systemair 318181 SYSVRF 120 Air Evo C HP Q Outdoor unit Mini VRF Heat Pump Installation Guide
- June 5, 2024
- systemair
Table of Contents
- systemair 318181 SYSVRF 120 Air Evo C HP Q Outdoor unit Mini VRF Heat
- Required tools for installation work
- ATTACHED FITTINGS
- Refrigerant Piping
- Air purge
- Electrical cabling
- Installation Place
- OUTDOOR UNIT INSTALLATION
- Installation space Unit mm
- Moving and installation
- INSTALL THE CONNECTING PIPE
- Refrigerant piping
- Leak Detection
- Heat Insulation
- Connecting method
- Confirmation for the diameters of indoor unit connecting pipes
- Confirmation for the diameters of outdoor unit connecting pipes
- Connection method
- Piping sizes at the branch pipe
- Pipe diameter of the connector in the outdoor unit’s body
- Illustration
- Indoor unit branch pipe
- Main pipe
- Remove Dirt or Water in the Piping
- Airtight Test
- Air Purge with Vacuum Pump
- Refrigerant Amount to be Added
- ELECTRICAL WIRING
- Outdoor Unit Wiring
- Indoor Unit Wiring
- The method of fixing the power cord and signal line
- Indoor unit power supply wiring
- TEST RUNNING
- PRECAUTIONS ON REFRIGERANT LEAKAGE
- Important information for the used refrigerant
- Information requirements for air to air conditioners
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
systemair 318181 SYSVRF 120 Air Evo C HP Q Outdoor unit Mini VRF Heat
Pump
WARNING
- If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
- An all pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
- The appliance shall be installed in accordance with national wiring regulations.
- The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
- An all pole disconnection device which has at least 3mm separation distance in all pole and a residual current device(RCD)with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.
- The power cord type designation is H05RN R/H07RN F or above.
- Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.
- Inappropriate installation may result in water leakage,electric shock or fire.
- Turn off the main power supply switch or breaker before attempting any electrical work.
- Make sure all power switches are off.Failure to do so may cause electric shock.
- Connect the connecting cable correctly.
- If the connecting cable is connected in a wrong way, electric parts may be damaged.
- When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.
- If air or any other has is mixed in refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it may resultingly causes pipe burst and injuries on persons.
- Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.
- Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts.
- Do not store it in a wet basement or expose to rain or water.
- After unpacking the unit, examine it carefully if there are possible damage.
- Do not install in a place that might increase the vibration of the unit.
- To avoid personal injury with sharp edges, be careful when handling parts.
- Perform installation work properly according to the Installation Manual.
- Inappropriate installation may result in water leakage, electric shock or fire.
- When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.
- Install the air conditioner securely in a location where the base can sustain the weight adequately.
- Perform the specified installation work to guard against an earthquake.
- If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
- If refrigerant gas has leaked during the installation work, ventilate the room immediately.
- If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
- After the installation work, confirm that refrigerant gas doer not leak.
- If refeigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.
- Electrical work must be performed by a qualified electrician.
- Make sure the air conditioner uses an exclusive power supply.An insufficient power supply capacity or inappropriate installation may cause fire.
- Use the specified cables for wiring connect the terminals securely fix.
- To prevent external forces applied to the terminals from affecting the terminals.
- Be sure to provide grounding.
- Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
- Conform to the regulations of the local electric company when wiring the power supply.
- Inappropriate grounding may cause electric shock.
- Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
- If a combustible gas leaks, and stays around the unit, a fire may occur.
Required tools for installation work
- Philips screw driver
- Hole core drill 65mm.
- Spanner
- Pipe cutter
- Knife
- Reamer
- Gas leak detector
- Tape measure
- Thermometer
- Mega-tester
- Electro circuit tester
- Hexagonal wrench
- Flare tool
- Pipe bender
- Level vial
- Metal saw
- Gauge manifold Charge hose:R410A special requirement.
- Vacuum pump Charge hose:R410A special requirement.
- Torque wrench
- 1/4(17mm)16N.m (1.6kgf.m)
- 3/8(22mm)42N.m (4.2kgf.m)
- 1/2(26mm)55N.m (5.5kgf.m)
- 5/8(15.9mm)120N.m (12.0kgf.m)
- Copper pipe gauge adjusting projection margin
- Vacuum pump adapter
ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
INSTALLATION FITTINGS
| NAME| SHAPE| QUANTITY
---|---|---|---
Outdoor unit installation| |
1
Outdoor unit owner’s manual| |
1
TECHNICAL DATE MANUAL| | 1
ERP INFORMATION| |
1
Water outlet pipe connector| | 1
Seal ring(8kW)| | 1
Rubber wire ring 10/12kW| | 2
Network matching wires| | 2
Connecting pipe 16kW| | 1
L-shaped pipe14kW| | 1
NOTE
- Check if any accessory in the above figure is missing. All the accessories must be kept properly.
