Whitecroft lighting PK-LEAFCASCADEFLEX Cascade Flex Luminaire Instruction Manual
- June 4, 2024
- Whitecroft lighting
Table of Contents
lighting PK-LEAFCASCADEFLEX Cascade Flex Luminaire
**Instruction Manual
**
Whitecroft Lighting Limited
Burlington Street, Ashton-under-Lyne, Lancashire OL7 0AX
Telephone +44 (0)161 330 6811
Facsimile: +44 (0)161 331 5855
Registered No. 3848973 England
Registered Office: As above
DIMENSIONS
Luminaire Dimensions (mm) & Weights (Kg)
Luminaire Type| Length| Width W| Height H| Weight
(Std)| Weight (Em| Minimum Void
600 x 600 Exposed Tee| 584| 584| 69| 4| 5.5| 180
600 x 600 Spring Tee| 599| 599| 83| 4| 5.5| 90
1200 x 300 SAS 330| 1194| 297| 68| 5.5| 7.5| 110
CABLE CONNECTIONS (Remove the product from packaging & inspect for damage)
-
None Emergency – Connect the mains wiring / Dali cables into the Driver according to the Driver symbols indicated & secure with the supplied cable clamp strain relief.
-
Emergency- (Fig1) Slacken screw (A) on the rear of the body then push & rotate the gear tray to a vertical position.
-
Feed the mains / Dali cables through the gear tray C/E & strain relief clamp & connect to the terminal blocks.
-
Connect the battery cables & note the commission date.
-
If COMEP/Dali system is fully addressable & using a single Dali pair, the Dali terminals must be linked as shown right. (Fig.2)
-
Rotate gear tray back into position & tighten screw (A)
CEILING INSTALLATION
Offer the luminaire body into the ceiling system from below & suspend it from the ceiling grid by either lay-in method or folding out ceiling-specific support tabs as detailed below. NB If necessary, fit a secondary suspension anchor into the hole in the corner (supplied by others)
POD OPTIC / SENSOR REMOVAL PROCEDURE
Should the luminaire cartridge require removal /replacement, please follow the
steps below. It is recommended that this work is undertaken with the luminaire
removed from the ceiling & with the front face of the luminaire protected from
damage.
-
Isolate & disconnect all Mains, Dali, & Sensor cables connected to the Driver or Luminaire gearbox assembly.
-
For canopy-mounted sensor variants, working from the rear of the luminaire, carefully prise off the retaining clip using a suitable tool & remove the sensor/lead from the front face.
-
On variants with a gearbox, separate the gearbox from the canopy by removing the 3 or 4 screws (Fig.9) & detach the earth lead spade from the gearbox.
-
Place a flat-bladed tool between the retaining collars & the spigot where indicated (Fig.10) & force clip inwards whilst turning collars in an anti-clockwise direction to release.
-
Offer the Driver or Gearbox assembly through the aperture in the rear of the canopy to remove from the canopy.
-
Refitting of pod optic/sensor is reverse of the procedure above Nb – No tool is required to fit retaining collars, turn in a clockwise direction until an audible click is heard.
SPECIFICATION
Lamp type: | LED |
---|---|
Output (lm): | 2300 / 3300 / 4300 / 5100 lm nom. Refer to the datasheet on the |
website
Colour Temp:| 4000K / 3000K – Ra80 / Ra90 – Tunable Ra80 (600 Only)
Materials: Body:| Mild steel finished White RAL9003
Optic :| Extruded & Injection Moulded Polycarbonate
Control gear:| Fixed output / DALI / Tunable White
Emergency:| Integral 3hr / COMES
Controls:| Organic Response
Supply:| 220-240v 50/60Hz AC
Ambient Temperature:| 0-25vC
Cable Connection Std:| Max cable section – 3 or 5 core 1.5mm ² (6mm strip
length) Suitable for loop in loop out
Cable connection Em:| Max cable section – 4 or 6 core 2.5mm ² (8mm strip
length) Suitable for loop in loop out
Ingress protection:| IP44 Front Face / IP20 Rear Face
Wattage:| Refer to the datasheet on the website
Ceiling Integration:| 600XTT24 & T15 Exposed Tee ( 38mm & 43mm high main
runners only)
SAS 130 Alugrid15/16 &15/08 600ST SAS 120, SAS 150, Burgess H4 1200 SAS 330
Optional adjustable suspend brackets available for other ceiling types –
LUMAFIXBKTKIT
Electrostatic Sensitive Device
Do Not Cover Luminaire With Thermal Insulation
GENERAL INFORMATION
- A qualified electrician, in accordance with IEE wiring regulations, should carry out connection to mains wiring
- Observe ESD precautions during installation.
- Emergency luminaires must be EARTHED.
- Ensure that the rated voltage and frequency requirements are compatible with the available mains supply.
- Cleaning of lenses should be carried out using clean, soft and lint-free cloths and anti-static cleaning fluid
- Do not carry out a high voltage insulation test, i.e. 500/1000v this may damage internal components.
- Batteries must be replaced by a qualified electrician when they do not meet the rated duration.
- Dali control cables must be double insulated & have an equivalent rating to the supply cable.
- The light source contained within this luminaire shall only be replaced by the manufacturer, his agent or a similarly qualified person
- The Luminaire body will become hot under normal operating conditions. Allow cooling before undertaking any necessary maintenance work.
- Ensure that the specified ceiling system is of sufficient strength to support the weight of the luminaire.
- Holes are situated in each of the optical cartridge endcaps to ensure drainage of any water ingress.
Nb Do not support luminaire from cross tees – Support from main runners only!
FURTHER INFORMATION
TECHNICAL SUPPORT
Telephone: 0161 331 5700
E-mail:technical@whitecroftlight.com
http://[www.whitecroftlighting.com/](http://www.whitecroftlighting.com/)