SEALEY SAC32775B 270L BELT DRIVE AIR COMPRESSOR Instructions
- June 5, 2024
- SEALEY
Table of Contents
270L BELT DRIVE AIR COMPRESSOR 7.5HP 3PH
MODEL NO: SAC32775B
Thank you for purchasing a Sealey product. Manufactured to a high standard,
this product will, if used according to these instructions, and properly
maintained, give you years of trouble-free performance.
IMPPORRTATANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY. NOTE THE SAFE
OPERATIONAL REQUIREMENTS, WARNINGS & CAUTIONS. USE THE PRODUCT CORRECTLY AND
WITH CARE FOR THE PURPOSE FOR WHICH IT IS INTENDED. FAILURE TO DO SO MAY CAUSE
DAMAGE AND/OR PERSONAL INJURY AND WILL INVALIDATE THE WARRANTY. KEEP THESE
INSTRUCTIONS SAFE FOR FUTURE USE.
SAFETY
1.1. ELECTRICAL SAFETY
-
WARNING! Electrical installation of the compressor to a 3-phase 415volt supply must only be carried out by a qualified electrician.
Make sure the power supply cable is correctly connected to the earth. It is the user’s responsibility to read, understand and comply with the following:
You must check all electrical equipment and appliances to ensure they are safe before use. You must inspect power supply leads, plugs and all electrical connections for wear and damage. You must ensure the risk of electric shock is minimized by the installation of appropriate safety devices. An RCCB (Residual Current Circuit Breaker) should be incorporated in the main distribution board.
You must also read and understand the following instructions concerning electrical safety. -
The Electricity At Work Act 1989 requires all portable electrical appliances, if used on business premises, to be tested by a qualified electrician, using a Portable Appliance Tester (PAT), at least once a year.
-
The Health & Safety at Work Act 1974 makes owners of electrical appliances responsible for the safe condition of the appliance and the safety of the appliance operator. If in any doubt about electrical safety, contact a qualified electrician.
-
Ensure insulation on all cables and the product itself is safe before connecting to main power supply.
-
Ensure that cables are always protected against short circuits and overload.
-
Regularly inspect power supply, leads, plugs and all electrical connections for wear and damage, especially power connections, to ensure that none are loose.
-
WARNING! IMPORTANT: Ensure the voltage marked on the product is the same as the electrical power supply to be used, and check that plugs are fitted with the correct capacity fuse.
-
DO NOT pull or carry the powered appliance by its power supply lead or output cables.
-
DO NOT pull power plugs from sockets by the power cable.
-
DO NOT use worn or damaged leads, plugs or connections. Immediately replace or have repaired by a qualified electrician.
These particular compressors are supplied without a mains plug. Follow the instructions below regarding the fitting of an appropriate plug.
1.2. Model SAC32775B requires a 415v 3 phase supply and must have an appropriate plug added.
- WARNING! Electrical installation of the compressor to a 3-phase 415 volt supply must only be carried out by a qualified electrician.
Ensure the power supply cable is connected to the Earth.
1.2.1. This product must be fitted with a 3-phase plug wired as illustrated in
(fig.1), wired to an appropriately fused supply.
Connect GREEN/YELLOW wire to Earth ‘E’ Connect BROWN wire to L1 Terminal.
Connect the BLACK wire to L2 Terminal. Connect the GREY wire to L3 Terminal.
- WARNING! It is essential to observe ACW (fig 1) Pulley’s direction on initial start-up. If CW is observed, stop immediately and consult a qualified electrician to invert 2 phases.
NOTE: The cable core colors found in the main cable on this compressor are consistent with Amendment 2 to 7671:2001. When completed, check there are no bare wires, that all wires have been connected correctly and the cable restraint is tight.
DO NOT use this product with a standard extension cable. Only use an ARMOURED extension cable.
IMPORTANT USER INFORMATION! Over-current protection of the power circuit is required in accordance with 7.2 of EN 60204-1:2006. The supply disconnecting device to be in accordance with 5.3 of EN 60204-1:2006.
Ask a qualified electrician about compliance. The use of extension leads to connect these compressors to the mains is not recommended.
1.3. GENERAL SAFETY
-
Familiarise yourself with the application and limitations of the compressor.
-
Ensure the compressor is in good order and condition before use. If in any doubt DO NOT use the unit and contact an electrician/ service agent.
-
WARNING! The compressor must only be serviced by an authorized agent. DO NOT tamper with, or attempt to adjust, the pressure switch or safety valve. DO NOT drill, weld or deform the compressed air tank.
-
Before moving, or maintaining the compressor ensure it is unplugged from the mains supply and that the air tank pressure has been vented.