- All the fittings should be Systemair fittings.
- Wired/Remote controller purchase separately
- Outlet sealant purchase separately.
- All the figures in the manual explain only the general appearance and dimensions of the unit.
- The air conditioner you purchased may not be completely consistent with the appearance and functions listed in the figures.
Refrigerant Piping
Piping kit used for the conventional refrigerant cannot be used. Use copper
pipe with 0.8 mm or more thickness for φ9.5. Use copper pipe with 1.0 mm or
more thickness for φ15.9.
Use copper pipe with 1.0 mm or more thickness for φ19.0. Flare nut and flare
works are also different form those of the conventional refrigerant.take out
the flare nut attached to the main unit of the air conditioner, and use it.
Before installation Be careful to the following items before installation.
Air purge
For air purge, use a vacuum pump. Do not use refrigerant charged in the outdoor unit for air purge. The refrigerant for air purge is not contained in the outdoor unit.)
Electrical cabling
Be sure to fix the power cables and indoor/outdoor connecting cables with clamps so that they do not contact with the cabinet, etc.
Installation Place
A place which provides a specified space around the outdoor unit. A place were the operation noise and discharged air are not given to your neighbors. A place that is not exposed to a strong wind. A place that does not block a passage. When the outdoor unit is installed in an elevated position, make sure it’s four feet securely installed. There must be sufficient space for carrying in the unit. A place where the drain water does not make any problem.
CAUTION
Install the outdoor unit at a place where discharge air is not blocked.
When an outdoor unit is installed in a place that is always exposed to a
strong wind like a coast or on a high storey of a building, secure a normal
fan operation by using a duct or a wind shield. When installing the outdoor
unit in a place that is constantly exposed to a strong wind such as the upper
stairs or rooftop of a building, apply the windproof measures referring to the
following examples Install the unit so that its discharge port faces to the
wall of the building. Keep a distance of 2000mm or more between the unit and
the wall surface.
Supposing the wind direction during the operation season of the discharge port is set at right angle to the wind direction.
Installation in the following places may result in some troubles. Do not install the unit in such places below
- A place full of machine oil.
- A place full of sulphuric gas.
- A place where high-frequency radio waves are likely to be generated as from audio quipment, welders, and medical equipment
OUTDOOR UNIT INSTALLATION
Installation place
Please keep away from the following place, or malfunction of the machine may be caused
- There is combustible gas leakage.
- There is much oil (including engine oil) ingredient.
- There is salty air surrounding(near the coast)
- There is caustic gas (the sulfide, for example) existing in the air (near a hotspring)
- A place the heat air expelled out from the outdoor unit can reach your neighbor’s window.
- A place that the noise interferes your neighbors every day life.
- A place that is too weak to bear the weight of the unit
- Uneven place.
- Insufficient ventilation place.
- Near a private power station or high Frequency equipment.
- Install indoor unit, outdoor unit, power cord and connecting wire at least 1m away from TV set or radio to prevent noise or picture interference.
- Install the unit in the place that can offer enough space for installation and maintenance.Don’t install it in the place that has a high requirement for noise,such as the bed room.
The insulation of the metal parts of the building and the air conditioner should comply with the regulation of National Electric Standard.
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. This is to prevent image interference and noise in those electrical appliances. Noise may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is kept.
Installation space Unit mm
8kW
10/12kW
Model | 80 | 100/120 | 140/160 |
---|---|---|---|
A | 910 | 950 | 1040 |
B | 982 | / | 1053 |
C | 390 | 406 | 452 |
D | 345 | 360 | 410 |
E | 120 | 175 | 191 |
F | 663 | 590 | 656 |
G | 712 | 840 | 865 |
H | 375 | 390 | 463 |
I | 426 | 440 | 523 |
Single unit installation
Parallel connect the two units or above
Parallel connect the front with rear sides
Moving and installation
Since the gravity center of the unit is not at its physical center, so please
be careful when lifting it with a sling. Never hold the inlet of the outdoor
unit to prevent it from deforming. Do not touch the fan with hands or other
objects. Do not lean it more than 45°, and do not lay it sidelong. Make
concrete foundation according to the sepecifications of the outdoor
units.(refer to
Fasten the feet of this unit with bolts firmly to prevent it from collapsing
in case of earthquake or strong wind.
