LEDone LOC-T88FT-36W 8FT T8 LED Internal Tube Installation Guide

June 5, 2024
LEDone

LOC-T88FT-36W 8FT T8 LED Internal Tube
**Installation Guide

**

LOC-T88FT-36W /38W Installation Guide

ELECTRICAL RATINGS: INPUT RATINGS

  • Voltage: 120-277VAC
  • Frequency: 50/60Hz
  • Current: 422mA
  • Wattage: 36W / 38W
  • Tube Length: 8 foot

ENVIRONMENTAL CONDITIONS:

The T8 LED tube cannot be installed in the rain, wet areas, dusty areas, flammable areas or combustible environments. Please confirm the light fixture meets the level of protection requirements if necessary.

INSTALLATION REQUIREMENTS:

The installation should be done by a licensed electrician. If the tube is Type B, please take the ballast and starter out of the light before installing. The operating temperature is -20 ° C + 40 ° C.

INSTALLATION INSTRUCTIONS:

The T8 tube can only work with the matched voltage.
Type B (ballast by-pass): To replace the traditional fluorescent tube, please reconnect the electric circuit. Please check the
connection instruction image as follows:

  • Step 1: Turn off the power before installing.

  • Step 2: Install the LED tube and make the electrical connection.
    More than one set installation image:

  • Step 3: Affix the field applied the label to the light fixture and install the tube. The tube is a double-ended wiring connection.

WARNINGS:

  • Check if the product is in good condition before installation.

  • The LED tube should not be knocked down or replaced with a driver randomly.

  • The product should not be placed in wet areas, high temperatures, or flammable or combustible environments. They should be in a cool, dry environment.

  • Risk of fire or electric shock
    WARNING: The electrical rating of this product is 120-277Vac. The installer must determine whether they have 120-277V at the luminaire before installation.

  • Risk of fire or electric shock
    WARNING : Installation requires knowledge of luminaries’ electrical systems. If you are not a qualified electrician, do not attempt installation. Contact a qualified electrician.

  • Risk of fire or electric shock
    WARNING:
    Install this product only in the luminaires that have the construction features and dimensions shown in the photographs/drawings.

  • Do not make or alter any open holes in the enclosure of wiring or electrical components during installation.

  • To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.

  • To avoid potential fire or shock hazards, do not use the retrofit kit in luminaires employing shunted bi-pin lamp holders.

    • Note: Shunted lamp holders are found only in fluorescent luminaires with instant-start ballasts. Instant start ballasts can be identified by the words “Instant Start” or “I.S.” marked on the ballast. This designation may be in the form of a statement pertaining to the ballast itself or may be combined with the marking for the lamps with which the ballast is intended to be used. For example, F40T12/IS. For more information, contact the LED luminaires retrofit kit manufacturer.
  • Installers should not disconnect existing wires from the lamp holder terminals to make new connections at lamp holder terminals. Instead, installers should cut the existing lamp holder leads away from the lamp holder and make new electrical connections to the lamp holder lead wires by employing applicable connectors.

Phone: (844) LEDONE6
Fax: 1-510-217-9461
Web: www.ledonecorp.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

LEDone User Manuals

Related Manuals