-
Maintain the compressor in good condition and replace any damaged or worn parts. Use genuine parts only. Unauthorized parts may be dangerous and will invalidate your warranty.
-
Read the instructions relating to any accessory to be used with this compressor. Ensure the safe working pressure of any air appliance used exceeds compressor output pressure. If using a spray a gun, check that the area selected for spraying is provided with an air change/ventilation system.
-
Ensure the air supply valve is turned off before disconnecting the air supply hose.
-
Move the compressor on a pallet or using slings beneath the receiver near to domed ends, employing a forklift truck or wheeled gantry crane. Beware of off-centre loads.
-
Use the compressor in a well-ventilated area and ensure it is placed on a firm surface.
-
Keep tools and other items away from the compressor when it is in use, and keep area clean and clear of unnecessary items.
-
Ensure the air hose is not tangled, twisted or pinched.
-
Keep children and unauthorized persons away from the working area.
-
DO NOT disassemble the compressor for any reason. The unit must be checked by qualified personnel only.
-
DO NOT use the compressor outdoors, or in damp, or wet, locations.
-
DO NOT operate within the vicinity of flammable liquids, gases or solids.
-
DO NOT touch the compressor cylinder, cylinder head or pipe from head to tank as these may be hot.
-
DO NOT use this product to perform a task for which it has not been designed.
-
DO NOT deface the certification plate attached to the compressor tank.
-
DO NOT cover the compressor or restrict airflow around the unit whilst operating.
▲ DANGER! DO NOT direct the output jet of air towards people or animals. -
DO NOT operate the compressor without an air filter.
-
DO NOT allow anyone to operate the compressor unless they have received full instructions.
-
WARNING! The air tank is a pressure vessel and the following safety measures apply:
-
DO NOT tamper with the safety valve, DO NOT modify or alter the tank in any way and DO NOT strap anything to the tank.
-
DO NOT subject the tank to impact, vibration or to heat and DO NOT allow contact with abrasives or corrosives.
-
Drain condensation from the tank daily.
-
WARNING! If an electrical fuse blows, ensure it is replaced with an identical fuse type and rating.
-
When not in use, store the compressor carefully in a safe, dry, childproof location.
INTRODUCTION
The heavy-duty 3-phase compressor is suitable for a professional workshop. A triple cylinder pump system coupled with a 7.5hp motor maximizes performance to keep running costs low compared to single-stage, single-phase models. The pump features heavy-duty full-cast cylinders, capped by alloy heads for improved heat dissipation and long life. Heavy-duty drive guards protect the belt and flywheel that is designed to force air over the pump to aid cooling. Supplied with full CE certification, test certifi cates, and operating/maintenance manual. Includes a drain valve for easy release of condensed water build-up in the tank.
SPECIFICATION
Model No: …………………………………………………..SAC32775B
Air Displacement cfm(L/min): …………………………….29.7(840)
Maximum Free Air Delivery cfm(L/min): ………………26.2(742)
Maximum Pressure: ………………………………….. 145psi(10bar)
Minimum Rated Supply: ……………………………………………32A
Motor Output: ………………………………………………………. 7.5hp
Outlet: ……………………………………………………………..1/2”BSP
Phase: …………………………………………………………………… 3ph
Receiver Capacity: ………………………………………………… 270L
Size (W x D x H): …………………………..1500 x 620 x 1080mm
Speed: …………………………………………………………….. 970rpm
Supply: …………………………………………………………………415V
ASSEMBLY
Unpack the product and check the contents. Should there be any damaged or
missing parts contact you, the supplier, immediately
Refer to the attached parts list.
Save the packing material for future transportation of the compressor. We
recommend that you store the packing in a safe location, at least for the
period of the guarantee. Then, if necessary, it will be easier to send the
compressor to the service centre.
|
---|---
4.1. ATTACH ANTI-VIBRATION MOUNTS
4.1.1. Assemble the anti-vibration mounts to the bottom tank brackets using
the nuts and washers supplied (fig 2).
4.2. ATTACH THE FILTERS
4.2.1. Screw the filter unit into the port openings in each head as shown in
(fig 5).
4.2.2. Place a filter cover over each threaded rod protruding from the back
half of the filter and secure each with a wing nut (fig 5).
OPERATION
WARNING! Ensure that you have read, fully understood and apply Section 1
Safety Instructions.
5.1. IMPORTANT. The use of extension leads to connect this compressor to
the mains is not recommended as the resulting voltage drop reduces motor, and
therefore pump performance and could damage your compressor.
5.2. Confirm that the mains voltage corresponds with the voltage shown on the
compressor data plate.