NOTE
All the pictures in this manual are for explanation purpose only. They may
be slightly different from the air conditioner you purchased depend on model
.The actual shape shall prevail.
INSTALL THE CONNECTING PIPE
Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements.
Refrigerant piping
CAUTION
Please pay attention to avoid the components while connect to the
connecting pipes.To prevent the refrigerant piping from oxidizing inside when
welding, it is necessary to charge nitrogen, or oxide will chock the
circulation system. The indoor and outdoor connecting pipe interface and power
line outletVavious piping and viring patterns can be selected,such as out from
the front ,the back the side ,and undersurface, etc. The follow display the
locations of several piping and wiring knock off interfaces.
Front out pipe
Side out pipe
Back out pipe
Undersurface out pipe
CAUTION
- Side out pipe: please remove the L-shape metal plate, otherwise can not wiring.
- Back out pipe:please wipe off the piping support rubber blanket beside the inner outlet pipe cover of the machine while back side getting out pipes.
- Front out pipe: cut the frontal hole of the pipe-outlet plate.
- The method of the out pipe in the same way of the back out pipe.
- Undersurface outlet pipe: the knock out should from inside to outside, and then piping and wiring through this.Pay attention to the piping the fat connecting pipe should out from the largest hole, otherwise the pipes will be rubbed. Please do the moth proofing for the knocked out hole, to avoid the pest processing into and destroy the components.
Leak Detection
Use soapy water or a leak detector to check whether air leaks at each joint. A and B indicate check valves of ODU C and D indicate IDU connecting pipe ports.
Heat Insulation
Carry out heat insulation treatment for the pipes at the gas and liquid sides respectively. Pipes on the liquid and air sides have a low temperature during cooling. Take sufcient insulation measures to prevent condensation. The gas side pipe must be treated with the closed-cell foam insulation material, which reaches the non-fammable level of B1 and heat resistance of over 120℃. When the outer diameter of the copper pipe is not greater than Φ12.7 mm, the thickness of insulation layer should be greater than 15 mm. When the outer diameter of copper pipe is equal to or greater than Φ15.9 mm, the thickness of insulation layer should be greater than 20 mm. The attached insulation material for the part of the IDU where the pipe connects must undergo heat insulation treatment that aves no gaps.
Connecting method
Select refrigerant pipe
Pipe definition | Pipe connect position | Code |
---|
Main pipe
| The pipe between outdoor unit to the first branch of indoor unit.|
L1
The main pipes of indoor unit| The pipe after the first branch do not drect connect with the indoor unit.|
L2~L5
The branch pipes of indoor unit| The pipe after the branch connect with the
indoor unit.| a,b,c, d,e,f
Indoor unit branch pipes components| The pipes connect with the main pipe、the
branch pipe and the the main pipe of indoor unit.|
A,B,C, D,E
The first connect methond
The second connect methond
NOTE
Use the special-purpose branch branches provided by Systemair only. Failing
to do so may lead to severe system malfunction. If the distance from the first
branch pipe to the last IDU exceeds 15 m, use connection method 2. The
connection distance between the IDU and branch pipe should not exceed 15 m.
Confirmation for the diameters of indoor unit connecting pipes
- R410A Indoor unit connecting pipes diameters 4.
- Example 1:In the Fig.4-5,The downstream inner units of the L2,and its total capacity is 28×2=56.
- R410A Indoor unit connecting pipes diameters.
Total capactiy of the downstream inner units| Main pipe size mm|
Branch Pipe
---|---|---
Air pipe| Iiquid pipe
A<160| Φ15.9| Φ9.5| FQZHN-01D
160≤A<230
|
Φ19.1
|
Φ9.5
|
FQZHN-01D
Confirmation for the diameters of outdoor unit connecting pipes
R410A outdoor unit connecting pipes diameters.
Total capa- ctiy of The outdoor units| Main pipe size when the tot- al
equivalent piping length of liquid + air side is <90m| Main pipe size when the
tot- al equivalent piping length of liquid + air side is ≥90m
---|---|---
air side
mm
| liquid side mm| The first Line Branch Pipe| air side
(mm)
| liquid side mm| The first Line Branch Pipe
A<155
|
Φ15.9
|
Φ9.5
|
FQZHN-01D
|
Φ19.1
|
Φ9.5
|
FQZHN-01D
155≤A<230
|
Φ19.1
|
Φ9.5
|
FQZHN-01D
|
Φ22.2
|
Φ9.5
|
FQZHN-02D
NOTE
- The straight distance between copper pipe turning and the co ntiguous branch pipe is at least 0.5 m.
