS is used to
control the heater, the colour screen controller must not be used.
The BMS can control fan speed and heat output and also read and report the
heater status.
Speed can be set in the range of 600 – 1700RPM in 1RPM steps. If the speed is set below 600RMP, the heating element is automatically disabled. Care has to be taken when selecting speed. The fan speed should be always correct for the selected heat output. If the speed is too low, the heater can overheat.
Heat output can be set in the range of 0 – 100% in 1% steps.
MODBUS Protocol
The DIP switches 1, 2 and 3 are used to configure each air curtain with a unique address.
RJ45 cable can be used to network up to 7 air curtains in a daisy-chain
configuration.
DIP switch setting 000X is reserved for when a controller or BMS is not used.
All possible addresses:
1 | 100X |
---|---|
2 | 010X |
3 | 110X |
4 | 001X |
5 | 101X |
6 | 011X |
7 | 111X |
RS485 serial half-duplex interface
MODBUS RTU
9600 baud
8 bits
1 start bit
no parity + 2 stop bits
‘mark’ parity + 1 stop bit
Supported MODBUS function codes:
0x03 read multiple input registers
0x04 read multiple holding registers
0x06 write single holding register
0x10 write multiple holding registers
16 Bit Input Registers:
1 Status
2 Temp 1
3 Temp 2
4 Temp Heatsink
5 Temp External
6 External Switches
Temperatures are formatted as 16 bit signed integers.
Units are sixteenths of a degrees Celsius, as used by DS18B20 temperature
sensors. The hex value 0xF000 is used to denote an invalid reading.
The status register uses bits to indicate faults:
Bit 0 – overheat
Bit 1 – heatsink overheat
Bit 2 – temp sensor 1
Bit 3 – temp sensor 2
Bit 4 – heatsink temp sensor
Bit 5 – remote temp sensor
Bit 6 – L2 on current low
Bit 7 – L2 off current high
Bit 8 – L3 on current low
Bit 9 – L3 off current high
Bit 10 – motor PSU
Bit 11 – motor
Bit 12 – MCU
Bit 13 – connection
Bit 14 – 12V auxiliary power
Bit 15 – main PCB relay
External switches register uses bits to show the state of switches:
Bit 0 – Switch 1
Bit 1 – Switch 2
Bit 2 – Switch 3
Bit 3 – Switch 4
16 Bit Holding Registers:
1 RPM (units revolutions per minute)
2 Power (units percentage 0 –100)
RPM must be set to at least 600, otherwise heating is disabled.
Touchscreen Controller Operation
Home Screen
The home screen provides information about the heater status and all relevant functions.
- Time
- Operating mode
- Heater status
- Door switch status
- Timer status
- Heat output
- Fan speed
- ON / Stand-by button
- Settings menu button
Settings menu
All functions and settings are available from this menu.
Time
The time can be set using the arrow buttons. A coin battery CR1220 maintains the time when power is interrupted. Time is displayed on the home screen and needs to be set to use the timer function.
Lock
PIN function can be enabled to prevent unwanted operation of the heater or
changing the settings.
The PIN can be completely disabled, enabled for settings only or all
functions.
The default Pin is set as 1234, but can be changed using the Change Pin
button. If the PIN is forgotten contact Consort technical help.
Timer
The 7 day timer function allows scheduling automatic switching between on and
stand-by. Each day can be individually enabled or disabled. The timer allows
up to two periods of operation per day. The white bars indicate when the
heater is timed to switch on.
Use the settings buttons to set up the time for each day (see next page), and
the copy button to copy settings from one day to another.
Timer – time schedule
There are 2 timer periods for each day available.
Tapping the slider in the top right corner will change between 1 or 2 time
periods.
The times for the first time periods are on the top of the screen, the times
for the second timer period are on the bottom of the screen. Times can be
adjusted in 15 minute intervals using the buttons.
When the timer is active, an icon will appear on the home screen giving
information about the next switch time.
External switches
There is a provision for 2 remote switches than can be wired into the air
curtain with. The switches must be voltage free type, NO or NC configuration.
SW1 can be connected to a door switch or occupancy sensor installed in the
door area. When the function is activated, the door switch will enable the air
curtain when the door is open and disable it when the door is closed. The
second slider is used to configure the system for the correct switch type.
When the air curtain is disabled by the door switch, the heater will operate
at a low fan speed. This will allow for a fast start-up when the door is
opened.
When SW1 is active, the home screen will show the status of the door switch.
SW2 is intended for a remote switch that can be used to disable the air
curtain from a remote location. Usually this would be a simple BMS or external
timer connection. Once disabled using remote switch the air curtain can’t be
controller by the touchscreen controller and will remain disabled until
enabled remotely.
Operating Mode selection
One of four operating modes can be selected.