5.3. The compressor should be operated on a horizontal flat surface, or one
that does not exceed 5° either transversely, and should be in a position that
allows good air circulation around the unit, 1000mm nominal gap.
5.4. Before using the compressor check the oil level by referring to the oil
sight glass (fig 5), if the oil level is not up to the red center mark it
should be further topped up with recommended oil, see section 6.7.
5.5. To top up, undo filler cap (fig 5), top up oil level to required level,
then replace filler cap.
5.6. Take care when selecting tools for use with the compressor. Air tool
manufacturers normally express the volume of air to operate a tool in cubic
feet per minute (cfm). This refers to free air delivered by the compressor
(‘air out’) which varies according to the pressure setting. DO NOT confuse
this with the compressor displacement which is the air taken in by the
compressor (‘air in’).
‘Air out’ is always less than ‘air in’ due to losses within the compressor.
5.7. STARTING THE COMPRESSOR.
5.7.1. To turn the compressor on depressing the green ON button (fi g 6).
5.7.2. To turn the compressor off depress the red button OFF (fi g 6).
5.7.3. Check that the ON/OFF button is in the OFF position.
5.7.4. Plug the mains lead into the mains supply and start the compressor by
depressing the green ON button (fi g 6).
5.7.5. Leave the compressor running with no airline or tools connected. Make
sure that the pressure in the tank rises and that the compressor stops
automatically when the maximum pressure is reached. This value is written on
the specification plate and may take in excess of 5 minutes. The compressor
will now operate automatically. The pressure switch (fig 6) stops the motor
when the maximum tank pressure is reached and restarts it when pressure falls
below the minimum threshold of approximately 2bar (29psi) less than the
maximum pressure.
5.7.6. Stop the compressor by depressing the red button OFF (fi g 6). The
compressed air inside the compressor head will flow out via the airline tube
situated beneath the switch housing. Restart is made easier and prevents the
motor from being damaged.
DO NOT, other than in an emergency, stop the compressor by switching off the
mains power, or by pulling the plug out, as the pressure relief will not then
occur and motor damage may result upon restart. When the compressor runs
correctly and is stopped correctly there will be:
A: A whistle of compressed air when the motor stops.
B: A protracted whistle (about 20-25 seconds) when the compressor starts with
no pressure in the tank.
NOTE: If the motor does not cut in and out, but runs continuously when
using an air appliance, the capacity of the compressor may be too small for
the equipment or tool.
Should the pressure in the main tank exceed the pre-set maximum, the safety
valve (fig 5) will activate.
WARNING! For this reason, DO NOT tamper with, or adjust, the pressure
switch (fig 6) or safety valve (fig 5).
MAINTENANCE
In order to keep the compressor in good working condition, periodic
maintenance is essential.
WARNING! Before performing any maintenance operation, switch off the
compressor, disconnect from the electricity supply and release all air from
the tank.
IMPORTANT!
Failure to carry out maintenance tasks may invalidate the warranty on your
compressor.
6.1. OPERATIONS TO BE CARRIED OUT AFTER THE FIRST 5 WORKING HOURS:
A: Check that all bolts/nuts are tight, particularly those retaining the
crankcase and cylinder head.
6.2. OPERATIONS TO BE CARRIED OUT AFTER THE FIRST 50 WORKING HOURS:
B: Replace the lubricating oil.
6.3. OPERATIONS TO BE CARRIED OUT DAILY:
A: Drain condensation by opening the valve located under the tank (fig 7).
Place a container under the valve and slowly open the valve by turning
counterclockwise.
6.4. OPERATIONS TO BE CARRIED OUT EVERY 100 HOURS
NOTE: Or more frequently, if the compressor operates in a very dusty
atmosphere.
A: Check oil level and, if necessary, top up.
B: Remove the fi lter elements (fi g 3) and clean with compressed air (wear eye
protection). DO NOT operate the compressor without the filters as foreign
bodies or dust could seriously damage the pump.
C: Check for oil leaks.
6.5. OPERATIONS TO BE CARRIED OUT EVERY 200 HOURS:
A: Replace the lubricating oil. For oil specifications see 6.7.
Remove the filler cap (fi g 5) then unscrew the drain plug (fi g 5) and drain the
oil into a suitable waste oil container.
Drain when the compressor is hot so that oil drains rapidly and completely.
Incline compressor to ensure complete drainage.
Replace drain plug and refi ll through the oil fi ller aperture. DO NOT overfi
ll. Replace fi ller cap.
B: Check the automatic cut-out at maximum pressure and the automatic cut-in at
2bar below.