- The straight distance between the contiguous branch pipes is at least 0.5 m.
- The straight distance which the branch pipes connected to the IDU is at least 0.5 m.
- Select branch joint
- Select the branch joint according to the total designed capacity of indoor units which it connects to.
- If this capacity is more than that of the outdoor unit, then select the connection according to the outdoor unit.
- The selection of branch header depends on the quantity of branches it connects to.
Connection method
| Gas side| Liquid side
---|---|---
8kW| Flaring| Flaring
10kW| Welding or Flaring| Flaring
12kW| Welding or Flaring| Flaring
14kW| Welding or Flaring| Flaring
16kW| Welding or Flaring| Flaring
Indoor unit| Flaring| Flaring
Branch pipe| Welding or Flaring| Welding or Flaring
Piping sizes at the branch pipe
Refrigerant| Indoor Unit Capacity Ax100W|
Gas Side Φ
|
Liquid Side Φ
---|---|---|---
R410A
| A≤45| 12.7Flaring nut| 6.4(Flaring nut)
A≥56| 15.9Flaring nut| 9.5Flaring nut
Pipe diameter of the connector in the outdoor unit’s body
Piping
MODEL side kW
| Pipe diameter of outdoor unit’s connector mm
---|---
Gas Side| Liquid Side
8| Φ15.9| Φ9.5
10| Φ15.9| Φ9.5
12
|
Φ15.9
|
Φ9.5
14|
Φ15.9
|
Φ9.5
16|
Φ19.1
|
Φ9.5
Outdoor Unit kW| Capacity of
ODU horsepower
| Max.
Number of IDUs
| Sum Capacity
of IDUs horsepower
---|---|---|---
8| 2.5| 4| 50%~130%
10| 3| 6| 50%~130%
12| 4| 7| 50%~130%
14| 5| 8| 50%~130%
16| 6| 9| 50%~130%
CAUTION
The total capacity of the IDUs must not exceed 130% of the load of the ODU.
When the capacity of IDUs is greater than 100% of the load, the output of the
IDUs will be derated.
Capacity ranking | Capacity horsepower | Capacity ranking | Capacity horsepower |
---|---|---|---|
18 | 0.6 | 80 | 2.5 |
22 | 0.8 | 10.5 | 3 |
28 | 1 | 120 | 4 |
36 | 1.25 | 140 | 5 |
45 | 1.7 | 160 | 6 |
56 | 2 |
When the outdoor unit connects one indoor unit.
MODEL kW
| The max height drop(m)| The length of refrigerant pipe m|
The number of bends
---|---|---|---
When outdoor unit is top| When outdoor unit is bottom
8| 10| 10| 8|
less than 10
10| 20| 20| 8
12| 20| 20| 8
14| 30| 20| 8
16| 30| 20| 8
Illustration
Outdoor Unit Take Model 160 for example.
Caution
Suppose in the displayed piping system, the total equi-valent piping length of
air side + liquid side is longer than 90m.
Indoor unit branch pipe
- Inner branch pipes are a~f, the size selection please refers to Table4-6. Note: The max. length of the branch pipe should not longer than 15m.
- The main pipes of indoor unit and the indoor unit branch pipe components
- The downstream inner units of the main pipe L2 are N1, N2, and its total capacity is 28×2=56, the size of pipe L2 isΦ15.9/Φ9.5, and the branch pipe B should be FQZHN-01D.
- The downstream inner units of the main pipe L4 are N3, N4, and its total capacity is 28×2=56, the size of pipe L4 isΦ15.9/Φ9.5, and the branch pipe D should be FQZHN-01D.
- The downstream inner units of the main pipe L5 are N5, N6, and its total capacity is 28+22=50, the size of pipe L5 isΦ15.9/Φ9.5, and the branch pipe E should be FQZHN-01D.The indoor unit below to the main pipe L3 are N3~N6, and its to-tal capacity is 28×3+22=106, the size of pipe L3 isΦ15.9/Φ9.5, and he branch pipe C should be FQZHN-01D.
- The indoor unit below to the main pipe A are N1~N6, and its to-tal capacity is 28×5+22=162, and the branch pipe should be FQZHN-01D, and because the total piping length of liquid + air side is ≥90m, check Table.4-4, and the first branch pipe should apply FQZHN-02D, and according to the principle of maximum value, it should apply FQZHN-02D.