Each mode uses a different method of selecting heat and fan settings when the
air curtain is not in stand-by mode. Use the settings button to configure each
mode.
Manual Mode
In manual mode user can select required fan and heat output by tapping + or –
symbols on the home screen next to the fan and heat bars.
There are 8 fan speeds and 8 heat settings available. It is possible set
maximum and minimum limits for fan speed and heat output.
Once limits are set and functions activated, only limited fan speed and heat
output will be available on home screen when in manual mode.
Automatic Mode
Automatic Mode is the best choice for easy to set-up efficiency and comfort. Set the height by moving slider to the required position. The air curtain will run at optimum fan speed and heat output based on the inlet temperature.
Temperature Mode 1
Temperature Mode 1 is very similar to Automatic Mode, with the addition of having an option for adjusting the airflow temperature. With the airflow temperature set in the middle of the scale, this is equivalent to Automatic Mode.
In certain situations, when required, airflow can be increased or decreased by increasing or decreasing the set installation height. Using a higher setting for the installation height will make the air curtain less energy efficient.
Temperature Mode 2
This operating mode is suitable for situations where the heater is used to maintain the room temperature or where the requirement is to adjust the heat output based on the indoor/ outdoor temperature.
This operating mode can use either the internal or supplied external
temperature sensor.
The temperature on the left defines the starting point below which the air
curtain uses full power.
The temperature on the right defines the point above which the air curtain
doesn’t produce any heat. As the measured temperature rises the heat output is
gradually reduced until heater doesn’t produce any heat.
Using the internal temperature, this mode can be used to maintain room
temperature.
With remote sensor installed outside, this mode can be used to compensate for
external temperature.
There is also an option to select fan function after the heater stops
producing heat. Fan can be set to turn off after the heater stops producing
heat or run all the time.
Heater status
The Status screen provides an overview of values from all connected heaters.
The heaters need to be run before some of the values can be calculated.
In the event of a fault a red warning triangle is displayed:
More details are available when tapping the details button. The detailed
status screens are primarily for installers or engineers to help with
installation or fault diagnostics.
The connected heaters screen shows all of the currently connected heaters, in order of address ID. Heaters are connected when the controller is first powered up. In order to connect to newly powered heaters, press Refresh to re- search for heaters.
For each connected heater, up to 3 detailed status screens are available.
These are general status, faults and sensor screens.
The links to the faults and sensor screens are hidden when no faults have been
identified.
The general status screen shows details about the heater and all of the
internal blower units.
The heater needs to be run before some of the values can be calculated.
The faults screen can provide detailed diagnostics of faults for each internal
blower unit.
The sensor screen shows the status of the temperature sensors.
Energy usage
The energy usage screen provides information related to energy used from the day the heater was installed. The values are calculated based 3PH 400V and so will differ from actual energy usage when mains voltage is lower or higher.
Identification
User can set ID number for controller identification. This number is shown on the left hand corner of the home screen. This feature is useful in situation where there are more than one controller side by side.
Declaration Of Conformity
In accordance with UK Government Guidance.
WE HEREBY CERTIFY THAT THE APPLIANCES DETAILED HEREON HAVE BEEN INSPECTED AND
TESTED, AND CONFORM TO THE REQUIREMENTS OF THE FOLLOWING UK STATUTORY
INSTRUMENTS WHERE APPLICABLE:
Electrical Equipment (Safety) Regulations 2016 SI. 2016 1101
Electromagnetic Compatibility Regulations 2016 SI. 2016 No. 1091
Radio Equipment Regulations 2017 SI. 2017 No. 1206
The Ecodesign for Energy Related Products and Energy Information (Amendment)
(EU Exit)
Regulations 2019. SI. 2010 2617
The Restriction of use of Certain Hazardous Substances. SI. 2012 No. 3032
The Supply of Machinery (Safety) Regulations 2008 (SI 2008/1597)
Transposed standards used:
- BSEN55014 (2006)
- BSEN301 489.1 & .3
- BSEN300 220.1 & .2
- BSEN60 730.2.9
- BSEN 60335.1 (2012 )
- BS EN 60335.2.30 (2009)
PART NUMBER AND DESCRIPTION OF APPLIANCE: RAC10HL, RAC15HL, RAC20HL
AIRCURTAINS
NAME OF RESPONSIBLE PERSON: A C REYNOLDS
POSITION: QUALITY ENGINEERING
DATE: 22/03/21
CONSORT EQUIPMENT PRODUCTS LTD.
THORNTON INDUSTRIAL ESTATE, MILFORD HAVEN, PEMBROKESHIRE, SA73 2RT. UK
TEL: +44 1646 692132 FAX: +44 1646 695195. E-MAIL:
ENQUIRIES@CONSORTEPL.COM
WWW.CONSORTEPL.COM
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>