WARNING! Never mix different oils and DO NOT use non-detergent/low-quality
oils as the compressor may be damaged.
WARNING! Dispose of waste oil only in accordance with local authority
requirements.
6.6. OPERATIONS TO BE CARRIED OUT EVERY 500 HOURS:
A: Replace air fi lter (fi gs 3 & 5).
B: Check all tube fi ttings and electrical connections.
6.7. OIL
Recommended oil for compressors, suitable for room temperatures ranging from
+5°C to +25°C.
SEALEY CPO or equivalent SAE 40 compressor oil. Room temperature below +5°C:
SAE 20 compressor oil.
IMPORTANT WARNING – Air contaminants taken into the compressor will aff
ect optimum performance. Example: Body filler dust or paint overspray will clog
the pump intake fi lter and may cause internal damage to pump/motor components.
WARNING! Any parts damaged by any type of contamination will not be
covered by warranty.
6.8. Inspection of pressure tank both inside and out.
Under the PRESSURE SYSTEMS SAFETY REGULATIONS 2000 it is the responsibility of
the owner of the compressor to initiate a system of inspection that both
defines the frequency of the inspection and appoints a person who has specific
responsibility for carrying out the inspection.
TROUBLESHOOTING
FAULT | POSSIBLE CAUSE | REMEDY |
---|---|---|
1A)Pressure drop in the tank | Air leaks at connections | Run compressor to |
maximum pressure, switch off. Brush soap solution over connections and look
for bubbles. Tighten connections showing leaks. If problem persists contact
Authorised Service Agent
1B)Pressure drop in the tank| Air leaks from safety valve| It should be
replaced, unless leaking at a joint
which can be sealed.
1C)Pressure drop in the tank| Air leaks from cylinder head gasket| Check
tightness of head bolts. If leak continues
contact authorised Service Agent
2)Pressure switch valve leaks when compressor is idle| Non-return valve seal
defective| Empty the air tank. Remove the check valve cap,
spring and seal. Clean the seal and its seat, or if
necessary replace the seal (fig 5)
3)Air leaks from tank body or tank welds| Internal corrosion caused by
infrequent tank
draining or nonpermitted modifications to tank| Tank could rupture or explode.
Cannot be repaired DISCONTINUE USE IMMEDIATELY
4A)Motor stops and will not restart| Thermal cut out has operated| Allow unit
to cool for 30 minutes before restarting
4B)Motor stops and will not restart| Supply fuse has tripped| Press trip reset
button (fig 6) and restart unit. If
repeated tripping occurs replace the check valve or contact authorised Service
Agent
5) Compressor stops and does not restart| Motor failure| Contact Authorised
Service Agent
6A)Compressor does not stop at maximum pressure| Pressure switch fault|
Contact Authorised Service Agent
6B)Compressor does not stop at maximum pressure| Filter clogged Head gasket or
valve fault| Replace filter element. Contact Authorised Service Agent
7)Compressor noisy with metallic knock| Bearing or piston damage| Contact
Authorised Service Agent
8)Excessive moisture in the discharged air| High humidity environment| Drain
tank after each use
ENVIRONMENT PROTECTION
Recycle unwanted materials instead of disposing of them as waste. All tools,
accessories and packaging should be sorted, taken to a recycling centre and
disposed of in a manner that is compatible with the environment. When the
product becomes completely unserviceable and requires disposal, drain any
fluids (if applicable) into approved containers and dispose of the product and
fluids according to local regulations.
WEEE REGULATIONS
Dispose of this product at the end of its working life in compliance with the
EU Directive on Waste Electrical and Electronic Equipment (WEEE). When the
product is no longer required, it must be disposed of in an environmentally
protective way. Contact your local solid waste authority for recycling
information.
Note: It is our policy to continually improve products and as such we
reserve the right to alter data, specifications and component parts without
prior notice.
Important: No Liability is accepted for incorrect use of this product.
Warranty: Guarantee is 24 months from purchase date, proof of which is
required for any claim.
Sealey Group, Kempson Way, Suffolk Business Park, Bury St Edmunds, Suffolk.
IP32 7AR
01284 757500
01284 703534
sales@sealey.co.uk
www.sealey.co.uk
© Jack Sealey Limited
Original Language Version
SAC32775B Issue 1 31/03/22
Documents / Resources
|
SEALEY SAC32775B 270L BELT DRIVE AIR
COMPRESSOR
[pdf] Instructions
SAC32775B 270L BELT DRIVE AIR COMPRESSOR, 270L BELT DRIVE AIR COMPRESSOR,
DRIVE AIR COMPRESSOR, AIR COMPRESSOR
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>