Main pipe
The main pipe L1, the outdoor unit capacity is 16kW, and check the Fig.4-7 to get the size of gas pipe/liquid pipe is Φ19.1/Φ9.5, and aslo the total equivalent length of liquid side and gas side pipes is >90m,then check the Fig.4-4 to get the size of gas pipe/liquid pipe is Φ22.2/Φ9.5, and according to the maximum value principle, it should apply the Φ22.2/Φ9.5. Allowable length and altitude difference of refrigerant pipe
| Pimitted value| Piping
---|---|---
Pipe Length| Total Pipe Length(Actual)| ≤50m(8kW)
≤65m(10/12kW)
≤100m(14/16kW)
| L1+L2+L3+L4+L5+a+b+c+d+e+f
Maximum Piping(L)
| Actual Length| ≤35m(8kW)
≤45m(10/12kW)
≤60m(14/16kW)
|
L1+L2+L3+L4+L5+f(The first connect methond) or L1+L3+L5+f(The second connect methond)
Equivalent Length| ≤40m(8kW)
≤50m(10/12kW)
≤70m(14/16kW)
Pipe Length(from the first line branch pipe to furhtest indoor unit)(m)| ≤20m| L2+L3+L4+L5+f(The first connect methond)
or L3+L5+f(The second connect methond)
Pipe Length(from the nearest branch pipe equivalent length(m)|
≤15m
| a,b,c,d,e
Drop Height
|
Indoor Unit-Outdoor Unit Drop Height(H)
|
Outdoor Unit up
| ≤10m(8kW)
≤20m(10/12kW)
≤30m(14/16kW)
|
Outdoor Unit Down
| ≤10m(8kW)
≤20m(10/12kW)
≤20m(14/16kW)
|
Indoor Unit to Indoor Unit Drop Heihgt(H)| ≤8m|
Note
When the total equivalent piping length of liquid + gas side is ≥90m, it must
increase the size of air side main pipe. Besides, according to the distance of
refrigerant pipe and the over matched state of inner unit, when the capacity
is decreasing it still can increase the gas side main pipe size.
The first cennect methond
The second cennect methond
Remove Dirt or Water in the Piping
Make sure there is no any dirt or water before connectiong the piping to the outdoor units. Wash the piping with high pressure nitrogen, never use refrigerant of outdoor unit.
Airtight Test
Air tightness test nitrogen must be used. (See the fgure on the right for the location of the maintenance access. Increase the pressure from the liquid pipe and gas pipe to 4.0 MPa at the same time not exceeding 4.0 MPa. If the pressure does not drop in 24 hours, the test is passed. When the pressure drops, check the leakage position (after you make sure that there is no leakage, discharge the nitrogen.
CAUTION
Never use oxygen, combustible gas, or poisonous gas in the air tightness
test. To prevent damage to the equipment, the pressure must not be held for
too long.
Air Purge with Vacuum Pump
Use a vacuum pump that can evacuate the pipe to the pressure of less than -100.7 kPa (5 Torr, -755mmHg). When the pump is stopped, do not let the pump oil fow back into the refrigerant pipe. The liquid and gas pipes should be evacuated with a vacuum pump for more than two hours to the pressure of less than 100.7kPa. Then, place the pipes with the pressure of less than 100.7 kPa for more than one hour, and check whether the reading of the vacuum gauge rises. (If the reading rises, there is residual water or gas leakage in the system. The leakage must be checked and solved and the test should be performed again. Water may enter into pipes in the following conditions: the installation is carried out in rainy seasons and the installation period is long; the pipes are condensed inside; rainwater enters the pipes. After the above vacuum drying of two hours, use nitrogen to increase the pressure to 0.05 MPa (vacuum breaking), and use a vacuum pump to decrease the pressure to lower than -100.7kPa or below and hold the pressure for one hour vacuum drying. If the pressure cannot be decreased to lower than -100.7 kPa after two-hour vacuumizing, repeat the vacuum breaking and vacuum process.) After that, place the vacuum pipes for one hour, and then check whether the reading of the vacuum gauge rises.
CAUTION
Use a vacuum pump to perform the vacuumizing process. Do not use refrigerant gas to discharge air. Use a vacuum pump that can vacuumize the pipe to the pressure of less than -100.7 kPa 5 Torr, -755 mmHg. When the pump is stopped, do not let the pump oil fow back into the refrigerant pipe. In order to prevent the entry of impurities, the R410A special tool must be used to ensure the compression strength. Use a flling hose with a top rod to connect to the maintenance access of the check valve or the refrigerant flling port.
Refrigerant Amount to be Added
Calculate the amount of the R410A refrigerant to be added based on the diameter and length of the liquid pipes of the ODU and IDUs.When the outdoor unit connects 1 indoor unit.
Liquid Side Piping Diameter | Refrigerant to be Added Permeter Piping |
---|---|
Φ6.4 | 0.022kg |
Φ9.5 | 0.054kg |
Φ12.7 | 0.110kg |
Φ15.9 | 0.170kg |
Additional refrigerant volume of divergent pipe is 0.1kg per item (Consider the liquid side of divergent pipe only.
ELECTRICAL WIRING
ODU electrical control system connection
CAUTION
Please select power source for indoor unit and outdoorunit respectively The
power supply has specified branch circuit with leakage protector and manual
switch. The outdoor unit model which corresponding to different outdoor unit
power supply should refer to the nameplate.
Outdoor Unit Wiring
The Specification of Power
Power Source | 220-240V~ 1Ph 50Hz |
---|---|
Model | Capicity(kW) |
Power Supply
| Hz| 50| 50| 50| 50| 50
Voltage| 220-240| 220-240| 220-240| 220-240| 220-240
Min.(V)| 198| 198| 198| 198| 198
Max.(V)| 264| 264| 264| 264| 264
MCA| 21.25| 28.75| 35| 40| 40
TOCA| 18.1A| 24A| 29A| 33A| 33A
MFA| 25| 32| 40| 40| 40
Compressor| MSC| Soft start| Soft star| Soft star| Soft star| Soft star
RLA| 9.45| 9.45| 15.5| 15.5| 15.5
OFM| kW| 0.08| 0.17| 0.17| 0.17| 0.17
FLA| 1.0| 1.52| 1.52| 1.52| 1.52
Indoor unit power of one system into the same branch circuit.) Please put the connective wire system between indoor unit and outdoor unit with the refrigerant system together. Use 3 core shielded wire as indoor unit and outdoor unit signal wire. The installation should comply with local electric standard. Power wiring should be engaged by specialized electrician.
CAUTION
Equipment complying with IEC 61000-3-12. A disconnection device having an
air gap contact separation in all active conductors should be incorporated in
the fixed wiring according to the National Wiring Regulation.The reserved
function is indicated in broken line table,users can select it when necessary.
Indoor/Outdoor Unit Signal Wire
Connect the wire according to their numbers. Wrong connection may cause malfunction .
Wiring Connection
Seal the wiring connection with the insulation material , or the condensing dew will be caused.
NOTE
The air-conditioners can connect with Central Control Monitor CCM. Before operation, please wiring correctly and set system address and network address of indoor units.
Wiring Terminal Description
CAUTION
Only the dedicated meter of Systemair can be used on the unit. For the
wiring method of the meter, please consult Systemair’s professional service
personnel. No digital multimeter interface for 8kW; and reserved digital
multimeter interface for 10kW ,12kW, 14kW and 16kW. The arrangement of OAE,
XYE and PQE depends on the unit
Note
The wired controller and centralized controller in the dashed box are optional
accessories. If necessary, please contact the local distributor for purchase.
CAUTION
- When the power cable is parallel to the signal wire, make sure that they are enclosed in respective conduits and are kept a reasonable wire spacing.
- Distance between power cables: less than 10A-300mm;less than 50A-500mm.
- The three-core shielded cable is used as the signal cables of the IDUs and ODU, and the shield layer must be grounded as required.
- The display box and build-out resistor are IDU accessories. The remote controller, centralized controller and wired controller are optional accessories.
- If necessary, contact the local distributor for purchase.
Note
The BP3 series IDUs provide standard remote controllers.
Indoor Unit Wiring
Safety device requirements
- Select the wire diameters( minimum value) individually for each unit based on the table 5-1 and table 5-2, where the rated current in table 5-1 means MCA in table 5-3. In case the MCA exceeds 40A, the wire diameters should be selected according to the national wiring regulation.
- Maximum allowable voltage range variation between phases is 2%.
- Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection,where MFA is used to select the current circuit breakers and residual current operation breakers.
Rated current of appliance(A)
| Nominal cross sectional area mm2
---|---
Flexible| cords| Cable for fixed| wiring
≤3| 0.5 and| 0.75| 1 to| 2.5
3| and| ≤6| 0.75 and| 1| 1 to| 2.5
6| and| ≤10| 1 and| 1.5| 1 to| 2.5
10| and| ≤16| 1.5 and| 2.5| 1.5 to| 4
16| and| ≤25| 2.5 and| 4| 2.5 to| 6
25| and| ≤32| 4 and| 6| 4 to| 10
32| and| ≤50| 6 and| 10| 6 to| 16
50| and| ≤63| 10 and| 16| 10 to| 25
The method of fixing the power cord and signal line
The method of fixing the power cord
8kw
10/12kw
14/16kw
The method of fixing the signal wire
8kw AND 10/12kw
14/16kw The fixed mode of signal wire 8kw and 14/16kw is shown in the figure. The signal wire goes through the wire clamp, and the cable is tightly tied to the clamp with a belt to prevent the signal wire from moving up and down.
- Signal wire is 3-core, polarized wire. Use 3-core shield wire to prevent interference.
- The grounding method now is grounding the closed end of the shield wire and opening (insulating) at the end.
- Shield is to be grounded.
- The control between outdoor unit and indoor unit is BUS type. Addresses is set on field during the installation.
CAUTION
Indoor/Outdoor unit signal wire is low voltage circuit. Do not let it touch
the high voltage power wire and put it to gather with power cord in the same
wire distribution pipe.
NOTE
The wire diameter and continuous length is under the condition that the
voltage vibration is within 2%. If the continuous length is exceed showing
value, choose the wire diameter follow relevant regulation.
Indoor unit power supply wiring
CAUTION
- Refrigerant piping system, indoor unit-indoor unit connection signal wires and indoor unit-outdoor unit connection singal wire are in the same system.
- hen power cord is parallel with signal wire, please put them into separate wire distribution pipes, and leave a proper distance.
- Reference distance: It is 300mm when current capacity of power cord is less than 10A, or 500mm when 50A.
- Please use shield wire as indoor unit/outdoor unit signal wire. Indoor/Outdoor unit signal wire wiring.
TEST RUNNING
Operate according to gist for test running on the electric control box cover.
CAUTION
Test running can not start until the outdoor unit has been connected to the
power for 12hr. Test running can not start until all the valves are affirmed
open. Never make the forced running. Or the protector sits back, danger will
occur.
PRECAUTIONS ON REFRIGERANT LEAKAGE
This air conditioner(A/C) adopts inncouous and nonflammable refrigerant. The locating room of the A/C should big engough that any refrigerant leakage is unable to reach critical thickness. So certain esssential action can be taken on time. Critical thickness the Max. thickness of Freon without any harm to person. Refrigerant critical thickness: 0.44[kg/m ] for R410A.3 Confirm the critical thickness through follow steps, and take necessary actions.
- Calculate the sum of the charge volume (A[kg])
- Total Refrigerant volume of 10HP=factory refrigerant volume + superaddition
- Calculate the indoor cubage (B[m ]) (as the minimum3 cubage
- Calculate the refrigerant thickness.
Counter measure against over high thickness. Install mechanicalventilator to reduce the refrigerant thickness under critical leve ventilate regularly. Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate.
Leak alarm related to mechanical ventilator.
NOTE
Please press constraint cool button to carry out refrigerant recycling
process. Keep the low pressure above 0.2MPa, other wise compressor may be
burnt out.
Important information for the used refrigerant
This product has the fluorinated gas it is forbidden to release to air.
- Refrigerant type: R410A
- Volume of GWP: 2088
- GWP=Global Warming Potential.
Attention
Frequency of Refrigerant Leak Checks 1
For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more,but of less than 50 tonnes of CO2 equipment,at least every 12 months, or where a leakage detection system is installed, at least every 24 months. For equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more,but of less than 500 tonnes of CO2 equipment,at least every six months, or where a leakage detection system is installed, at least every 12 months. For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more,at least every three months, or where a leakage detection system is installed at least every six months. Non hermetically sealed equipment charged with fluorinated greenhouse gases shall only be sold to the end user where evidence is provide that the installation is to be carried out by an undertaking certified person. Only certificated person is allowed to do installation, operation and maintenance.
Information requirements for air to air conditioners
Cooling mode
Information requirements for air-to-air conditioners
Model: SYSVRF 120 AIR EVO C HP Q.Test matching indoor units form, non-duct: SYSVRF CASSETTE 36 Q + 3× SYSVRF CASSETTE 28 Q
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Type compressor driven
If applicable driver of compressor:electric motor
Item
| ****
Symbol
| ****
Value
| ****
Unit
| | ****
Item
| ****
Symbol
| ****
Value
| ****
Unit
Rated cooling capacity| Prated,c| ****
12.22
| ****
kW
| | Seasonal space cooling energy efficiency| η s,c| ****
230.6
| ****
%
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27/19℃ dry/wet bulb| | Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given
outdoor temperatures Tj
Tj=+35℃| Pdc| ****
12.22
| ****
kW
| | Tj=+35℃| EERd| ****
2.83
| ****
–
Tj=+30℃| Pdc| ****
9.10
| ****
kW
| | Tj=+30℃| EERd| ****
4.98
| ****
–
Tj=+25℃| Pdc| ****
5.94
| ****
kW
| | Tj=+25℃| EERd| ****
8.54
| ****
–
Tj=+20℃| Pdc| ****
4.33
| ****
kW
| | Tj=+20℃| EERd| ****
9.06
| ****
–
| | | | | | | |
Degradation co- efficient for air conditioners| ****
Cdc
| ****
0.25
| ****
–
| | | | |
Power consumption in modes other than active mode
Off mode
| POFF| ****
0.017
| ****
kW
| | ****
Crankcase heater mode
| PCK| ****
0.009
| ****
kW
Thermosat-off mode| PTO| ****
0.073
| ****
kW
| | ****
Standby mode
| PSB| ****
0.017
| ****
kW
Other items
Capacity control
| ****
variable
| | For air-to-air air conditioner:air flow rate,outdoor measured| ****
–
| ****
5000
| ****
m3/h
Sound power level,outdoor| LWA| ****
70
| ****
d B
| | | | |
GWP of the refrigerant| | ****
2088
| kg CO2 eq 100years| | | | |
Contact details
|
If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi split air conditioners,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit recommended by the manufacturer or importer.
Heating mode
Information requirements for air-to-air conditioners
Model(s): SYSVRF 120 AIR EVO C HP Q.Test matching indoor units form, non-duct:
SYSVRF CASSETTE 36 Q + 3×SYSVRF CASSETTE 28 Q
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Idication if the heater is equipped with a supplementary heater:no
If applicable:driver of compressor:electric motor
Parameters shall be declared for the anerage heating season,parameters for the
warmer and colder heating seasoms are optional
Item| Symbol| Value| Unit| | Item| Symbol| Value| Unit
Rated heating capacity| Prated,h| ****
13.96
| ****
kW
| | Seasonal space heating energy efficiency| η s,h| ****
169.8
| ****
%
Declared heating capacity for part load at indoor teperature 20℃ and outdoor temperatures Tj| | Declared coefficient of performance or gas utilisation efficiency/auxiliary energy factor for part load at given
outdoor temperatures Tj
Tj =-7℃| Pdh| 7.12| kW| | Tj =-7℃| COPd| 3.01| –
Tj =+2℃| Pdh| 5.06| kW| | Tj =+2℃| COPd| 3.99| –
Tj =+7℃| Pdh| 3.34| kW| | Tj =+7℃| COPd| 6.01| –
Tj =+12℃| Pdh| 3.47| kW| | Tj =+12℃| COPd| 7.34| –
Tbiv=bivalent temperature| Pdh| 7.90| kW| | Tbiv=bivalent temperature| COPd|
3.01| –
TOL=operation temperature| Pdh| 7.12| kW| | TOL=operation temperature| COPd|
1.84| –
Bivalent temperature| Tbiv| -7| ℃| | | | |
| | | | | | | |
Degradation co- efficient for heat pumps()| **
Cdh
| ****
0.25
| ****
–
| | | | |
Power consumption in modes other than “active mode”| | Supplementary heater
Off mode| POFF| 0.017| kW| | Back-up heating capacity(*)| elbu| 1.82| kW
Thermosat-off mode| PTO| 0.011| kW| | Type of energy input|
Crankcase heater mode| PCK| 0.009| kW| | Standby mode| PSB| 0.017| kW
Other items
Capacity control
| ****
variable
| | For air-to-air heat pump:air flow rate,outdoor measured| ****
–
| ****
5000
| ****
m3 /h
Sound power level,outdoor| LWA| 70| d B| | | | |
GWP of the refrigerant| | 2088| kg CO2
eq100year)
| | | | |
Contact details|
If Cdh is not determined by measurement then the default degradation
coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and
performance data may be obtained on the basis of performance of the outdoor
unit ,with a combination of indoor unit recommended by the manufacturer or
importer